Intesis DALI to BACnet Server gateway
Order Codes:INBACDAL0640200 (64 ballasts, 1 DALI channel)INBACDAL1280200 (128 ballasts, 2 DALI channels)
HOW IT WORKS
The Intesis INBACDAL***0200 Gateway has been specially designed to work as a translator between a DALI installation and BACnet IP or BACnet MSTP based control and monitoring systems.
Intesis acts as a master in the DALI bus, allowing both BACnet IP and BACnet MSTP client/master devices to read and write on all configured DALI signals.
BACnet MSTP devices are connected to the serial port of the gateway, while BACnet IP devices are connected to the Ethernet port. On the DALI side, the gateway simulates a DALI-2 master device allowing other DALI/DALI-2 devices to be present in the DALI channels.
Configuration project and DALI commissioning is done through Intesis MAPS.
FEATURES
- Handles conversion between BACnet (IP & MSTP) and DALI/DALI2 ballasts and DALI-2 sensors (occupancy and light instances)
- Support for BACnet IP or BACnet MSTP, not both simultaneously*
- Designed following DALI IEC 62386 standard and certified by DiiA
- Supports parts 201, 202 y 207 for ECGs
- Supports parts 303 and 304 for Sensors
- DALI line scan (ballast detection) and commissioning
- Configuration through IP or USB (Console) port
- Front cover LED indicators to provide easy to check communication status on both the Ethernet and serial ports
- Includes Intesis MAPS with automatic updates for both Intesis MAPS and Gateway’s firmware* INBACDAL1280200 does not offer BACnet MSTP communication
INTEGRATION EXAMPLE
VERSION SUPPORT 1 DALI CHANNEL
VERSION SUPPORT 2 DALI CHANNELS
CONNECTIONS
PROTOCOLS
DALI is an industry-standardized protocol, for digital lighting control, and is specified in the multi-part international standard IEC 62386 The digital nature of DALI allows two-way communication between devices, so that a device can report a failure, or answer a query about its status or other information. Wiring is relatively simple; DALI power and data is carried by the same pair of wires, without the need for a separate bus cable For further information, please visit https://www.digitalilluminationinterface.org |
BACnet is the Data Communication Protocol for Building Automation and Control Networks. Developed under the auspices of the American Society of Heating, Refrigerating and AirConditioning Engineers (ASHRAE). BACnet is an American national standard, a European standard, a national standard in more than 30 countries and an ISO global standard. The protocol is supported and maintained by ASHRAE Standing Standard Project committee 135. For further information, please visit www.bacnet.org |
COMMUNICATION
BACnet |
DALI | ||
MSTP |
IP |
||
Connection | EIA485 (3 wire isolated)9.6, 19.2, 38.4, 57.6, 76.8, 115.2kbps | 10BASE-T100BASE-TX10 Mbps100 Mbps | DALI |
Data rate | 1.2 kbps | ||
Data Types&Functions supported | Object types0-AO (Analog Output) 1-AI (Analog Input)2-AV (Analog Value)3-BO (Binary Output)4-BI (Binary Input)5-BV (Binary Value)13-MI (Multistate Input)14-MO (Multistate Output)15-MV (Multistate Value) | Functions
Trend Logs Calendars Schedules |
Part 201: Fluorescent lights (DALI type 0)Part 202: Emergency lights (DALI type 1)Part 207: LED modules (DALI type 6)Part 103: Control devices Part 303: Occupancy sensorsPart 304: Light sensors |
ELECTRICAL & MECHANICAL FEATURES
Enclosure | Plastic, type PC (UL 94 V-0)Net dimensions (dxwxh): 90x88x56 mmRecommended space for installation (dxwxh): 130x100x100mmColor: Light Grey. RAL 7035 |
Mounting | Wall.DIN rail EN60715 TH35. |
Terminal Wiring (for power supply and low-voltage signals) | Per terminal: solid wires or stranded wires (twisted or with ferrule)1 core: 0.5mm2… 2.5mm22 cores: 0.5mm2… 1.5mm23 cores: not permittedIf cables are more than 3.05 meters long, Class 2 cable is required |
Power | 1 x Plug-in screw terminal block (3 poles)Positive, Negative, Earth24VDC +/-10% |
Ethernet | 1 x Ethernet 10/100 Mbps RJ452 x Ethernet LED: port link and activity |
Port A | 1 x DALI port (Plug-in screw terminal block orange 2 poles)1500VDC isolation from other portsDALI guaranteed power: 235mAVoltage rating: 16VDC1 x Plug-in screw terminal block green (2 poles)Reserved for future use |
Switch A(SWA) | 1 x DIP-Switch for serial EIA485 configuration: Reserved for future use |
PORT B | INBACDAL06402001 x Serial EIA232 (SUB-D9 male connector)Reserved for future use1 x Serial EIA485 Plug-in screw terminal block (3 poles)A, B, SG (Reference ground or shield)1500VDC isolation from other ports(except PORT B: EIA232)INBACDAL12802001 x Serial EIA232 (SUB-D9 male connector) Reserved for future use1 x DALI port (Plug-in screw terminal block green 2 poles) 1500VDC isolation from other portsDALI guaranteed power: 235mAVoltage rating: 16VDC |
Switch B(SWB) | 1 x DIP-Switch for serial EIA485 configuration: Position 1:ON: 120 Ω termination activeOff: 120 Ω termination inactivePosition 2-3:ON: Polarization activeOff: Polarization inactive |
Battery | Size: Coin 20mm x 3.2mmCapacity: 3V / 225mAhType: Manganese Dioxide Lithium |
Console Port | Mini Type-B USB 2.0 compliant1500VDC isolation |
USB port | Type-A USB 2.0 compliantOnly for USB flash storage device(USB pen drive)Power consumption limited to 150mA(HDD connection not allowed) |
Push Button | Button A: Check the user manualButton B: Check the user manual |
Operation Temperature | 0°C to +50°C |
Operational Humidity | 5 to 95%, no condensation |
Protection | IP20 (IEC60529) |
LED Indicators | 10 x Onboard LED indicators2 x Run (Power)/Error2 x Ethernet Link/Speed2 x Port A TX/RX2 x Port B TX/RX1 x Button A indicator 1 x Button B indicator |
Web: www.intesis.com
© HMS Industrial Networks S.L.U – All rights reservedThis information is subject to change without notice
[xyz-ips snippet=”download-snippet”]