Backflow PreventersBraukmann BA300Backflow Preventerwith flanged connections
APPLICATION
Backflow preventers of this type are suitable for the protection of drinking water systems against back pressure, backflow, and back-siphonage.The backflow preventer protects drinking water for fluids up to and including liquid category 4 to EN 1717.They can be used for residential buildings, industrial and commercial purposes within the scope of their specification.The powder-coated ductile iron housing provides increased corrosion protection.
APPROVALS
- DVGW
- BELGIQUE
- NF
- KIWA
- WARS
- SVGW
- VdS (BA300-80ZVDS)
- VA-ETA
SPECIAL FEATURES
- LEAD-FREE: Pb content of all materials less than 0.1 %
- Optimal protection of the drinking water supply system
- Easy access to all internal components
- Powder-coated inside and outside – Powder used is physiologically and toxicologically safe
- Easy Maintenance due to optimized construction
- Triple security – two check valves and a discharge valve separate the backflow preventer into three pressure zones
- Few individual parts
- Lightweight
- Standardized discharge connection
- ACS certified
- All materials are KTW approved
- Approved by OTH (Hungary)
TECHNICAL DATA
Media | |
Medium: | Drinking water |
Connections/Sizes | |
Connection size: | DN65 – DN200 |
Discharge pipe connection: | DN150 |
Pressure values | |
Min. inlet pressure: | 1.5 bar |
Max. operating pressure: | 10 bar |
Operating temperatures | |
Max. operating temperature
medium: |
65 °C (WRAS 60 °C) |
Specifications | |
Installation position: | Horizontal with discharge
valve downwards |
Product Specification Sheet • EN0H-1242GE23 R0421 • Subject to change
CONSTRUCTION
Overview | Components | Materials |
1 Three ball valves for theconnection of a differentialpressure gauge | Brass | |
2 Inlet/Outlet check valves | Stainless Steel | |
3 Housing | Ductile iron, powder-coatedwith polyamide | |
4 Discharge valve | CW626N with stainless steelseat | |
5 Pressure control line | Polyethylene with stainlesssteel braid(BA300-80ZVDS stainlesssteel) | |
Not depicted components: | ||
Diaphragm | EPDM | |
Sealing washers | EPDM |
METHOD OF OPERATION
BA-type backflow preventers are divided into three pressure zones. The pressure in zone1 is higher than in zone 2, which in turn is higher than in zone 3. A discharge valve is connected to zone 4 which opens at the latest when the differential pressure between zones 5 and 6 drops to 0.14 bar. The water from zone 7 discharges to the atmosphere, both check valves close and therefore separate zone 8 from zone 9 and 10. In this way, the danger of backpressure or back-siphonage into the supply network is prevented. The pipework connection is interrupted and the drinking water network is protected.
TRANSPORTATION AND STORAGE
Keep parts in their original packaging and unpack them shortly before use.The following parameters apply during transportation and storage:
Parameter | Value |
Environment: | clean, dry, and dust-free |
Min. ambient temperature: | 5 °C |
Max. ambient temperature: | 55 °C |
Min. ambient relativehumidity: | 25 % * |
Max. ambient relativehumidity: | 85 % * |
INSTALLATION GUIDELINES
Setup requirements
- Install shut-off valves before and after the backflow preventer
- Install backflow preventer downstream of the filter or strainer– This protects the appliance against dirt
- Install in horizontal pipework with the discharge valve downwards
- Ensure good access– Simplifies maintenance and inspection
- In order to avoid flooding, it is recommended to arrange a permanent professionally dimensioned wastewater connection
- The installation environment should be protected against frost and ventilated well
- Install discharge pipework that has adequate capacity
- These armatures need to be maintained regularly
Installation Example
Connection sizes: | |||||
DN: | 65 | 80 | 100 | 150 | 200 |
inch: | 12/2″ | 3″ | 4″ | 6″ | 8″ |
Min. clearance above backflowpreventer: | 650 mm | 650 mm | 650 mm | 650 mm | 650 mm |
Clearance from wall: | 160 mm | 160 mm | 160 mm | 200 mm | 200 mm |
TECHNICAL CHARACTERISTICS
Pressure drop characteristics
DIMENSIONS
Overview
Parameter | Values | |||||
Connection sizes: | DN | 65 | 80 | 100 | 150 | 200 |
Weight: | kg | 23.9 | 32.7 | 44.6 | 70.9 | 114.1 |
Dimensions: | L | 356 | 440 | 530 | 630 | 763 |
H | 157 | 172 | 190 | 224 | 259 | |
h | 246 | 275 | 296 | 314 | 346 | |
T | 77 | 77 | 77 | 77 | 77 | |
F* | 185 | 200 | 220 | 285 | 340 | |
Nominal flow rate at Δp = 1.0 bar: | m3/h | 35.8 | 54.3 | 108 | 190.9 | 339.3 |
Discharge flow rates in the event of failure: | m3/h | 35 | 35 | 35 | 35 | 35 |
Note:1 to 3 see chapter Method of operationNote All dimensions in mm unless stated otherwise.Note:* F = width
ORDERING INFORMATION
The following tables contain all the information you need to make an order of an item of your choice.When ordering, please always state the type, the ordering or the part number.OptionsThese backflow preventers are available in the following sizes: DN65, DN80, DN100, DN150, DN200.
- standard– not available
BA300-…A | BA300-80ZVDS | |
Connection type: | Standard version, connection sizes DN65 – DN200Connection with flanges, PN10 | • |
with VdS certificate VdS No.: G417057 DN80 | • |
Note: … = space holder for connection size
Description | Dimension | Part No. |
TKA295 | Test kitAnalog pressure measuring device with differential pressure display. With case and accessories, ideal for inspection and maintenance of backflow preventer type BA | |
TKA295 |
Spare PartsBackflow Preventer BA300, from 2011 onwards
Overview | Description | Dimension | Part No. |
1. Inlet check valve | |||
DN65 | 904052 | ||
DN80 | 904053 | ||
DN100 | 904054 | ||
DN150 | 904055 | ||
2. Outlet check valve | |||
DN65 | 904057 | ||
DN80 | 904058 | ||
DN100 | 904059 | ||
DN150 | 904060 | ||
DN200 | 904061 | ||
3. Discharge valve | |||
DN65 – | 904062 | ||
DN200 | |||
4. Pressure control line | |||
DN65 | 904063 | ||
DN80 | 904064 | ||
DN80* | 904073 | ||
DN100 | 904065 | ||
DN150 | 904066 | ||
DN200 | 904067 | ||
5. Sealing set | |||
DN65 | 904068 | ||
DN80 | 904069 | ||
DN100 | 904070 | ||
DN150 | 904071 | ||
DN200 | 904072 | ||
6. Retaining Clip and Ring | |||
DN65 | 904192 | ||
DN80 | 904193 | ||
DN100 | 904194 | ||
DN150 | 904195 | ||
DN200 | 904196 |