Honeywell MIDAS-M Multi Gas Transmitter User Guide

QUICK REFERENCE GUIDE

MIDAS-M MULTI GAS TRANSMITTERFixed Single Point ExtractiveMulti-Gas Transmitter

Introduction

The Midas-M® is a Fixed Extractive Single Point with 4-in 1 Multi-Gas Detector that draws a sample locally or from a remote point to a sensor cartridge that is located inside the detector’s chassis. A wide range of toxic, flammable, and oxygen gas sensor cartridges are available that enable the detection of gases used or generated in the Semiconductor and other manufacturing industries.NOTE: Midas-M is shipped from the factory with the security function disabled. We strongly recommend enabling this function for the safe use of the detector. To enable it, select Set up > Security and type an 8 character password.NOTE: Instrument grounding is required to ensure stable performance and to limit the effects of radiofrequency interference before installation.

Safety

CAUTIONFailure to observe the following precautions can cause injury to persons or damage to property:

  • To minimize the risk of electrostatic charging, provide a suitable ground connection, and install the equipment in such a way that no accidental discharges occur.
  • When Midas-M reaches the end of its life, it should be disposed of by local regulations.
  • Do not use cleaning solvents or abrasives to clean the gas detector.
  • Do not attempt to modify the product in any way from the manufacturer’s design or specification. Warranty will be void and malfunction of the gas detector may result.
  • Use only genuine spare parts and accessories with Midas-M. Malfunction may result if non-standard parts are used.
  • • Midas-M is suitable for ordinary locations only and must not be installed in hazardous locations.
  • Installation must be by the recognized standards of the appropriate authority in the country concerned. For Europe, see  EN60079-14, EN60079-29-2, and EN61241-14. For installations in North America, the National Electrical Code  (NFPA 70) should be strictly observed. All the appropriate local and national regulations should be observed.

Approvals

  • Electrical UL/CSA/IEC/EN 610101
  • EMC EN 50270
  • ROHS

What’s in the Box

  • 1 Transmitter device
  • 2 Tubes (Large box only)
  • 1 Quick Reference Guide

Overview

1. Power LED 7. Bar graph for gas concentration display
2. Alarm 1 LED 8. Entry indicator for menu operation
3. Alarm 2 LED 9. Gas concentration
4. Fault LED 10. Unit
5. Selected channel number indicator for menu operation 11. Gas name, menu, fault message
6. Device status icons 12. Buttons
Wireless Connected Fault
Bluetooth Connected Inhibit
Internal pump running Bump test in progress
Cancel
Accept
Up
Down

Mounting the Transmitter Device

  1. Open the door
  2. Remove two screws
  3. Carefully pull main chassis forward
  4. Drill two holes 2.2 in
  5. • Partially screw the fixings into the mounting surface.• Place the mounting bracket assembly over the screws, so they passthrough the mounting holes and then slide down to locate in the slots.• Tighten the screws to secure the mounting bracket assembly.
  6. • Align the rounded corner at the lower of the main module with the similar rounded corner at the bottom of the mounting  bracket assembly• Slide the main module backward while pushing the main module up after connecting with a mounting bracket so that the PCB and connector and tubes engage simultaneously.
  7. Ensure the PCB, connector, and tubes are fully engaged by firmly pushing the main chassis horizontally backward on the mounting bracket assembly. DO NOT PUSH ON THE LCD AS THIS MAY DAMAGE IT.
  8. • Align the two fixing screws located at the bottom of the chassis with the screw threads on the mounting bracket assembly.• Tighten the screws to secure the chassis to the mounting bracket assembly.
  9. Remove the internal packing card securing the pump. Failure to remove this packing will result in damage to the Midas-M detector.

Transmitter Terminals

TerminalNumber Function Description
1 24Vdc Input 0Vdc
2 24Vdc Input +24Vdc
3 mA output – Channel 1 COM
4 mA output – Channel 1 mA-
5 mA output – Channel 1 mA+
6 mA output – Channel 2 COM
7 mA output – Channel 2 mA-
8 mA output – Channel 2 mA+
9 mA output – Channel 3 COM
10 mA output – Channel 3 mA-
11 mA output – Channel 3 mA+
12 mA output – Channel 4 COM
13 mA output – Channel 4 mA-
14 mA output – Channel 4 mA+
15 Relay 1 Normally Closed
16 Relay 1 Common
17 Relay 1 Normally Open
18 Relay 2 Normally Closed
19 Relay 2 Common
20 Relay 2 Normally Open
21 Relay 3 Normally Closed
22 Relay 3 Common
23 Relay 3 Normally Open

Commissioning

WARNINGBefore carrying out any work, ensure local and site procedures are followed. Ensure that the associated control panel is inhibited to prevent false alarms. The following procedure should be followed carefully and only performed by suitably trained personnel.

  1. Ensure the detector is wired correctly.
  2. Ensure that the correct sensor cartridge is fitted. (If the cartridge has not been stored at room temperature, allow one hour  for equilibration.)
  3. Ensure the on/off switch on the bottom of the mounting bracket assembly is in the on position.
  4. Apply power to the system.
  5. After the startup routine, the detector will display the normal operating mode.
  6. Perform a leak test to ensure all connections are secure.
  7. Waiting…’ will be displayed on booting time.
  8. Allow the detector to stabilize until the ‘Warm-up’ message is no longer displayed after booting. The maximum warm-up time is dependent on the sensor type. Refer to individual cartridge datasheets. Warm-up times are typically much faster.
  9. Ensure the correct ID code is selected in Set-up -> alarm menu
  10. If this is a first-time startup, the “Detect New Cartridge ~” message could be displayed. Press the ‘O’ button to clear themessage.

Specifications

Operating Temperature: 0°C~40°C
Physical:
Size (unit with Sensor cartridge) 136 mm(H) x 83 mm(W) x 152 mm (D) (5.35 x 3.27 x 5.98 in)
Weight – Sensor cartridge 0.17 ~ 0.22 kg (0.38 ~ 0.49 lb) dependent on sensor type
Optional Relay Dimensions:
Size 137 mm (H) X 84 mm (W) X 41 mm (D) (5.39 X 3.31 X 1.61 in)
Weight 0.31 kg (0.68 lb)
Power Requirements:
Operating Voltage 24 VDC Nominal 15 to +10% (20.4 to 26.4 VDC)
Operating Voltage with  Power overEthernet (PoE) 48 VDC PoE (IEEE 802.3af compliant)
Power Consumption:
Transmitter unit (normal condition)¹ Typ. 5W
Transmitter unit (full load condition)² < 11.45W
Transmitter with optional relay < 12.9 W
Outputs:
Visual Alarm, power, fault LEDs, and LCD with all the gas readings and events. LEDs: Power(Green), Alarm 1 (Red), Alarm 2 (Red), Fault (Yellow)
Relays Alarm1, Alarm2, Fault Relays (3) rated 1.0 A @ 30VDC or 1.0A @ 30Vdc or 0.5A @ 125Vac Max 10 uA @ 10 mV  minimum, configurable as normally open or closed, latched  or unlatched.
Analog 3 wire sink, 3 wire source, or 4 wire fully isolated; 0 to 21 mA. for each channel.
DigitalCommunications Modbus / TCP Ethernet / Power over Ethernet (PoE)
¹ Normal condition:(1) No gas alarm(2) Without tube and pressure/vacuum²Full load condition:(1) 4-ch gas alarms are on(2) Maximum tubing length and pressure/vacuum on the inlet/exhaust line

Contact Us

AmericasHoneywell Analytics 405 Barclay BoulevardLincolnshire, IL 60069Tel: +1 847 955 8200Toll free: +1 800 538 0363Fax: +1 847 955 8208[email protected] Asia Pacific, India.Honeywell Analytics Asia Pacific, Co., Ltd.7F Sangam IT Tower, 434 Worldcup Buk-ro, Mapo-gu, Seoul 03922, South KoreaTel: +82 (0 2 6909 0300Fax: +82 (0 2 2025 0388India Tel: +91 124 4752 700[email protected]
Europe, Middle East, and AfricaLife Safety Distribution AG(LSD)Javastrasse 2 8604 Hegna SwitzerlandTel: +41 (0)44 943 4300Fax: +41 (0)44 943 4398[email protected] Mainland ChinaHoneywell Industrial Safety Gas DetectorsBuilding#1, 555 Huanke Road Zhang JiangHi-Tech Park Pudong New Area Shanghai201203, ChinaTel: 021-80386800Fax: 021-60246070[email protected]
TaiwanHoneywell Taiwan Ltd6F-2, No.8, ZiQiang S. Road, Jubei City,30264 TaiwanTel: +886-3-5169284Fax: +886-3-5169339[email protected]

Manuals and other information about this product are available at:www.honeywellanalytics.com/en/products/Midas-M

References

[xyz-ips snippet=”download-snippet”]


Posted

in

by