Honeywell Home M100 Small Linear Thermoelectric Actuator User Manual

M100Small Linear Thermoelectric Actuator

PRODUCT DATA

Design

  • Available in normally open or normally closed versions
  • M30 x 1,5 connection (other connections available on request)
  • Fits on specified RESIDEO and Heimeier thermostatic radiator valves and valve inserts for manifolds and compact radiators
  • Power supply 24 V or 230 V
  • Auxiliary switch models to drive pump or fan

Application

M100 small linear actuators are used with RESIDEO room temperature controllers and/or for time-controlled two-point regulation of heating and cooling systems equipped with fan coil units, radiators, floor heating systems, etc.

Features

  • Small size allows limited space installation
  • Reliable longtime operation
  • No mounting tools required
  • Noiseless operation
  • Ready-to-wire connection cable
  • Visual valve position indicator furnished with actuator
  • Overload protection (4 kV) for 230 V versions

Specifications

Specifications M100-AG; -AO; -BG; -BO:approx. 3 minM100-AGX; -AOX; -BGX; -BOX:approx. 5.5 min
Closing time see diagram on next page
Maximum stroke 4 mm
Stem force 90 N
Ambient temperature max. 50 °C (122 °F)
Power supply A..-Versions: 24 Vdc ± 20%; 50/60 HzB..-Versions: 230 Vac ± 20%; 50/60 Hz
Initial current M100-AG; -AO: approx. 0.6A M100-BG; -BO: approx. 0.3 AM100-AGX; -AOX: approx. 0.2 AM100-BGX; -BOX: approx. 0.05 A
Permanent current M100-AG; -AO: 0.09 AM100-BG; -BO: 0.013 AM100-AGX; -AOX: 70 mAM100-BGX; -BOX: 7 mA
Power M100-AG; -AO; -BG; -BO: 3 W
Consumption M100-AGX; -AOX; -BGX; -BOX: 2 W
Protection standard IP43
Cable length 1 m (3.3 ft), other cable lengths possible on request
Cable wires 2 x 0.5 mm2

NOTE: Opening and closing times depend on ambient temperature. Current values at nominal voltage and resistance.

Dimensions

Fig. 1. Dimensions

NOTE: All dimensions in mm unless otherwise stated.

Function

When the operating current is applied, a thermostat containing an expanding medium is heated, which after a pause period causes stroke movement.

Opening and Closing Time

NOTE: Opening and closing times depend upon ambient temperature and model.

Ordering Information

OS no. Description Valve action (Valve opens when heated) Voltage Cable Power consumption
M100-AG M100 small linear

thermoelectric actuator

valve closed without current 24 V Lenght: 1 m Wires: 2 x 0.5 mm2 3 W
M100-AO valve open without current 24 V
M100-BG valve closed without current 230 V
M100-BO valve open without current 230 V
M100-AGX M100 small linear thermoelectric actuator — low initial power consumption valve closed without current 24 V

Lenght: 1 m Wires: 2 x 0.5 mm2

2 W
M100-AOX valve open without current 24 V
M100-BGX valve closed without current 230 V
M100-BOX valve open without current 230 V

Installation Positions

NOTE: Connection leads must not touch the piping (heat transfer).

Wiring Diagram

Accessories

ZA100M-D      Adapter for Danfoss-Valve RAVLZA100M-GD  Adapter for Danfoss-Valve RA

For more informationhomecomfort.resideo.com/europe

Ademco 1 GmbHHardhofweg 4074821 MOSBACHGERMANYPhone: +49 6261 810Fax: +49 6261 81309

Manufactured for and on behalf of the Pittway Sàrl, La Pièce 4, 1180 Rolle, Switzerland by its Authorised Representative Ademco 1 GmbH EN0H-1512GE23 R0720 Subject to change © 2020 Pittway Sàrl. All rights reserved. This document contains proprietary information of Pittway Sàrl and its affiliated companies and is protected by copyright and other international laws. Reproduction or improper use without the specific written authorization of Pittway Sàrl is strictly forbidden. The Honeywell Home trademark is used under license from Honeywell International Inc.

References