Standby Generators Liquid-Cooled Gaseous Engine
Standby Generators
Standby Generators
Standby Generators Liquid-Cooled Gaseous Engine
1 of 9
INCLUDES: · Two Line LCD Tri-Lingual Digital NexusTMController · Isochronous Electronic Governor · Sound Attenuated Enclosure
Standby Power RatingModel QT070 (Aluminum – Bisque) – 70 kW 60 Hz Model QT080 (Aluminum – Bisque) – 80 kW 60 Hz Model QT100 (Aluminum – Bisque) – 100 kW 60 Hz Model QT130 (Aluminum – Bisque) – 130 kW 60 Hz Model QT150 (Aluminum – Bisque) – 150 kW 60 Hz
· Closed Coolant Recovery System
· Smart Battery Charger
· UV/Ozone Resistant Hoses
· ±1% Voltage Regulation
· Natural Gas or LP Operation
· 2 Year Limited Warranty
· UL 2200 Listed
*Built in the USA using domestic and foreign partsMeets EPA Emission Regulations 70, 100, 130 & 150 kW meet CA/MA emissions requirement with optional catalyst80 kW not for sale in CA/MA
FEATURES
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
¡ TEST CRITERIA: PROTOTYPE TESTED SYSTEM TORSIONAL TESTED
NEMA MG1-22 EVALUATION MOTOR STARTING ABILITY
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at ±1%.¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.¡ GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.
ISO9 0 0 1: 2008
Standby Generators
70 · 80 · 100 · 130 · 150 kW
application & engineering data
GENERATOR SPECIFICATIONSType Rotor Insulation Class Stator Insulation Class 2 of 9 Telephone Interference Factor (TIF) Alternator Output Leads 1-PhaseAlternator Output Leads 3-PhaseBearingsCouplingExcitation SystemVOLTAGE REGULATIONType Sensing RegulationGOVERNOR SPECIFICATIONSType Frequency Regulation Steady State Regulation
Synchronous H H<50 4 wire 6 wire (70, 80 & 150 kW) or 12 wire (100 & 130 kW) Sealed Ball Flexible Disc (70, 80 & 150 kW) or Gear Drive (100 & 130 kW) BrushlessElectronic Single Phase± 1%Electronic Isochronous± 0.25%
ENGINE SPECIFICATIONS: 80 kWMake Model Cylinders Displacement (Liters) Bore (in/mm) Stroke (in/mm) Compression Ratio Intake Air System Lifter Type
Generac V-Type 8 5.43.55/90.2 4.17/105.99:1 Naturally AspiratedHydraulic
ENGINE SPECIFICATIONS: 70, 100, 130 & 150 kW
Make
Generac
Model
V-Type
Cylinders
10
Displacement (Liters)
6.8
Bore (in/mm)
3.55/90.2
Stroke (in/mm)
4.17/105.9
Compression Ratio
9:1
Intake Air System
Naturally Aspirated
Lifter Type
Hydraulic
ELECTRICAL SYSTEMBattery Charge Alternator Static Battery ChargerRecommended Battery (battery not included)System Voltage
12 Volt 30 Amp 2 AmpGroup 24F, 525 CCA (70, 80 & 150 kW)or Group 27F, 700 CCA (100 & 130 kW) 12 Volts
GENERATOR FEATURESRevolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Class H insulation is NEMA rated All models fully prototyped tested
ENCLOSURE FEATURES
Aluminum weather protective enclosure
Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
Enclosed critical grade muffler
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
Small, compact, attractive Makes for an easy, eye appealing installation.
SAE
Sound attenuated enclosure ensures quiet operation.
ENGINE LUBRICATION SYSTEMOil Pump Type Oil Filter Type Crankcase Capacity (qt/l)ENGINE COOLING SYSTEMType Water PumpFan Speed (rpm)Fan Diameter (in/mm)Fan ModeFUEL SYSTEMFuel Type Carburetor Secondary Fuel Regulator Fuel Shut Off Solenoid Operating Fuel Pressure
Gear Full flow spin-on cartridge 5/4.7 (70, 100, 130 & 150 kW)or 6/5.7 (80 kW)Closed Belt driven 2300 – 70 kW 2174 – 80 kW 1670 – 100 kW 1950 – 130 kW 2200 – 150 kW 22/558.8 (70 kW) or 26/660.4 (80, 100, 130 & 150 kW) Pusher (70 kW) or Puller (80, 100, 130 & 150 kW)Natural gas, propane vapor Down Draft Standard Standard11-14″ water column/21-26 mm HG
(All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271)
Standby Generators
70 · 80 · 100 · 130 · 150 kW
GENERATOR OUTPUT VOLTAGE/kW – 60 Hz
kW LPG
120/240 V, 1Ø, 1.0 pf
67
120/208 V, 3Ø, 0.8 pf
70
QT070
120/240 V, 3Ø, 0.8 pf
70
277/480 V, 3Ø, 0.8 pf
70
120/240 V, 1Ø, 1.0 pf
77
120/208 V, 3Ø, 0.8 pf
80
QT080
120/240 V, 3Ø, 0.8 pf
80
277/480 V, 3Ø, 0.8 pf
80
120/240 V, 1Ø, 1.0 pf
100
120/208 V, 3Ø, 0.8 pf
100
QT100
120/240 V, 3Ø, 0.8 pf
100
277/480 V, 3Ø, 0.8 pf
100
120/240 V, 1Ø, 1.0 pf
130
120/208 V, 3Ø, 0.8 pf
130
QT130
120/240 V, 3Ø, 0.8 pf
130
277/480 V, 3Ø, 0.8 pf
130
120/240 V, 1Ø, 1.0 pf
144
120/208 V, 3Ø, 0.8 pf
150
QT150
120/240 V, 3Ø, 0.8 pf
150
277/480 V, 3Ø, 0.8 pf
150
Amp LPG 292 243 211 105 333 278 241 120 417 347 301 150 542 451 391 195 625 520 451 225
kW Nat. Gas 64 67 67 67 77 80 80 80 89 94 94 94 117 122 122 122 136 142 142 142
operating data
Amp Nat. Gas
CB Size (Both)
267
300
232
300
201
250
101
125
3 of 9
333
400
278
300
240
300
120
150
371
450
326
400
283
350
141
175
488
600
423
500
367
450
183
225
567
700
493
600
427
500
214
250
SURGE CAPACITY IN AMPS
ENGINE FUEL CONSUMPTION
QT070 QT080 QT100 QT130 QT150
120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø
Voltage Dip @ < .4 pf
15%
30%
129
356
194
471
168
408
83
201
174
435
186
466
161
404
70
175
150
413
186
452
161
392
107
261
236
648
364
885
315
767
161
390
486
1214
534
1334
463
1156
250
624
Note: Fuel pipe must be sized for full load. For Btu content, multiply gal/hr x 90950 (LP) or ft3/hr x 1000 (NG).
QT070 QT080 QT100 QT130 QT150
Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load
Natural Gas
(ft³/hr) (m³/hr)
110
3.1
260
7.4
500
14.2
696
19.8
1020
29
95
2.7
549.5 15.6
784.4 22.2
1024.8 29.0
1252.2 35.5
130
3.7
371
10.5
713
20.3
991
28.2
1260 35.8
135
3.8
482
13.7
927
26.3
1292 36.7
1786 50.8
155
4.4
556
15.8
1070 30.4
1491 42.4
2061 58.6
For megajoule content, multiply l/hr x 25.35 (LP) or m³/hr x 37.26 (NG).
Refer to “Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD permitting purposes.
(gal/hr)1.2 2.85 5.46 7.62 11.17 1.4 3.46 6.62 9.24 12.78 1.4 4.1 7.9 11 13.9 1.4 5.3 10.3 14.3 19.8 1.7 6.09 11.72 16.33 22.57
Propane (l/hr) 4.6 10.8 20.8 29.1 42.6 5.51 13.11 25.1 34.96 48.38 5.4 15.5 29.8 41.5 52.6 5.7 20 38.7 54 74.6 6.5 23.2 44.7 62.3 86.1
(ft3/hr)44 104 200 280 411 53 126 241 336 465 52 149 287 400 507 55 193 373 520 719 63 224 431 600 830
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Standby Generators
70 · 80 · 100 · 130 · 150 kW
operating data
ENGINE COOLING
Air flow (inlet air including alternator and combustion air in ft³/min)
System coolant capacity (gal/liters)
4 of 9
Heat rejection to coolant (BTU/hr)
Maximum operation air temperature on radiator (°C/°F)
Maximum ambient temperature (°C/°F)
70 kW 5200/147.24.5/17 287,000/302.8
80 kW 5300/150.14/15.1 316,000/333.4
100 kW 5500/155.74.5/17 342,000/360.860/150 50/140
130 kW 6450/182.64.5/17 496,000/523.3
150 kW 7800/220.94.5/17 568,000/599.3
COMBUSTION REQUIREMENTS
Flow at rated power (cfm/cmm)
205/5.8
143/4
262/7.4
336/9.5
410/11.6
SOUND EMISSIONS
Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode*
64
65
68
69
66
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load*
72
74
72
75
79
*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfm/cmm) Exhaust temperature at muffler outlet (°C/°F)
557/15.8 477/890
720/20.4 796/1465
888/25.1 516/960
1119/31.7 521/970
1535/43.5 593/1100
ENGINE PARAMETERS
Rated Synchronous rpm
1800
3600
2300
2970
3600
POWER ADJUSTMENT FOR AMBIENT CONDITIONSTemperature Deration ……………………………………………………………………………………………..3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F Altitude Deration (70,100,130 & 150)………………………………………………………………………1% for every 100 m above 183 m or 3% for every 1000 ft above 600 ft Altitude Deration (80 kW) …………………………………………………………………………………… 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ftCONTROLLER FEATURES2-Line Plain Text LCD Display ……………………………………………………………………………………………………………………….Simple user interface for ease of operation. Mode Switch: Auto …………………………………………………………………………………………………………………………….Automatic Start on Utility failure. 7 day exerciserOff……………………………………………………………………………………………………………Stops unit. Power is removed. Control and charger still operate. Manual…………………………………………………………………………….. Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds ………………………………………………………………………………………………………………………………………… Standard Engine Start Sequence……………………………………………………………………………………………………… Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration) Engine Warm-up…………………………………………………………………………………………………………………………………………………………………………………………… 5 sec Engine Cool-Down …………………………………………………………………………………………………………………………………………………………………………………………1 min Starter Lock-out ………………………………………………………………………………………………………………..Starter cannot re-engage until 5 sec after engine has stopped. Smart Battery Charger ……………………………………………………………………………………………………………………………………………………………………………….. Standard Automatic Voltage Regulation with Over and Under Voltage Protection……………………………………………………………………………………………………………….. Standard Automatic Low Oil Pressure Shutdown …………………………………………………………………………………………………………………………………………………………. Standard Overspeed Shutdown ………………………………………………………………………………………………………………………………………………………………………. Standard, 72 Hz High Temperature Shutdown……………………………………………………………………………………………………………………………………………………………………….. Standard Overcrank Protection …………………………………………………………………………………………………………………………………………………………………………………. Standard Safety Fused……………………………………………………………………………………………………………………………………………………………………………………………. Standard Failure to Transfer Protection………………………………………………………………………………………………………………………………………………………………………. Standard Low Battery Protection……………………………………………………………………………………………………………………………………………………………………………….. Standard 50 Event Run Log……………………………………………………………………………………………………………………………………………………………………………………… Standard Future Set Capable Exerciser………………………………………………………………………………………………………………………………………………………………………. Standard Incorrect Wiring Protection…………………………………………………………………………………………………………………………………………………………………………. Standard Internal Fault Protection …………………………………………………………………………………………………………………………………………………………………………….. Standard Common External Fault Capability……………………………………………………………………………………………………………………………………………………………….. Standard Governor Failure Protection………………………………………………………………………………………………………………………………………………………………………… Standard
Standby Generators
70 · 80 · 100 · 130 · 150 kW
available accessories
Model #G006463-4G006478-0G005632-1 – 70, 80 & 150 kW G005633-0 – 100 & 130 kW G005620-0 – 70, 100 & 130 kW G006204-0 – 80 kW G005667-0 – 150 kW
Product Mobile LinkTM
Description
Generac’s Mobile Link allows you to check the status of your generator
from anywhere that you have access to an Internet connection from a
PC or with any smart device. You will even be notified when a change in
the generator’s status occurs via e-mail or text message. Note: Harness
5 of 9
Adapter Kit required. Available in the U.S. only.
Harness Adapter Kit
The Harness Adapter Kit is required to make liquid-cooled units compatible with Mobile LinkTM.
Cold Weather Kit
If the temperature regularly falls below 32 °F (0 °C), install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap.
Extreme Cold Weather Recommended where the temperature regularly falls below 32 °F (0 °C)
Kit
for extended periods of time. For liquid cooled units only.
G005651-0
Base Plug Kit
Add base plugs to the base of the generator to keep out debris.
G005703-0 G005660-0 – 70, 100, 130, and 150 kW G006915-0 – 80 kW G006664-0 G006665-0G006873-0G007005-0G006510-0
Paint Kit
If the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure.
Scheduled Maintenance Kit
The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac liquid-cooled generators.
Completely wireless and battery powered, Generac’s wireless remote Local Wireless Monitor monitor provides you with instant status information without everleaving the house.
Wireless Remote Extension Harness
Recommended for use with the Wireless Remote on units up to 60 kW, required for use on units 70 kW or greater.
Smart Management Module (50 Amps)Wi-Fi LP Fuel Level MonitorE-Stop
Smart Management Modules are used in conjunction with the Automatic Transfer Switch to increase its power management capabilities. It provides additional power management flexibility not found in any other power management system.The Wi-Fi enabled LP fuel level monitor provides constant monitoring of the connected LP fuel tank. Monitoring the LP tank’s fuel level is an important step in making sure your generator is ready to run during an unexpected power failure. Status alerts are available through a free application to notify when your LP tank is in need of a refill.E-stop allows for immediate fuel shutoff and generator shutdown in the event of anemergency.
Standby Generators
70 · 80 · 100 · 130 · 150 kWDrawing #0H7452-D6 of 9
(IF EQUIPPED)
interconnections
70 kW
installation layoutDrawing #0F6287-E7 of 9
DIMENSIONS: MM [INCH]
Standby Generators
80 kWDrawing #0L3178-B8 of 9
Standby Generators
RADIATOR/EXHAUST DISCHARGE AIR (BOTH SIDES)
BATTERY 12V GROUP 26NEGATIVE GROUND P/N: 058208
A_1
1422 [56] CENTER OF GRAVITYSEE NOTE 5AIR INTAKE (BOTH SIDES)
REMOVE COVER FOR ACCESS TO RADIATOR FILL CAP
LOW VOLTAGE
AREA ONLY 91
TOP VIEW
[3.6] 206
[8.1]
872 [34.3]
SERVICE ITEM OIL FILL CAP OIL DIP STICK OIL FILTER OIL DRAIN HOSE RADIATOR DRAIN HOSE AIR CLEANER ELEMENT SPARK PLUGSMUFFLER FAN BELT BATTERY
5.4L LEFT DOOR LEFT DOOR LEFT DOOR RIGHT DOOR LEFT DOOR EITHER DOOR EITHER DOOR SEE NOTE 12 EITHER DOOR RIGHT DOOR
REFERENCE OWNERS MANUAL FOR PERIODIC REPLACEMENT PART LISTINGS.
STUB-UP AREA SEE NOTE 4
128 [5.0]
86 [3.4]
EXHAUST MUFFLERS & FAN BELT ENCLOSED WITHIN SEE NOTE 12
CONTROL PANEL BATTERY CHARGER IS ENCLOSED WITHIN.
NOTES:1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1241 (49″) WIDE 3228 (127″) LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, STATE, AND LOCAL CODES.3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION: – SEE SPECIFICATION SHEET OR OWNERS MANUAL – ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.4. INSIDE STUB-UP AREA FOR AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (.5 AMP MAX) CONNECTION AND ACCESS TO TRANSFER SWITCH CONTROL WIRES. REMOVE FRONT COVER FOR ACCESS.5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION ANDRECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. 7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O. 8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5(USE STANDARD SAE TORQUE SPECS) 10. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPECSHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. 11. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLEAND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. 12. REMOVE EITHER LEFT OR RIGHT HAND SIDE PANEL TO ACCESS EXHAUST MUFFLERSAND FAN BELT. 13. FIELD CUT HOLE IS ONLY REQUIRED FOR MOUNTING OF GENERATOR ON AN EXISTINGPAD.VISE ACTION LATCH, ONE PER DOOR, TWO LIFT-OFF DOORS PER SIDE OF GENERATOR.
RADIATOR/ EXHAUST DISCHARGE AIR68 [2.7]47 [1.8]
A
A
1521 [59.9] OVERALL HEIGHT
1777 [70.0]
51 [2.0]2832 [111.5]LEFT SIDE VIEWFUEL LINE CONNECTION 3/4″ NPT FEMALE COUPLING
STUB-UP AREAFIELD CUT FOR OUTSIDE CONDUIT CONNECTION ONLY SEE NOTE 13
LIFTING PROVISION (4 PLACES) SEE NOTES 5, 8 AND CENTER OF GRAVITY DIMENSIONS.
935 [36.8]REAR VIEW
WEIGHT DATA
ENGINE/KW
ENCLOSURE MATERIAL
WEIGHT GENSET ONLYKG [LBS]
WEIGHT SHIPPING SKIDKG [LBS]
SHIPPING WEIGHT KG [LBS]
5.4L/80KW
AL
925 [2035]
79 [175]
1004 [2210]
DIMENSIONS: MM [INCH]
A ARIGHT SIDE VIEW
installation layout
Standby Generators
100 · 130 · 150 kW
installation layoutDrawing #0H4105-B9 of 9
DIMENSIONS: MM [INCH]
Generac Power Systems, Inc. · S45 W29290 HWY. 59, Waukesha, WI 53189 · generac.com©2017 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0199370SBY-M 05/31/17