Honeywell C7355B In-Duct IAQ Monitor User Guide

Honeywell C7355B In-Duct IAQ Monitor

ABOUT

This air quality monitor is specially designed for monitoring multiple air quality parameters in the air duct. The sensor is installed in the outdoor or return air duct. Real time monitoring parameters are particles (PM2.5 and PM10), carbon dioxide (CO2), TVOC, air temperature and relative humidity.

The intelligent control algorithms built into the device help to minimize the influence of ambient temperature and humidity on the measured values. The device is packaged with numerous presets suitable for most commercial building requirements that enable quick and easy initial setup.

The device, with pilot tube inlet and outlet design instead of common air pump, adapts to a wider range of air speeds and ensures a long lifetime of usage. It provides Modbus RTU (RS-485) communication protocol and easily integrates with the building management system.

INITIAL SETUP

The device will power on when voltage is connected.

NOTE: Upon first use or re-use after long time shelving, the device should be continuously powered-on for at least 48 hours to ensure stable output of all measured values.

LIGHT INDICATION

The bottom right side of the device is the indicator area. For this monitor (Part number: C7355B1052), only refer to the ON and SCALE indicators.

When the power is on, it will illuminate to indicate the device is working. Otherwise, the device is faulty.
This light indicates the one-minute average value of PM2.5, and changes color depending on concentration.When PM2.5<35 μg/m3 green light on35–75 μg/m3 yellow light on>75 μg/m3 red light on

COMMUNICATION SETTINGS

Wired communication (Modbus RS-485) is available for the device. The wiring terminals are shown below for detailed wiring and installation, please refer to Mounting Instructions.

SPECIFICATIONS

Part Number: C7355B1052Detection Parameters: PM 2.5/PM 10, CO2, TVOC, Temperature and RHOperating Environment: 4 °F­140 °F (-20 °C­60 °C); 0­99%RH (non-condensing)Storage Conditions: 32 °F­122 °F (0 °C­50 °C); 10­60%RHOverall Dimension: 7.09 in x 4.92 in x 2.58 in (180 mm x 125 mm x 65.5 mm)Net weight: 1.87 lb (850 g)Certification Standard: CE/FCC

Modbus Register Table

Mode: RTU (MSB First)Baud Rate:1-48002-96003-144004-192005-384006-560007-576008-115200default: 2-9600bpsStart Bits: 1Data Bits: 8Stop Bits: 1 / 2default: 1Parity: None / Odd / Evendefault: None

Register Map

Support Function code:3 – Read Holding Registers4 – Read Input Registers6 – Write Single Register16 – Write Multiple registers

Table 1. Modbus Register Table.

Starting Register Decimal Data Description Function Read/ Write Quantity of Registers (2Bytes/16bit) Format Decimals Data Range, Data Description Default
0/1050 PM2.5 hourly average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
2/1052 PM10 hourly average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
8/1058 CO2 hourly average measurement 4 R 2 Float-Big Endian 0 0–5,000 ppm  
10/1060 TVOC hourly average measurement 4 R 2 Float-Big Endian 3 0–4000 mg/m3  
12/1000 PM2.5 one minute average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
14/1002 PM10 one minute average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
16/1004 Temperature real-time measurement 4 R 2 Float-Big Endian 2 -20.00 °C–60.00 °C  
18/1006 Humidity real-time measurement 4 R 2 Float-Big Endian 2 0–100.00% RH  
20/1008 CO2 real-time measurement 4 R 2 Float-Big Endian 0 0–5,000 ppm  
22/1010 TVOC real-time measurement 4 R 2 Float-Big Endian 3 0–4000 mg/m3  
24/1100 PM2.5 24-hour moving average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
26/1102 PM10 24-hour moving average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
32/1108 CO2 24-hour moving average measurement 4 R 2 Float-Big Endian 0 0–5,000 ppm  
34/1110 TVOC 8-hour moving average measurement 4 R 2 Float-Big Endian 3 0–4000 mg/m3  
1300 Primary pollutant 24- hour average measuring value (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 2 Float-Big Endian   1300  
1302 Primary pollutant type (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 1 INT16   1-PM25, 2-PM10, 3-CO2; 4-TVOC  
1303 Index level of the primary pollutant (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 1 INT16   Level 1-ExcellentLevel 3-Light pollutionLevel4-Medium pollutionLevel 5-Heavy pollution Level 6-Severe pollution  
1304 AQI value of the primary pollutant) (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 1 INT16   0–500  
1320 PM2.5 AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1321 PM10 AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1322 CO2 AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1323 TVOC AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1350 PM2.5 Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
1351 PM10 Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
1352 CO2 Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
1353 TVOC Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
78 3 color LED status 4 R 1 INT16   0-OFF, 1-Green,

2-Yellow, 3-Red

 
0 Modbus Address 3/6 R/W 1 UINT16   1–247 1
1 Modbus rate (bps) 3/6 R/W 1 UINT16   1-4800, 2-9600, 3-14400, 4-19200, 5-38400, 6-56000, 7-57600, 8-115200 2
2 Modbus Parity check bit 3/6 R/W 1 UINT16   1- NONE, 1STOP_BIT, 2- NONE, 2STOP_BIT, 3- Odd, 1STOP_BIT, 4- Even, 1STOP_BIT 1
4 Temperature correction value 3/16 R/W 2 Float-Big Endian 2 -3.0–3.0 °C/ -6.0–6.0 °F -2.0
6 Humidity correction value 3/16 R/W 2 Float-Big Endian 2 -5.0–5.0%RH 0
14 CO2 compensation value 3/16 R/W 2 Float-Big Endian 0 -300.0–300.0 ppm 0

In order to reserve the decimal part, the measuring value with decimal will be magnified 10/100/1000 times, marked as x10/x100/x1000.

Starting Register Decimal Data Description Function Read/ Write Quantity of Registers (2Bytes/16bit) Format Decimals Data Range, Data Description Default
50/1175 PM2.5 hourly average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
51/1176 PM10 hourly average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
54/1179 CO2 hourly average measurement x1 4 R 1 UINT16 0 0–5000corresponding to 0–5,000 ppm  
55/1180 TVOC hourly average measurement x1000 4 R 1 UINT16 3 0–3575corresponding to –4.000 mg/m3  
56/1150 PM2.5 one minute average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0~1000.0 μg/m3  
57/1151 PM10 one minute average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
58/1152 Temperature real-time measurement x100 4 R 1 INT16 2 -2000–6000 corresponding to -20.00 °C–60.00 °C  
59/1153 Humidity real-time measurement x100 4 R 1 UINT16 2 0–10000 corresponding to 0–100.00% RH  
60/1154 CO2 real-time measurement x1 4 R 1 UINT16 0 0–5000 corresponding to 0–5,000 ppm  
61/1155 TVOC real-time measurement x1000 4 R 1 UINT16 3 0–3575 corresponding to –4.000 mg/m3  
62/1200 PM2.5 24-hour moving average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
63/1201 PM10 24-hour moving average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
66/1204 CO2 24-hour moving average measurement x1 4 R 1 UINT16 0 0–5000

corresponding to 0–5,000 ppm

 
67/1205 TVOC 24-hour moving average measurement x1000 4 R 1 UINT16 3 0–3575corresponding to 0–4.000 mg/m3  

Honeywell Building TechnologiesHoneywell715 Peachtree Street NEAtlanta, GA 30308customer.honeywell.com

Honeywell Building TechnologiesHoneywell GmbHBöblinger Strasse 1771101 Schönaich, Germanybuildings.honeywell.com

® U.S. Registered Trademark©2020 Honeywell International Inc.31-00441—01 M.S. 11-20

report this ad

References

[xyz-ips snippet=”download-snippet”]