Honeywell C7355A Room IAQ Monitor User Guide

Honeywell C7355A Room IAQ Monitor

ABOUT

IAQ Monitor is an advanced, configurable, RS-485 connected device for commercial buildings. It monitors CO2, PM2.5/PM10, TVOC, temperature and humidity. This device provides a Modbus RTU (RS-485) interface, easily integrating with the building automation system.

INITIAL SETUP

The device will power on after voltage is connected.

NOTE: Upon first use (or re-use after a long time shelving) device should be powered continuously for more than 48 hours to ensure stable output of all measured values.

LIGHT RING INDICATOR

There is a circle ring indicator lighting the center of the housing. This light is used to show the measured air quality.

This light indicates the one minute average value of PM2.5, and changes color depending on concentration.

The indicator light behavior can be configured according to DIP switches:

Table 1. DIP Switch Settings.

Indicator Setting

DIP4

DIP3 DIP2 DIP1
Light OFF

OFF

OFF OFF OFF
Three-color

OFF

ON ON ON

Default

Green Normally ON

ON

OFF OFF OFF

When the three-color option is selected, indicator color corresponds to the following measured ranges:— Green <35 μg/m3— Yellow 35—75 μg/m3— Red >75 μg/m3

Communication Settings

Wired communication (Modbus RTU) is available for the device. The wiring terminals are shown below. For detailed wiring and installation, please refer to the User Guide.

SPECIFICATIONS

Part Number: C7355A1050Detection Parameters: PM2.5/PM10, CO2, TVOC, temperature and relative humidity (RH).Operating Environment:Temperature: 32 to 122 °F (0 to 50 °C)Humidity: 0—90% RHStorage Conditions:Temperature: 14 to 122 °F (-10 to 50 °C);Humidity: 0–90% RH (Non-condensing)Overall Dimensions: 5.12 in. × 5.12 in. × 1.77 in. 130 mm × 130 mm × 45 mmNet weight: 0.66 lb (300 g)Certification Standard: CE/FCC

Modbus Register Table

Mode: RTU (MSB First)Baud Rate:1-48002-96003-144004-192005-384006-560007-576008-115200default: 2-9600bpsStart Bits: 1Data Bits: 8Stop Bits: 1 / 2default: 1Parity: None / Odd / Evendefault: None

Register MapSupport Function code:3 – Read Holding Registers4 – Read Input Registers6 – Write Single Register16 – Write Multiple registers

Table 2. Modbus Register Table.

Starting Register Decimal

Data Description Function Read/ Write Quantity of Registers (2Bytes/16bit) Format Decimals

Data Range, Data Description

Default
0/1050 PM2.5 hourly average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
2/1052 PM10 hourly average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
8/1058 CO2 hourly average measurement 4 R 2 Float-Big Endian 0 0–5,000 ppm  
10/1060 TVOC hourly average measurement 4 R 2 Float-Big Endian 3 0–4000 mg/m3  
12/1000 PM2.5 one minute average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
14/1002 PM10 one minute average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
16/1004 Temperature real-time measurement 4 R 2 Float-Big Endian 2 -20.00 °C–60.00 °C  
18/1006 Humidity real-time measurement 4 R 2 Float-Big Endian 2 0–100.00% RH  
20/1008 CO2 real-time measurement 4 R 2 Float-Big Endian 0 0–5,000 ppm  
22/1010 TVOC real-time measurement 4 R 2 Float-Big Endian 3 0–4000 mg/m3  
24/1100 PM2.5 24-hour moving average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
26/1102 PM10 24-hour moving average measurement 4 R 2 Float-Big Endian 1 0–1000.0 μg/m3  
32/1108 CO2 24-hour moving average measurement 4 R 2 Float-Big Endian 0 0–5,000 ppm  
34/1110 TVOC 8-hour moving average measurement 4 R 2 Float-Big Endian 3 0–4000 mg/m3  
1300 Primary pollutant 24- hour average measuring value (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 2 Float-Big Endian   1300  
1302 Primary pollutant type (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 1 INT16   1-PM25, 2-PM10,

3-CO2; 4-TVOC

 
1303 Index level of the primary pollutant (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 1 INT16   Level 1-Excellent Level 3-Light pollution

Level4-Medium pollution

Level 5-Heavy pollution Level 6-Severe pollution

 
 
1304 AQI value of the primary pollutant) (One of PM2.5/PM10/CO2/ TVOC) (Calculated based on 24-hour or 1-hour moving average measurement) 4 R 1 INT16   0–500  
1320 PM2.5 AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1321 PM10 AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1322 CO2 AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
1323 TVOC AQI value (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   0–500  
 
1350 PM2.5 Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
1351 PM10 Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
1352 CO2 Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
1353 TVOC Pollution index level (Calculated based on 24-hour moving average measurement) 4 R 1 INT16   1–6  
78 3 color LED status 4 R 1 INT16   0-OFF, 1-Green,2-Yellow, 3-Red  
0 Modbus Address 3/6 R/W 1 UINT16   1–247 1
1 Modbus rate (bps) 3/6 R/W 1 UINT16   1-4800, 2-9600,3-14400, 4-19200,5-38400, 6-56000,7-57600, 8-115200 2
2 Modbus Parity check bit 3/6 R/W 1 UINT16   1- NONE, 1STOP_BIT, 2- NONE, 2STOP_BIT, 3-Odd, 1STOP_BIT,4-Even, 1STOP_BIT 1
4 Temperature correction value 3/16 R/W 2 Float-Big Endian 2 -3.0–3.0 °C/

-6.0–6.0 °F

-2.0
6 Humidity correction value 3/16 R/W 2 Float-Big Endian 2 -5.0–5.0%RH 0
14 CO2 compensation value 3/16 R/W 2 Float-Big Endian 0 -300.0–300.0 ppm 0

In order to reserve the decimal part, the measuring value with decimal will be magnified 10/100/1000 times, marked as x10/x100/x1000.

Starting Register Decimal

Data Description Function Read/ Write Quantity of Registers (2Bytes/16bit) Format Decimals Data Range, Data Description

Default

50/1175 PM2.5 hourly average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
51/1176 PM10 hourly average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
54/1179 CO2 hourly average measurement x1 4 R 1 UINT16 0 0–5000corresponding to 0–5,000 ppm  
55/1180 TVOC hourly average measurement x1000 4 R 1 UINT16 3 0–3575corresponding to –4.000 mg/m3  
56/1150 PM2.5 one minute average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0~1000.0 μg/m3  
57/1151 PM10 one minute average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
58/1152 Temperature real-time measurement x100 4 R 1 INT16 2 -2000–6000corresponding to -20.00 °C–60.00 °C  
59/1153 Humidity real-time measurement x100 4 R 1 UINT16 2 0–10000corresponding to 0–100.00% RH  
60/1154 CO2 real-time measurement x1 4 R 1 UINT16 0 0–5000corresponding to 0–5,000 ppm  
61/1155 TVOC real-time measurement x1000 4 R 1 UINT16 3 0–3575corresponding to –4.000 mg/m3  
62/1200 PM2.5 24-hour moving average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
63/1201 PM10 24-hour moving average measurement x10 4 R 1 UINT16 1 0–10000corresponding to 0–1000.0 μg/m3  
66/1204 CO2 24-hour moving average measurement x1 4 R 1 UINT16 0 0–5000corresponding to 0–5,000 ppm  
67/1205 TVOC 24-hour moving average measurement x1000 4 R 1 UINT16 3 0–3575corresponding to 0–4.000 mg/m3  