WISE-4012E6-ch Input/Output IoT Wireless I/OModule for IoT Developers
Introduction
The Advantech WISE IoT Developer Kit is a complete hardware & software solution to help users develop IoT applications and simulate their projects in the simplest way. The WISE IoT Developer Kit provides everything you need to get going: a WISE-4012E 6-ch universal input or output wireless Ethernet I/O module, and developer kit including WebAccess 8.0 with open interfaces for the intelligent application developer, extension board for simulating sensor status, a micro USB cable for power input, and a screwdriver for wiring. The WISE4012E has an integrated Wi-Fi interface with AP mode and web configuration which can be accessed by mobile device directly.Data can be logged in the I/O module and then automatically pushed to the file-based cloud.
Features
- 2.4 GHz IEEE 802.11b/g/n WLAN
- 2-ch 0 ~ 10V Input, 2-ch DI, and 2-ch Relay Output
- Includes WebAccess with demo project for developer
- Includes extension board for simulating sensor status
- Includes micro USB cable for power input
- Supports Modbus/TCP with RESTful web service
- Supports wireless client and server mode that can be accessed directly without AP or router
- Supports mobile device web configuration with HTML5 without the platform limitation
- Supports file-based cloud storage and local logging with timestamp
Product Concept: Data A-P-P
IoT Developer Kit
- WISE-4012E (x1)
- Extension Board (x1)
- USB Cable (x1)
- Screwdriver (x1)
- WebAccess (x1)
Application Scenario 1Connect to end devices
Application Scenario 2Connect to an extension board
Specifications
Voltage Input |
|
Channel | 2 |
Resolution | 12-bit |
Sampling Rate | 10 Hz (Total) |
Accuracy | ±0.1 VDC |
Input Type and Range | 0 ~ 10 V |
Input Impedance | 100 kΩ |
Digital Input |
|
Channels | 2 |
Logic level | Dry Contact 0: Open 1: Close to GND |
Supports 3 kHz Counter Input (32-bit + 1-bit overflow) | |
Keep/Discard Counter Value when Power-off | |
Supports 3 kHz Frequency Input | |
Supports Inverted DI Status | |
Relay Output |
|
Channels | 2 (Form A) |
Contact Rating (Resistive Load) | 120 VAC @ 0.5 A |
Isolation (b/w coil & contacts) | 30 VDC @ 1A |
Relay On Time | 1,500 Vrms |
Relay Off Time | 10 ms |
Insulation Resistance | 7 ms |
Maximum Switching | 1 GΩ min. @ 500 VDC |
Supports Pulse Output | 60 operations/minute |
Supports High-to-Low and Low-to-High Delay Output | |
Environment |
|
Operating Temperature | -25 ~ 70°C (-13 ~ 158°F) |
Storage Temperature | -40 ~ 85°C (-40 ~ 185°F) |
Operating Humidity | 20 ~ 95% RH (non-condensing) |
Storage Humidity | 0 ~ 95% RH (non-condensing) |
General |
|
WLAN | IEEE 802.11b/g/n 2.4GHz |
Connectors | Plug-in screw terminal block (I/O) |
Watchdog Timer | System (1.6 second) and Communication (programmable) |
Certification | CE, FCC, R&TTE, NCC, SRRC, RoHS, ANATEL |
Dimensions (W x H x D) | 80 x 139 x 25 mm |
Enclosure | PC |
Power Input | Micro-B USB 5 VDC |
Power Consumption | 1.5 W @ 5 VDC |
Supports User-Defined Modbus Address | |
Supports Data Log Function | Up to 10,000 samples with timestamp |
Supported Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, and HTTP, MQTT |
Supports RESTful Web API in JSON format | |
Supports Web Server in HTML5 with JavaScript & CSS3 | |
Supports System Configuration Backup and User Access Control |
Ordering Information
WISE-4012E-AE-WA | WISE-4012E IoT Developer Kit with WebAccess |
Advantech WebAccess 8.0WebAccess Cloud ArchitectureWebAccess is a 100% web-based HMI and SCADA software with private cloud software architecture. WebAccess can provide large equipment vendors, SIs, and Enterprises access to and manipulation of centralized data to configure, change/update, or monitor their equipment, projects, and systems all over the world using a standard web browser. Also, all the engineering works, such as database configuration, graphics drawing, and systemmanagement and the troubleshooting can be operated remotely. This can significantly increase the efficiency of maintenance operations and reduce maintenance costs.Business Intelligence DashboardWebAccess 8.0 provides an HTML5 based Dashboard as the next generation of WebAccess HMI. System integrators can use Dashboard Editor to create the customized information page by using analysis charts and diagrams which are called widgets. Ample widgets have been included in the built-in widget library, such as trends, bars, alarm summary, maps…etc. After the dashboard screens have been created, the end-user can view the data by Dashboard Viewer in different platforms, like Explorer, Safari, Chrome, and Firefox for a seamless viewing experience across PCs, Macs, tablets, and smartphones.Open InterfacesWebAccess has three interfaces for different uses. First, WebAccess provides a Web Service interface for partners to integrate WebAccess data into APPs or application systems.Second, a pluggable widget interface has been opened for a programmer to develop their widget and run on WebAccess Dashboard. Last, WebAccess API, a DLL interface for programmers to access the WebAccess platform and develop Windows applications. With these interfaces, WebAccess can act as an IoT platform for partners to develop IoT applications in various vertical markets.Google Maps and GPS Tracking IntegrationWebAccess integrates real-time data on each geographical site with Google Maps and GPS location tracking. For remote monitoring, users can intuitively view the current energy consumption on each building, production rate on each field or traffic flow on the highway together with alarm status. By right-clicking on Google Maps or entering the coordinate of the target, users can create a marker for the target and associate the real-time data of three sites with a display label. Furthermore, this function also integrates with GPS modules to track the location of the marker in Google Maps and allows it to be used in-vehicle systems.Ample Driver SupportWebAccess supports hundreds of devices. In addition to Advantech I/Os and controllers, WebAccess also supports all major PLCs, controllers, and I/Os, like Allen Bradley, Siemens, LonWorks, Mitsubishi, Beckhoff, Yokogawa, etc. WebAccess can easily integrate all devices in one SCADA. All of these device drivers are integrated into WebAccess and free of charge. For a complete list of WebAccess drivers, refer to webaccess.advantech.com.Distributed SCADA Architecture with Central Database ServerSCADA nodes run independently of any other node. Each SCADA node communicates to automation equipment using communication drivers supplied with Advantech WebAccess.The Project Node is a centralized database server of configuration data. A copy of the database and graphics of all SCADA nodes is kept on the Project Node. The historical data is also stored in the database in the project node.Open Data ConnectivityAdvantech WebAccess exchanges online data with 3rd party software in real-time by supporting OPC UA/DA, DDE, Modbus, and BACnet Server/Client. It supports SQL, Oracle, MySQL, and MS Access for offline data sharing.Software Requirements
Operating System | Windows XP (SCADA Node Only), Windows 7 SP1, Windows 8 Professional, Windows Server 2008 R2 or later |
Hardware | Intel Atom or Celeron. Dual-Core processors or higher recommended2GB RAM minimum, more recommended30GB or more free disk space |
Wireless IoT Sensing DevicesAll product specifications are subject to change without notice.Online Downloadwww.advantech.com/products
References
[xyz-ips snippet=”download-snippet”]