AMRTA 507296-03 Residential Packaged Units Air Conditioners and Heat Pumps Instruction Manual

507296-03 Residential Packaged Units Air Conditioners and Heat Pumps

INSTALLATION AND MAINTENANCE INSTRUCTIONS*RP14AC AND *RP14HP SERIES UNITSRESIDENTIAL PACKAGED UNITSAir Conditioners and Heat Pumps 507296-03 12/2020

THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCEWARNINGInstallation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and qualified service personnel should install or service this equipment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death.

Table of ContentsUnit Dimensions ………………………………………………….2 Roof Curb Dimensions …………………………………………4 Adjustable Roof Curb Dimensions………………………….6 Installation ………………………………………………………….8 Electrical Wiring…………………………………………………10 Duct System …………………………………………………….. 11 Filters ………………………………………………………………. 11 Condensate Drain………………………………………………12 Sequence of Operation……………………………………….12 Maintenance ……………………………………………………..15 Wiring Diagrams ………………………………………………..18

WARNINGFor your safety, do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Such actions could result in property damage, personal injury, or death.

WARNINGIf this unit is to be installed in a mobile or manufactured home application, the duct system must be sized to achieve static pressures within the manufacturer’s guidelines. All other installation guidelines must also be followed. Failure to do so may result in equipment damage, personal injury, and improper performance of the unit.

215 Metropolitan Drive West Columbia, SC 29170

*P507296-03*(P) 507296-03

CAUTIONThe installation of this appliance must conform to the requirements of the National Fire Protection Association; the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.

507296-03

Save these instructions for future referenceIssue 2107

Page 1 of 19

Unit Dimensions – Small Base Air Conditioners & Heat Pumps

47.66

2.48

1.98

2.33

2.33

16.77

14.02

TOP VIEW

11.49

RETURN AIR

SUPPLY AIR

11.49

18.52 16.07

47.66 SIDE VIEWS

POWER ENTRY POWER ENTRY

3.2520.31 21.06 23.19

6.94 4.56

13.44

13.44

14.326.20 3.07Page 2 of 19

5.86

40.89

CONDENSATE DRAIN 3/4 NPT

21.63

13.21TYPICAL DRAIN LOCATION

3.87 3.62

17.07

34.19 29.59

12.12 6.20

Issue 2107

POWER ENTRY 1-1/8 DIA. KNOCKOUTLOW VOLTAGE ENTRY 7/8 DIA. KNOCKOUT

ELECTRIC HEAT POWER ENTRY4.06

507296-03

Unit Dimensions – Large Base Air Conditioners & Heat Pumps

56.13

2.33

2.11

2.39

19.49

19.49

TOP VIEW

11.49

RETURN AIR

SUPPLY AIR

2.33

11.49

18.52 16.07

47.66 SIDE VIEWS

POWER ENTRY POWER ENTRY6.94 3.2510.06 25.81 26.56 28.68

18.19

18.19

14.32

6.20 507296-03

3.76

4.20

44.89

CONDENSATE DRAIN 3/4 NPT

21.63

13.21TYPICAL DRAIN LOCATION

3.87

17.07

3.62 4.06 33.59 38.19

12.14

6.20

Issue 2107

POWER ENTRY 1-1/8 DIA. KNOCKOUT LOW VOLTAGE ENTRY 7/8 DIA. KNOCKOUTELECTRIC HEAT POWER ENTRYPage 3 of 19

Roof Curb Dimensions – Small Base Air Conditioners & Heat Pumps

3/4 (19)

Opening for Power Entry Through Unit Base

RETURN OPENING

5-1/2 x 5-5/8 in.

(140 x 31 mm)

44-3/8 (1127)

11-1/2

16-7/8 (429)

2-1/8

Insulated

(287)

(54)

Panels

5-3/4

1

(146) (25)

5-1/2

(140)

SUPPLY OPENING

13-7/8 (352)

8 (203) 14 (356)

17-1/4

11-1/2 18 (457)

(438)

(287) 24 (610)

3

44-3/8 (1127)

(76)

1-3/8

13 (35)

(330)

Opening for Power Entry Through Unit Base 3 x 13 in. (76 x 330 mm)

3-3/4 (95)

NOTE – Roof deck may be omitted within confines of curb.

Page 4 of 19

Issue 2107

507296-03

Roof Curb Dimensions – Large Base Air Conditioners & Heat Pumps

Opening for Power Entry Through Unit Base 5-1/2 x 5-5/8 in. (140 x 31 mm)

44-3/8 (1127)

Insulated Panels

3/4 (19)

19-1/2

11-1/2

(380)

1

(287) (25)

RETURN OPENING

2-1/8 (54)19-1/2

(380)

SUPPLY

OPENING 11-1/2

22-7/8

(287)

(581)

52-7/8 (1343)Opening for Power Entry Through Unit Base 3 x 13 in. (76 x 330 mm)

3-3/4 (95)

7 (178)

8 (203) 14 (356) 18 (457) 24 (610)

NOTE – Roof deck may be omitted within confines of curb.

507296-03

Issue 2107

Page 5 of 19

Adjustable Roof Curb Dimensions – Small Base Air Conditioners & Heat PumpsCLIPLOCK CORNER DETAILTop Edge Wood Nailer Strip

CURB PROFILE1 1/21-3/4 Opening for Power Line Entry thru base44-3/8 Insulated Panels44-3/8

Bottom FlangeTypical Slot Typical Locking TabNOTE: See Cliplock 1000 installation instructions for complete assembly and installation procedures and requirements.1

11-5/8

16-7/8

1

5-3/4

5-1/2

3-1/2

13-1/2

17-1/4

3-5/8

1-3/8

2-1/8 13-7/814 11-5/8

Page 6 of 19

Bottom Curb AssemblyOpening for Power Entry thru base

NOTE – Roof deck may be omitted within confines of curb.Issue 2107

507296-03

Adjustable Roof Curb Dimensions – Large Base Air Conditioners & Heat PumpsCLIPLOCK CORNER DETAILTop Edge Wood Nailer Strip

CURB PROFILE1 1/21-3/4 Opening for Power Line Entry thru base44-3/8 Insulated Panels52-7/8

Bottom FlangeTypical Slot Typical Locking TabNOTE: See Cliplock 1000 installation instructions for complete assembly and installation procedures and requirements.1

11-5/8

19-5/8

5-1/2

1 5-3/4

23-1/8

3-1/2

13-1/2

3-1/2

6-7/8

2-1/8 19-3/811-5/8 14

Bottom Curb AssemblyOpening for Power Entry thru base

507296-03

NOTE – Roof deck may be omitted within confines of curb. Issue 2107

Page 7 of 19

WARNINGImproper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer or service agency.InstallationThese instructions explain the recommended method of installation of the packaged heat pump and air conditioner units and associated electrical wiring.This unit is designed and approved for use as a selfcontained air-to-air outdoor heat pump and air conditioner system.The units are factory-equipped with a transformer and blower control for applications without auxiliary heat. Electric heat accessory kits (PHK-) can be ordered for field installation of additional heat where required.These instructions, and any instructions packaged with mating components and/or accessories, should be carefully read prior to beginning installation. Note particularly any CAUTIONS or WARNINGS in these instructions and all labels on the units.These instructions are intended as a general guide only, for use by qualified personnel and do not supersede any national or local codes in any way. Compliance with all local, state, provincial, or national codes pertaining to this type of equipment should be determined prior to installation.Inspection of Shipment Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. File a claim with the transportation company.If any damages are discovered and reported to the carrier, DO NOT INSTALL THE UNIT, as claim may be denied.Check the unit rating plate to confirm specifications are as ordered.Limitations The unit should be installed in accordance with all national and local safety codes.Limitations of the unit and appropriate accessories must also be observed.The unit must not be installed with any ductwork in the outdoor air stream. The outdoor fan is not designed to operate against any additional static pressure.

Location The unit is designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings. The location must also allow for adequate service access.The unit must be installed on a solid foundation that will not settle or shift. Adequate structural support must be provided. Install the unit in level position. Isolate the base from the building structure to avoid possible transmission of sound or vibration into the conditioned space.The heat pump unit foundation should be raised to a minimum of 3″ above finish grade. In areas that have prolonged periods of temperature below freezing and snowfall, the heat pump unit should be elevated above the average snow line. Extra precaution should be taken to allow free drainage of condensate from defrost cycles to prevent ice accumulation. The unit should not be located near walkways to prevent possible icing of surface from defrost condensate.Avoid placing the unit near quiet areas, such as sleeping quarters or study rooms. Normal operating sound levels may be objectionable if the unit is placed near certain rooms.For improved start-up performance, the condenser coil should be washed with suitable detergent to remove any residue from manufacturing processes.Use of Unit During Construction Use of this unit as a construction heater or air conditioner is not recommended during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.If this unit has been used for heating or cooling of buildings or structures under construction, the following conditions must be met or the warranty will be void:· A room thermostat must control the unit. The use of fixed jumpers that will provide continuous heating or cooling is not allowed.· A pre-filter must be installed at the entry to the return air duct.· The return air duct must be provided and sealed to the unit.· Return air temperature range between 55°F (13°C) and 80°F (27°C) must be maintained.· Air filters must be replaced and pre-filters must be removed upon construction completion.· The input rate and temperature rise must be set per the unit rating plate.· The heat exchanger, components, duct system, air filters and evaporator coil must be thoroughly cleaned following final construction clean-up.

Page 8 of 19

Issue 2107

507296-03

· The unit operating conditions (including airflow, cooling operation, ignition, input rate, temperaturerise and venting) must be verified according to these installation instructions.

Clearances All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances to combustibles required for construction, servicing, and proper unit operation.In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material.In Canada, units may be installed on combustible floors. Units must be installed outdoors.Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet.

Front of unit

Clearance to Combustibles0 in.

Clearance for Service Access24 in.

Back of unit

0 in.

Left side

0 in.

Right side

0 in.

0 in. 24 in. 24 in.

Base of unit

0 in.

0 in.

Top of unit

0 in.

48 in.

For any future service, installer must provide access to screws of top and rear panels.

Table 1. Minimum Clearances

Compressor Units are shipped with compressor mountings factory adjusted and ready for operation. Do not loosen compressor mounting bolts.Roof Curb Installation If a roof curb is used, follow the manufacturer’s installation instructions and be sure that all required clearances are observed (see Clearances section).Prior to setting the unit on the roof curb, the shipping bracket located underneath the unit must be removed. Remove the two screws in the base rail (located on the front and rear sides of the unit). The four screws and the bracket can be discarded. See Figure 1.Rigging Unit Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation.1. Connect rigging to the unit base rails using both holes in each corner.2. All panels must be in place for rigging. 3. Place field-provided spreaders in place. Spreadersmust be of adequate strength and length (must exceed unit dimension by 6 inches).Units may also be moved or lifted with a forklift. The lengths of the forks of the forklift must be a minimum of 42 inches.

Field-Provided Lifting Spreaders Recommended

507296-03

Shipping Bracket and Mounting Screws Must be Removed for Rooftop or Downflow ApplicationFigure 1.Issue 2107

Page 9 of 19

CAUTIONBefore lifting a unit, make sure that the weight is distributed equally on the cables so that it will lift evenly.High Voltage Power Entry Thermostat Wire EntryGas EntryFigure 2.Unpacking Locate the four stacking brackets at each corner of the top panel. Remove the screws and washers that secure these brackets. All screws must be re-installed. The washers and stacking brackets can be discarded. Remove the bag and remaining packaging material, which can be discarded. Locate the four plastic fork slot bumpers on the base rails. Remove the fasteners and bumpers and discard.CAUTIONAs with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.Service Access Access to all serviceable components is provided by four removable panels: upper access panel (for blower, ID coil, and optional filter), auxiliary heat access, control access panel, and compressor access.

Electrical WiringAll field wiring must be done in accordance with National Electrical Code recommendations, local codes, and applicable requirements of UL Standards, or in accordance with Canadian Electrical Code recommendations, local codes, or CSA Standards. Power wiring, disconnect means, and over-current protection are to be supplied by the installer. Refer to the unit rating plate for maximum over-current protection and minimum circuit ampacity, as well as operating voltage. The power supply must be sized and protected according to specifications supplied.The unit must be grounded with a separate ground conductor. See Figure 4 for typical field wiring connection. The wiring diagram can be found on the unit inside the access panel. Low voltage control wiring are terminal strip or pigtail leads located on the main control box and are color-coded to match the connection called out on the wiring schematic.NOTE: An optional bottom-entry power kit is available for these units. See the kit instructions for proper installation details.

CAUTIONWhen connecting electrical power and control wiring to the unit, waterproof-type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation.

Units are factory wired for a 230-volt power supply. If power supply is 208 volts, it will be necessary to change a wire connection on the unit transformer from 240V terminal to 208V terminal as shown on the wiring diagram.Use only copper conductors.If any of the original unit wiring is replaced, the same size and type wire must be used.

Contactor

Ground Lug

Field-Supplied Fused or Circuit Breaker Disconnect

Single Phase Power Supply

WARNINGThis unit is charged with HFC-410A refrigerant. Operating pressures for units charged with HFC-410A are higher than pressures in units charged with HCFC22. All service equipment MUST be rated for use with HFC-410A refrigerant.

If 208 Volt is supplied, transformer connection must be changedFigure 3. 208/230 Line Voltage Wiring

Page 10 of 19

Issue 2107

507296-03

! CAUTION Do not connect C connections except when required by the indoor thermostat. Refer to thethermostat installation instructions.

Thermostat The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow the manufacturer’s instructions enclosed with the thermostat for general installation procedure. Color-coded insulated wires (#18 AWG) should be used to connect the thermostat to the unit. A minimum of five wires are required for proper installation.

THERMOSTAT R C Y1 O W G

OUTDOOR UNIT R Red C Blue Y1 Yellow* O OrangeW White G Green

*”O” connection used only on heat pump models SINGLE PHASE

L2

L1

GROUND

SCREW

The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should not be sized to match the dimensions of the duct connections on the unit.The unit is shipped ready for horizontal flow (side duct connections) or downflow (bottom duct connections). All units are equipped with a drain pan overflow switch that is installed and wired at the factory. Duct attachment screws are intended to go into the duct panel flanges. Duct to unit connections must be sealed and weather proofed.For horizontal duct systems:1. Remove the duct covers on side of the unit. They can be discarded.2. Install the duct system to the unit.For downflow duct systems:1. Remove the duct covers on side of the unit. Keep the screws and the covers as they will be re-installed later.2. Remove the downflow duct covers located inside unit. Remove the four screws securing each cover. Remove the covers from the unit. They can be discarded.3. Remove screws located between the supply and return air openings that attach the blower deck to the base pan. These screws can interfere with bottom duct connections or roof curb seals. Discard these screws.4. Install the duct system to the unit.5. Re-install the duct covers removed in Step 1.

POWER WIRING 208/230-1-60(75° MIN. WIRE) POWER WIRING 24V CONTROL WIRING(NEC CLASS 2)W1, W2 can be used to stage electric heat accessory on 10, 15 & 20 kW models. 5 And 7 kW heater accessory function off W1 only.Figure 4. Typical Wiring ConnectionsDuct SystemThe duct system should be designed and sized according to the methods in the Air Conditioning Contractors of America (ACCA) manual that is most appropriate to the installation application.A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. It is recommended that supply and return duct connections at the unit be made with flexible joints.

FiltersAir filters are not supplied with the unit. A field-provided air filter must always be installed ahead of the evaporator coil and must be kept clean or replaced. Dirty filters will reduce the airflow of the unit.An optional filter rack kit may be purchased separately for installation inside the unit’s coil compartment. Air filter sizes are shown in Table 2 for use with filter rack kit.

NOTE:The filter rack must be installed prior to installation of the unit in applications where access to the rear panel is limited.

Unit Model 24,30,36 42,48,60

Filter 1 14 x 20 x 1 20 x 20 x 1

Filter 2 20 x 20 x 1

Table 2. Unit Air Filter Sizes – inches

507296-03

Issue 2107

Page 11 of 19

Condensate DrainThis package unit is equipped with a 3/4″ FPT coupling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads.Do not operate unit without a drain trap. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will prevent positive drainage without a proper trap.The condensate drain line must be properly trapped, routed to a suitable drain and primed prior to unit commissioning.NOTE: Install drain lines and trap so they do not block service access to the unit.See Figure 5 for proper drain arrangement. The drain line must pitch to an open drain or pump to prevent clogging of the line. Seal around the drain connection with suitable material to prevent air leakage into the return air system.To prime trap, pour several quarts of water into drain, enough to fill drain trap and line.CAUTIONDrain lines should be hand-tightened only. Do not use tools to tighten fitting into drain.

Minimum Pitch:

1 in (25) Per 10″

(3048 mm) of

Unit

Line

Open Vent

Crankcase Heater (if used) Some models may be equipped with a crankcase heater to prevent excessive migration of liquid refrigerant into the compressor during off cycles. Power must be maintained to the unit to keep this feature active.Except as required for safety while servicing, do not open the system disconnect switch.Heater Kit Accessory (if used) The unit is fully equipped for cooling operation without auxiliary heat. A heater kit accessory may also be used. To install the heater kit accessory (see Figure 7):1. Disconnect the power and open the main control access.2. Disconnect the plug separating the high voltage wire harness. Remove the high voltage wire harness plug and discard.3. Remove the heater blockoff by removing the four screws holding it in place.4. Insert the heater into the control panel and fasten in the same mounting holes.5. Plug the heater wiring harness into the wire harness on the control assembly. Field wiring of the auxiliary heater is separate from the unit power supply. Wire the power supply wiring for the heater to the appropriate connections on the heater kit.Sequence of OperationCooling When the thermostat is in the cooling mode, the O circuit is powered, which energizes the reversing valve. Upon cooling demand, the thermostat closes circuit R and Y. Closing R and Y closes the unit contactor, starting the compressor and outdoor fan. The thermostat automatically closes the R to G circuit, which brings on the indoor blower at the same time. Upon satisfying cooling demand, the thermostat will open the above circuits and open the main contactor, stopping the compressor and outdoor fan. If the unit is equipped with a delay timer, the blower will continue to operate for 60 to 90 seconds, which improves system efficiency.

Mounting FrameTrap must be deep enough to offset maximum static difference (generally, 3 inches (76 mm) minimum). In addition, the drain line must be supported if longer than 10 feet.Trap must be primed at start-up.Figure 5. Typical Condensate Drain Connection

Heating – Heat Pump Stage Upon heating demand, the thermostat closes circuit R to Y, which closes the unit contactor, starting the compressor and outdoor fan. The reversing valve is not energized in the heating mode. The thermostat again automatically brings on the indoor fan at the same time. Upon satisfying heating demand, the thermostat opens above circuits and stops unit operation.Heating – Auxiliary Electric Heat Upon heating demand for auxiliary electric heat, the thermostat closes circuit R to W, which energizes the

Page 12 of 19

Issue 2107

507296-03

heater sequencers as well as the indoor blower. Upon satisfying auxiliary heat demand, the thermostat opens above circuits and heating elements sequence off; blower continues to operate until all heating elements have turned off.Defrost System The defrost system includes two components: the defrost thermostat and the defrost control.Defrost ThermostatThe defrost thermostat is located on the evaporator coil. When the defrost thermostat senses 35°F or cooler, the thermostat contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 60°F.Defrost ControlThe defrost control board includes the combined functions of time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections (see Figure 6).The control provides automatic switching from normal heating operation to defrost mode and back. During the compressor cycle (call for defrost), the control accumulates compressor run time at 30, 60, 90 minute field-adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and the defrost begins.

DEFROST TIMING PINS (P1)TEST PINSCOMPRESSOR DELAY PINS REVERSING VALVES87LOW PRESSURE SWITCHDEFROST THERMOSTAT (S6)S4HIGH PRESSURE SWITCH

DIAGNOSTIC LEDS24V TERMINAL STRIP CONNECTIONSSERVICE LIGHT CONNECTIONS

Figure 6. Defrost Control Board

1. An on-board outdoor ambient temperature sensor on the defrost control bypasses the low pressure switch during low ambient temperature below 15°F in heating mode to eliminate nuisance low pressure trips.NOTE: 15°F is an approximate temperature, depending upon model and installation location.2. A defrost cycle will initiate when there has been a low pressure switch trip; the defrost sensor must be closed and the defrost time interval must not have expired.

507296-03

Figure 7. Heater Kit Accessory InstallationIssue 2107

Page 13 of 19

3. At the end of the defrost cycle, when the unit goes back to heating mode, the low pressure switch is checked to see if it has reset. If so, the strikeout is not counted. This prevents lockout during extreme winter conditions.Defrost Control Timing PinsEach timing pin selection provides a different accumulated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. It is intended that this product should be set at the 60-minute time interval at initial installation. If the timing selector jumper is not in place, the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.NOTE:For geographic areas that experience low temperature and high humidity conditions (below 35°F and above 80% RH), the defrost timer pin must be field set at installation to a 60 or 30 minute defrost interval to ensure reliable system operation while in heating mode.A test option is provided for troubleshooting. The test mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power up, the control will ignore the test pins. When the jumper is placed across the TEST pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and reapplied.Compressor Delay (Quiet Shift) The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.NOTE: The 30-second “off” cycle is not functional when jumpering the TEST pins.Time Delay The defrost control includes a compressor timer, which ensures the compressor is off for a minimum amount of time between operating cycles.The timed-off delay is 5 minutes long. The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens.

The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.

Pressure Switch Circuit High and low pressure switches are connected to the defrost control board on heat pump models. Air conditioning models have a high pressure switch installed in line with compressor contactor coil (see Figure 6).During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch (see Table 3).The unit will remain locked out until power to the board is interrupted, then re-established, or until the jumper is applied to the TEST pins for 0.5 seconds.NOTE: The defrost control board ignores input from the low pressure switch terminals as follows:· During the TEST mode· During the defrost cycle· During the 90-second start-up period· For the first 90 seconds each time the reversing valve switches heat/cool modesIf the TEST pins are jumpered and the 5-minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90-second start-up period.

Diagnostic LEDs The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition as shown in Table 3.

Defrost Board Diagnostic LEDs

Green LED (DS2)

Red LED (DS1)

Condition

OFF

OFF

No Power to Control

Simultaneous slow FLASH

Normal Operation / Power to Control

Alternating Slow FLASH 5-min Anti-Short-Cycle Delay

ON

Slow FLASH

Low Pressure Switch Ignored (Low Ambient)

Fault & Lockout Codes

OFF

Slow FLASH Low Pressure Switch Fault

OFF

ON

Low Pressure Switch Lockout

Slow FLASH

OFF

High Pressure Switch Fault

ON

OFF

High Pressure Switch Lockout

Table 3. Defrost Control (CMC1) Diagnostic LEDs

Page 14 of 19

Issue 2107

507296-03

System Performance This equipment is a self-contained, factory optimized refrigerant system, and should not require adjustments to system charge when properly installed. If unit performance is questioned, perform the following checks.

Ensure unit is installed per manufacturer’s instructions and that line voltage and air flow is correct. Refer to the following tables for proper performance value. The indoor metering device varies by model; when checking performance of a unit using an orifice for metering, refer to the suction superheat value to judge performance. When checking performance of a unit that uses an expansion valve for metering, refer to the subcooling value to judge system performance.

If the measured performance value varies from table value allowance, check internal seals, service panels and duct work for air leaks, as well as restrictions and blower speed settings. If unit performance remains questionable, remove system charge, evacuate to 500 microns, and weigh in refrigerant to nameplate charge. It is critical that the exact charge is re-installed. Failure to comply will compromise system performance.

If unit performance is still questionable, check for refrigerant related problems, such as blocked coil or circuits, malfunctioning metering device or other system components.

Model

Suction

Liquid

Superheat +/- 3° Subcooling +/- 2°

2 Ton

13

2.5 Ton

16

3 Ton

14

3.5 Ton

14

4 Ton

16

5 Ton

17

Based on outdoor ambient temperature of 82°F, and indoor entering air of 80°F db, 67°F wb.

Table 4. Air Conditioner Unit Cooling System Performance Values

Model

Suction

Liquid Subcooling

Superheat +/- 3°

+/- 2°

2 Ton

18

2.5 Ton

16

3 Ton

16

3.5 Ton

22

4 Ton

22

5 Ton

5

Based on outdoor ambient temperature of 82°F, and indoor entering air of 80°F db, 67°F wb.

Table 5. Heat Pump Cooling System Performance Values

Model

Liquid Subcooling +/- 2°

2 Ton

25

2.5 Ton

15

3 Ton

28

3.5 Ton

20

4 Ton

35

5 Ton

28

Based on outdoor ambient temperature of 47°F, and indoor entering air of 70°F db.

Table 6. Heat Pump Heating System Performance Values

Maintenance

WARNINGBefore performing maintenance operations on the system, shut off all electrical power to the unit. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury or death.

Periodic inspection and maintenance normally consists of changing or cleaning the filters and cleaning the evaporator coil. On occasion, other components may also require cleaning.Filters Filters are not supplied with the unit. Inspect once a month. Replace disposable or clean permanent type as necessary. Do not replace permanent type with disposable.Motors Indoor and outdoor fan and vent motors are permanently lubricated and require no maintenance.Indoor fans are equipped with a permanent magnet constant torque motor. These motors remain energized and are controlled by 24V signals. For high static applications, use Tap 3 for cooling speed and Tap 5 for heating speed.Evaporator Coil Dirt and debris should not be allowed to accumulate on the evaporator coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning. Care should be used when cleaning the coil so that the coil fins are not damaged.Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.

507296-03

Issue 2107

Page 15 of 19

Condenser Coil Clean condenser coil annually with water and inspect monthly during the cooling season.Condenser coil may need to be cleaned at startup in case oil from the manufacturing process is found on the condenser coil.

80 DB / 67 WB Deg. Return Air

Cooling

Input

Pressure 65°

(1000 BTU)

24

135

30

135

36

135

Suction

42

129

48

132

60

130

24

250

30

247

36

250

Liquid

42

248

48

265

60

256

Table 7. Cooling Performance – AC ModelsAir Temperature Entering Evaporator Coil, Degree F

70°

75°

80°

82°

85°

90°

95°

100° 105° 110° 115°

136

137

139

139

141

143

146

148

150

152

154

137

140

142

143

145

147

150

152

154

155

157

137

140

142

143

144

147

149

151

152

154

155

132

135

139

140

141

143

145

146

147

148

149

136

139

143

144

145

146

147

149

151

152

154

131

133

134

135

136

139

141

144

146

149

152

266

282

298

304

318

340

363

388

413

438

463

269

292

314

323

336

358

380

406

432

457

483

275

301

326

336

351

375

399

423

446

470

493

271

293

316

325

339

362

385

411

436

462

487

286

308

329

338

352

376

400

427

455

482

509

276

296

316

324

340

365

386

415

438

473

503

Page 16 of 19

Issue 2107

507296-03

80 DB / 67 WB Deg. Return Air

Cooling

Input

Pressure 65°

(1000 BTU)

24

130

30

130

36

136

Suction

42

127

48

132

60

133

24

236

30

254

36

267

Liquid

42

238

48

248

60

245

Table 9. Cooling Performance – HP / DF ModelsAir Temperature Entering Evaporator Coil, Degree F

70°

75°

80°

82°

85°

90°

95°

100° 105° 110° 115°

134

138

141

143

145

148

151

152

154

155

156

133

136

139

140

141

143

145

147

149

151

153

138

140

142

143

144

145

147

149

151

152

154

131

134

138

139

141

144

147

147

148

148

148

135

138

142

143

144

147

149

151

152

154

155

134

135

136

136

137

138

140

142

146

149

146

255

275

294

302

316

339

362

388

414

440

466

274

294

314

322

336

360

383

410

437

464

491

285

303

322

329

343

367

391

417

443

468

494

259

280

302

310

324

348

371

396

421

445

470

271

294

317

326

340

363

386

412

438

464

490

276

296

316

312

340

365

373

415

438

473

479

Table 8. Heating Performance – HP / DF Models

70 Deg. F Return Air

Air Temperature Entering Evaporator Coil, Degree F

Cooling

Input

Pressure 0°

(1000 BTU)

10°

17°

20°

25°

35°

40°

47°

50°

55°

60°

24

33

41

49

60

65

73

89

97

108

113

121

129

30

31

38

45

55

59

66

81

88

98

102

109

117

36

35

42

49

58

62

69

82

89

98

102

109

115

Suction

42

25

33

42

54

59

68

85

94

106

111

120

129

48

32

39

47

57

62

69

84

92

102

107

114

122

60

30

37

44

54

58

65

80

87

97

101

108

116

24

249

256

263

272

276

283

296

303

312

316

323

329

30

246

253

260

270

274

281

295

302

312

316

323

330

36

251

258

265

275

279

286

300

307

317

321

328

335

Liquid

42

297

300

304

309

311

315

322

326

331

333

337

341

48

289

297

306

318

323

332

349

358

370

375

384

393

60

272

281

290

302

307

316

334

343

355

360

369

378

507296-03

Issue 2107

Page 17 of 19

Page 18 of 19

Wiring Diagrams

Figure 8. Connections Diagram – A/C Constant TorqueIssue 2107

CRANK CASE HEATER (IF USED) HR1

BLK BLK

CONNECTION DIAGRAM A/C (CONSTANT TORQUE BLOWER)SINGLE PHASE

NOTE: TAP1 FOR FAN ONLY TAP 2 FOR COOLING TAP3 FOR HIGH STATIC COOLING TAP4 AND TAP5 FOR ELECTRIC HEAT- REFER TO HEATING LABEL

INDOOR BLOWER MOTORN GL CB-3

W1 & W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 10, 15 & 20KW MODELS5 & 7.5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY.

J2-1

BLK

BLK

54 3 2 1

J2-6 J2-5 BLK

WHT

BLU

WHT

GRN

L1

K1-1 CONTACTOR

T1

C12 DUAL CAPACITOR

YELH

C

S

R

C

COMPRESSOR

B1

F

TRANSFORMER TI

L B3INDOOR BLOWER MOTOR

G

N

BLK W/ STRIPE

BLK 208V 240V24V

BLU

RED

YEL

YELCONTACTOR KIGRN

J1-12

S173

YEL

BLU S79 YEL

THERMOSTAT

WHT

G S1W1 C R

S4

J1-11

YEL Y

J1-2 ORG J1-1 BLACK J1-3

YEL W/ STRIPE

BLK RED

208/230-1-60 POWER SUPPLY WITH MIN.75 C COPPER WIRE

T2CONTACTOR K1-2L2

GRY

OUTDOOR

FAN

B4

MOTOR

PUR

LINE VOLTAGE FIELD INSTALLED

YEL W/ STRIPE J2-2

J2-4J1: PLUG THROUGH CONTROL PANEL (12 PIN) J2: PLUG FOR ACCESSORY HEAT (6 PIN)

THERMAL PROTECTION SWITCH (IF USED)

LOW PRESSURE SWITCH (IF USED)

NOTE: IF ANY OF THE ORIGINAL WIRE IS REPLACED THE SAME SIZE AND TYPE WIRE MUST BE USED. USE COPPER CONDUCTOR ONLY, MIN 75 C WIRE

HIGH PRESSURE SWITCH

CONTROL CIRCUIT WIRING TO BE 24 VOLT, N.E.C. CLASS 2

WARNINGELECTRIC SHOCK HAZARD. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.

537663-01

507296-03

Page 19 of 19

Figure 9. Connections Diagram – Heat Pump Constant TorqueIssue 2107

DIAGNOSTIC CODES FOR DEFROST CONTROL LEDS(See instructions or markings on System Diagnostic Module for codes of System Diagnostic Module)

Description No Power to Control Normal Operation / Power toControl Anti-Short Cycle Lockout Low Pressure Switch Fault Low Pressure Switch Lockout High Pressure Switch Fault High Pressure Switch Lockout

DS1 (GREEN) OFF

DS2 (RED) OFF

Simultaneous Slow Flash

Alternate Slow Flash

OFF

Slow Flash

OFF

ON

Slow Flash

OFF

ON

OFF

Note: Because the Pressure Switches are monitored only when “Y1” (Input) is active, the code for pressure switch open will not be seen when “Y1” is off. Instead, the “Normal Operation” or “Anti Short Cycle” code will be seen.Also, when a pressure switch opens and caused a short cycle lockout, the pressure switch-open code will be seen until it closes, then the short cycle lockout code will flash unless it has already expired.J1: PLUG THROUGH CONTROL PANEL (12 PIN) J2: PLUG FOR ACCESSORY HEAT (6 PIN)

J2-1 BLK

BLK

BLK

208/230V-1PH,60HZ

L1 CONTACTOR

CRANK CASE HEATER (IF USED) HR1

BLK BLK

K1-1 BLKT1

C12

C

S

R

FAN

NC

C

DEFROST CONTROLCMC1

F

PUR

ORG C

COMPRESSOR B1

YEL

H

DUAL CAPACITOR

J1-2 J1-1BLK J1-3

T1 TRANSFORMER

208V 240V24V

L

B3 INDOOR BLOWER MOTOR

G

N

WHT

BLU

BLU

BLK RED

CONTACTOR K1-2

L2

T2

GRY YEL W/STRIPE

CONDENSER FAN MOTORB4J2-2

YEL W/STRIPE

YEL GRNYEL

CONNECTION DIAGRAM, HEAT PUMP CONSTANT TORQUE BLOWER, SINGLE PHASENOTE: TAP1 FOR FAN ONLY TAP 2 FOR COOLING TAP3 FOR HIGH STATIC COOLING TAP4 AND TAP5 FOR ELECTRIC HEAT- REFER TO HEATING LABEL

NOTE: IF ANY OF THE ORIGINAL WIRE IS REPLACED THE SAME SIZE AND TYPE WIRE MUST BE USED. USE COPPER CONDUCTOR ONLY, MIN 75 C WIRE

INDOOR BLOWER MOTOR

N

G

L

C

543 2 1

W1 & W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 10, 15 & 20KW MODELS5 & 7.5 KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY.

J2-6

J2-5

BLK

WHT

BLU RED

FLOAT SWITCH (IF USED)

YEL

WHT GRN

REV. VALVEL1LOW PRESSURE SWITCHS79DEFROST T’STATS6BLUCONTACTORK1

DEFROST CONTROLFAN

GRY GRY BLK BLKBRN BRN

J1-5 J1-6 J1-8 J1-9 J1-7J1-10

O-OUT LO-PS DF

COMMON

Y1 OUT

YEL

J1-11

YEL

J1-12 HI-PS

THERMAL PROTECTION SWITCH (IF USED)S173

W1 C L R24 V O Y1CMC1

BLU

J2-4

HIGH PRESSURE SWITCHS4

WHT

WHT BLURED ORG YEL

THERMOSTATG W1 C R O YS1 CONTROL CIRCUIT WIRING TO BE 24 VOLT, NEC CLASS-2

WARNINGELECTRIC SHOCK HAZARD. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.

LINE VOLTAGE FIELD INSTALLED

537661-01

report this ad

507296-03

[xyz-ips snippet=”download-snippet”]