SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the Smart-UPS and batteries.
Read these instructions carefully and look at the equipment to become familiar with the equipment before attempting to install, operate, service or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies aprocedure.
The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.
DANGERDANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNINGWARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
DANGERCAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury
Product Handling Guidelines
<18 kg <40 lb
18-32 kg 40-70 lb
32-55 kg 70-120 lb
>55 kg >120 lb
Safety and General Information
Adhere to all national and local electrical codes.
All wiring must be performed by a qualified electrician.
Changes and modifications to this unit not expressly approved by APC could void the warranty.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.
Replace the battery immediately when the UPS indicates battery replacement is necessary.
The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs), in a rack.
Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.
Always install peripheral equipment above the UPS in rack-mount configurations.
Additional safety information can be found in the Safety Guide supplied with this unit.
Product Description
The APC by Schneider Electric Smart-UPS™ is a high performance uninterruptible power supply (UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to acceptable levels or the batteries are completely discharged.
This user manual is available on the enclosed Documentation CD. Download the latest version (if any) of the user manual from the APC by Schneider Electric web site, www.apc.com
Specifications
For additional specifications, refer to the APC by Schneider Electric Web site at www.apc.com
Weight Specifications
UPS + Battery Pack
Battery Pack
24 kg (53 lb)
10.5 kg (23 lb)
Temperature
Operating
0° to 40° C (32° to 104° F)
Storage
-15° to 45° C (5° to 113° F) charge UPS battery every six months
Maximum Elevation
Operating
3,000 m (10,000 ft)
Storage
15,000 m (50,000 ft)
Humidity
0% to 95% relative humidity, non-condensing
0° to 40° C (32° to 104° F)
Battery
CAUTION :RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
Replace the battery at least every 5 years.
Replace the battery immediately when the UPS indicates battery replacement is necessary.
Replace battery at the end of its service life.
Replace batteries with the same number and type of batteries as originally installed in the equipment.
Replace the battery immediately when the UPS indicates a battery over temperature condition, or UPS internal overtemperature, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Replace all battery modules (including the modules in External Battery Packs) which are older than one year, when installing additional battery packs or replacing the battery module(s)
Failure to follow these instructions could result in equipment damage and minor or moderate injury.
Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.
Maintenance free, sealed lead acid
UPS model
Replacement Battery Pack
SMT1200RMJ1U
SMT1500RM1U
SMT1500RMI1U
APCRBC88J
APCRBC88
APCRBC88
Replace used batteries with APC by Schneider Electric approved batteries.
To order a replacement battery go to the APC by Schneider Electric Web site, www.apc.com.
Always recycle used batteries.
For information on recycling a used battery, refer to the Battery Disposal
Information sheet included with the replacement battery.
Product Overview
Front panel features
Battery
Battery connector
Display interface
Bezel
Rear panel features
Circuit breaker/Overload protection
UPS input
Controlled outlet group 1
Controlled outlet group 2
RJ45 connector – serial UPS monitoring port
USB port
SmartSlot for optional accessory card1200/1500 VA 100/120 Vac1500 VA 230 Vac
Installation
For UPS installation information, refer to the Smart-UPS 1200/1500 VA 100/120/230 Vac Rack-Mount 1U Installation Guide that is included with the UPS. The Installation Guide is also available on the Documentation CD included with the UPS and on the APC by Schneider Electric Web site, www.apc.com.
Operation
Connect Equipment
CAUTION: RISK OF ELECTRIC SHOCK
Adhere to all local and national electrical codes.
Wiring should be performed by qualified electrician.
Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in minor or moderate injury.
Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.
Connect equipment to the outlets on the rear panel of the UPS.
Connect the UPS to the building utility power. Connect the UPS to a two pole, three wire, grounded source only.
To use the UPS as a MASTER ON/OFF switch, turn on equipment that is connected to the UPS.
To turn on the UPS and all connected equipment press the ON/OFF button on the front panel of the UPS.
Refer to “Switched Outlet Groups” on page 12 for information on switched outlet group configuration.
Outlet type and location may vary.Rear panel features
Serial port: Connect a computer to use power management software.
USB port: Connect a computer to use power management software.
Display Panel
Overview
Online LED
On Battery LED
Alert LED
Replace Battery LED
UP/DOWN arrow buttons
Display screen
ENTER button
UPS ON/OFF button
ESCAPE button
Display interface operation
Press either the ESC or ENTER buttons to access the main menu.
Use the UP/DOWN arrow buttons to scroll through menu options.
Press ENTER to view sub menus. Scroll through the list of options.
Press ENTER to select an option. Press ESCAPE to exit a sub menu and return to a main menu.
Menu overview
The display interface has Standard and Advanced menu screens. The preference for Standard or Advanced menu options is made during initial installation and can be changed at any time using the Configuration menu.
Standard menus are the most commonly used menus. The default screen shows Load and Battery Capacity bar graphs.
The Advanced menus include more status information and additional sub menus. The default screen shows scrolling status information.
Note: Actual menu screens may differ by model and firmware revision.
Main Menu Display Description Logs Last 10 transfer events (if applicable)About Model identification
Main Menu
Display Description
Standard Option
Advanced Option
Status* Advanced menu Status items displayed as scrolling information
At initial start up use the Setup Wizard to configure the following settings.
Function
Factory Default
Options
Description
Language
English
English
French
German
Spanish
Italian
Portuguese
Japanese
The language for the display interface. Language options will vary by model.
OutputVoltage230 Vac models only
230 Vac
220 Vac
230 Vac
240 Vac
UPS output must be off to configure this setting.
Local Power Quality
Good
Good
Fair
Poor
Select the desired utility input power quality.
Good: The UPS will go on battery power more often to provide the cleanest power supply to connected equipment
Fair: The UPS will tolerate some voltage fluctuations before switching to battery power.
Poor: The UPS will tolerate more voltage fluctuations and will go on battery power less often.
The Power Quality setting will automatically change the high and low transfer points and the transfer sensitivity setting.
Menu Type
Standard
Standar
Advanced
The Advanced menus include all parameters. The Standard menus display a limited set of menus and options.
Date
UPS manufacture date + 90 days
mm-yyyy
At initial start up, enter the current date.
General settings
Configure these settings at any time, using the display interface or PowerChute™ software
Function
Factory Default
Options
Description
High TransferPoint
100 Vac models: 108 Vac
120 Vac models: 127 Vac
230 Vac models: 253 Vac
100 Vac models: 108-114 Vac
120 Vac models: 127-136 Vac
230 Vac models: 242-276 Vac
To avoid unnecessary battery usage, the high and low transfer points can be adjusted.
Set the transfer point higher if the AC voltage is chronically high.
Set the transfer point lower if the AC voltage is chronically low.
When the Power Quality setting is changed the high and low transfer points will automatically be adjusted.
230 Vac models only: The transfer point options will change based on the output voltage setting.
Low TransferPoint
100 Vac models: 92 Vac
120 Vac models: 106 Vac
230 Vac models: 207 Vac
100 Vac models: 86-92 Vac
120 Vac models: 97-106 Vac
230 Vac models: 186-216 Vac
Transfer Sensitivity
Normal
Normal
Reduced
Low
Set the sensitivity to a level that is appropriate for the connected equipment.
Normal: The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment.
Reduced: The UPS will tolerate some voltage fluctuations before switching to battery power.
Low: The UPS will tolerate more voltage fluctuations and will go on battery power less often.
When the Power Quality setting is changed the transfer sensitivity will automatically be adjusted.
Low Runtime Alert
120 sec
Value set in seconds
The UPS will emit an audible alarm when the remaining runtime has reached this level.
Date of Last Battery Replacement
Date set at factory
Reset this date when the battery module is replaced.
Audible Alarm
On
On
Off
The UPS will mute all audible alarms if this is set to Off or when any of the display buttons are pressed.
Display Mode
Auto Dim
Always O
Auto Dim
Auto Off
The display interface remains continuously illuminated.
The display interface illumination will diminish after two minutes of inactivity.
The display interface illumination will extinguish after two minutes of inactivity.
Function
Factory Default
Options
Description
Auto Self-Test Interval
On start up and 14 days after each self-test.
Last test + 14 days
Last test + 7 day
Start up+ 14 day
Start up + 7 days
The interval at which the UPS will execute a self-test.
The batteries must be charged to at least 70% capacity to perform a self-test.
On start up onl
Never
“Start up” on these menus refers to any time the UPS is turned on.
Reset to Factory Default
No
Yes
No
Restore the UPS factory default settings.
Switched Outlet Groups
Overview
The UPS has two Switched Outlet Groups. Each can be configured to independently perform the following actions:
Turn off: Disconnect from power immediately and restart only with a manual command.
Turn on: Connect to power immediately.
Shutdown: Disconnect power, and automatically reapply power when utility power becomes available
Reboot: Shut down and restart.
Turn on or off in a specified sequence
Automatically turn off or shut down when various conditions occur.
Note: If the Switched Outlet Groups are not configured, all of the outlets on the unit will provide battery backup power.
Configure the Switched Outlet Groups
Connect equipment to the Switched Outlet Groups.
Nonessential equipment that should shut off quickly in the event of a power outage to conservebattery runtime can be added to a short power off delay.
If equipment has dependent peripherals that must restart or shut down in a specific order, suchas an ethernet switch that must restart before a connected server, connect the devices to separate groups
Equipment that needs to reboot independently from other equipment should be added to a separate group.
Use the Configuration menus to configure how the Switched Outlet Group will react in the eventof a power outage.
Customize Switched Outlet Groups
Use the Configuration menu to change the Switched Outlet Group settings.
Function
Factory Default
Options
Description
Turn On Delay
0 sec
Set the value in seconds
The amount of time the UPS or Switched Outlet Group will wait between receiving the command to turn on and the actual startup.
Turn Off Delay
90 sec
Set the value in seconds
The amount of time that the UPS or Switched Outlet Group will wait between receiving the command to turn off and the actual shut down.
Reboot Duration
8 sec
Set the value in seconds
The amount of time that the UPS or Switched Outlet Group must remain off before it will restart.
Minimum Return Run Time
0 sec
Set the value in seconds
The amount of battery runtime that must be available before the UPS or Switched Outlet Group will turn on.
Load Shed Time On Battery
Disabled
Enable
Disable
When the unit switches to battery power, the UPS can disconnect power to the Switched Outlet Group to save runtime.
Load Shed Time On Battery
1800 sec
Set the value in seconds
The amount of time the Switched Outlet Group will continue function after the UPS begins operating on battery.
Load Shed Runtime Remain
Disabled
Enable
Disable
When the battery runtime falls below the specified value, the Switched Outlet Group will turn off.
Load Shed Runtime Remain
120 sec
Set the value in seconds
Remaining runtime required for the outlets to stay on.
Load Shed on Overload
Disabled
Enable
Disable
In the event of an overload (greater than 100% output), the Switched Outlet Group will immediately turn off to conserve power for critical loads. The Switched Outlet Group will only turn on again with a manual command.
Troubleshooting
Problem and Possible Cause
Solution
The UPS will not turn on or there is no output
The UPS has not been turned on.
Press the ON button once to turn on the UPS.
The UPS is not connected to utility power.
Ensure that the power cable is securely connected to the unit and to the utility power supply.
The input circuit breaker has tripped.
Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.
The unit shows very low or no input utility voltage.
Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage.
The UPS has detected an internal fault.
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
The UPS is operating on battery, while connected to utility power
The input circuit breaker has tripped.
Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.
There is very high, very low, or distorted input line voltage.
Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.
The UPS is beeping
The UPS is in normal operation.
None. The UPS is protecting the connected equipment.
UPS does not provide expected backup time
The UPS battery is weak due to a recent outage or is near the end of its service life.
Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated.
The UPS is experiencing an overload condition.
Check the UPS load display. Unplug unnecessary equipment, such as printers.
Display interface LEDs flash sequentially
The UPS has been shut down remotely through software or an optional accessory card.
None. The UPS will restart automatically when AC power returns.
The Alert LED is illuminated, the UPS displays a message and emits a constant beeping
The UPS has detected an internal fault.
Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.
The replace battery LED is illuminated
The battery has a weak charge
Allow the battery to recharge for at least four hours. Then, perform a Self-Test. If the problem persists after recharging, replace the battery
The replacement battery is not properly connected.
Ensure that the battery connector is securely connected.
Transport
Shut down and disconnect all connected equipment.
Disconnect the unit from mains power.
Disconnect all internal and external batteries (if applicable).
Follow the shipping instructions outlined in the Service section of this manual.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
Review the Troubleshooting section of the manual to eliminate common problems.
If the problem persists, contact APC by Schneider Electric Customer Support through the APC bySchneider Electric web site, www.apc.com.
Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
Call Customer Support. A technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
If the unit is under warranty, the repairs are free.
Service procedures and returns may vary internationally. For country specific instructions refer to the APC by Schneider Electric web site, www.apc.com.
Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.Note: Before shipping, always disconnect battery modules in a UPS or external battery pack. The disconnected internal batteries may remain inside the UPS or external battery pack.
Write the RMA# provided by Customer Support on the outside of the package
Return the unit by insured, prepaid carrier to the address provided by Customer Support.
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanshipfor a period of two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com. SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT recommendations or specifications. Further, SEIT shall not be liable for defects resulting from:
unauthorized attempts to repair or modify the product,
incorrect or inadequate electrical voltage or connection,
inappropriate on site operation conditions,
Acts of God,
exposure to the elements, or
theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES. IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE. NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BYAPPLICABLE LAW.To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the SEIT Web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase
APC by Schneider Electric Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is available at no charge in any ofthe following ways:
Visit the APC by Schneider Electric Web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests.
www.apc.com (Corporate Headquarters) Connect to localized APC by Schneider Electric Web sites for specific countries, each of which provides customer support information.
www.apc.com/support/ Global support searching APC by Schneider Electric Knowledge Base and using e-support.
Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
For information on how to obtain local customer support, contact the APC by Schneider Electric representative or other distributors from whom you purchased your APC by Schneider Electric product