1100D SERIES WIRELESS RECEIVERSInstallation Guide
Figure 1: 1100D Wireless Receiver
DESCRIPTION
The 1100D Series Wireless Receiver provides up to 32 wireless zones for XT30/XT50 Series panels.The 1100DE features 128‑bit AES encryption.The 1100D Series provides two‑way, supervised communication using 900 MHz frequency-hopping spread spectrum technology.
Compatibility
- XT30 Series panels
- XT50 Series panels with firmware Version 102 or higher
- Encryption requires panel Version 183 or higher
- 1100T Translator requires receiver firmware Version 207/301 and higher
What is Included?
- One 1100D Wireless Receiver
- Hardware Pack
PROGRAM THE PANEL
After completing each of the following steps, press CMD to advance to the next option. Refer to the panel programming guide as needed.
- Reset the panel.
- At a keypad, enter 6653 (PROG) to access the PROGRAMMER
- In SYSTEM OPTIONS, program a HOUSE CODE between 1 and See House Code Explained for more information.
- If you are programming an XT50 Series panel, select NO at the BUILT-IN 1100 WIRELESS prompt to allow the panel to use the 1100D for wireless communication.
- (1100DE only) At the 1100 ENCRYPTION prompt, select ALL to only add encrypted wireless devices to the system. Select BOTH to allow both encrypted and non-encrypted wireless devices to be programmed.
- (1100DE only) The default passphrase appears at the ENTER PASSPHRASE Press CMD to keep the default. Press any select key or area to change the passphrase and enter an 8-character hexadecimal string (0-9, A-F).
- Press CMD until STOP Press a top row select key or area to save the programming.
SELECT A LOCATION
The receiver should be centrally located between the DMP panel and the 1100 Series transmitters used in the installation based on the wiring specifications below. Use an 1106 Series Universal Wireless Transmitter to perform an LED survey.
- With the cover removed, hold the transmitter in the desired location.
- Press the tamper switch to send data to the panel and determine if communication is confirmed or faulty.Confirmed: If communication is confirmed, for each press or release of the tamper switch, the LED blinks immediately on and immediately off.Faulty: If communication is faulty, the LED remains on for about 8 seconds or flashes multiple times in quick succession. Relocate the receiver until the LED confirms clear communication.
WIRE AND MOUNT THE RECEIVER
The panel immediately recognizes the 1100D if the panel is programmed with a house code. Do not use shielded wire between the panel and receiver.
- Connect the red, yellow, green, and black wires to the PANEL terminal on the 1100D.
- Connect the other end of the wires to terminals 7, 8, 9, and 10 on the panel. See Figure 2
- Use the included #6 screws to secure the 1100D to the wall. See Figure 2 for mounting hole locations.
- Snap the cover back onto the base.
ADDITIONAL INFORMATION
Wiring Specifications for Keypad Bus
- DMP recommends using 18 or 22‑gauge unshielded wire for all Keypad and LX‑Bus circuits. Do Not use twisted pair or shielded wire for LX‑Bus and Keypad Bus data circuits. To maintain auxiliary power integrity when using 22‑gauge wire do not exceed 500 feet. When using 18‑gauge wire do not exceed 1,000 feet. Install an additional power supply to increase the wire length or add devices.
- The maximum distance for anyone circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As the wire distance from the panel increases, DC voltage on the wire decreases.
- The maximum number of devices per 2,500 feet circuit is 40.
- The maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices cannot operate properly. Refer to the panel installation guide and LX‑Bus/Keypad Bus Wiring Application Note.
Programming ZonesRefer to the panel XT30/XT50 Series Programming Guide (LT‑0981) for completely wireless programming information.When any wireless input zone for a particular address is programmed, the 1100DH responds to the panel for this address.Other devices, such as keypads or hardwired zone expanders, cannot use this address. Zones connected directly to the panel cannot be wireless. See Table 1 for designated zone numbers.
DMP PANEL | AVAILABLE ZONES | ZONE RANGES |
XT50 with built‑in receiver | 48 | 11 ‑ 14, 21 ‑ 24, 31 ‑ 34, 41 ‑ 44, 51 ‑ 54, 61 ‑ 64, 71 ‑ 74, 81 ‑ 84, 80, 85 ‑ 99 |
XT30 and XT50 (1100D Series) | 32 | 11 ‑ 14, 21 ‑ 24, 31 ‑ 34, 41 ‑ 44, 51 ‑ 54, 61 ‑ 64, 71 ‑ 74, 81 ‑ 84 |
Table 1: Zone Number Designations
1100D LED OperationThe six labeled LEDs on the 1100D PCB display wireless receiver operation and activity. See Figure 2 for LED locations and Table 1 for LED indications.House Code ExplainedThe house code identifies the panel, receiver, and transmitters to each other. The 1100D automatically sends the specified house code to wirelesstransmitters when transmitter serial numbers are programmed into the panel. The 1100D only listens for transmissions using the specified housecode or the programmed transmitters’ serial numbers.
LED |
INDICATIONS |
RF RX | Flashing yellow indicates data is being received from a transmitter. |
RF TX | Flashing green indicates data is being sent to a transmitter. |
PANEL RX | Flashing yellow indicates data is being received from a panel. |
PANEL TX | Flashing green indicates data is being sent to the panel. |
STATUS | Solid red indicates memory is being uploaded. Turns off when complete. |
PWR | Solid green indicates there is the power to the wireless receiver. |
Transmitter Supervision TImeFor listed installations, program wireless transmitter supervision times in panel zone programming according to the values specified in Table 2. Refer to the panel programming guide for complete wireless programming information.
UL Listing |
Listed Accessories |
Supervision Time |
UL 268 Smoke‑Automatic Fire Detectors | 1164 Synchronized Smoke Detector1164NS Smoke Detector with No Sounder1168 Wireless Smoke/CO/Low Temp Detector | 3 |
UL 365 Police Station Connected Burglar Accessory | 1103 Universal Transmitter | 60 |
UL 521 Heat Detectors for Fire Protective Signaling
Systems |
1183‑135F, 1183‑135R Heat Detectors | 3 |
UL 609 Local Burglar Alarm Units and SystemAccessory | 1103 Universal Transmitter | 60 |
UL 634 Connections and Switches for use withBurglar Alarm Systems Accessory | 1101, 1102, 1103, 1106 Universal Transmitters | 60 |
UL 636 Holdup Alarm Units and Systems Accessory | 1142 Two‑Button Holdup Transmitter | 60 |
UL 639 Intrusion Detection Units Accessory | 1127W, 1127C PIR Motion Detectors | 60 |
UL 985 Household Fire Warning System Accessory | 1135 Siren9060, 9063, 9862 Keypads | 240 |
UL 1023 Household Burglary System Units Accessory | 1101, 1102, 1103, 1106 Universal Transmitters1127W, 1127C PIR Motion Detectors1135 Siren1142 Two‑Button Holdup Transmitter9060, 9063, 9862 Keypads | 60 |
UL 1076 Proprietary Burglar Alarm Units Accessory | 1103 Universal Transmitter9862 Keypad | 60 |
UL 1610 Central Station Burglar Alarm Units Accessory | 1103 Universal Transmitter1135 Siren9060, 9063, 9862 Keypads | 60 |
UL 2075 Gas and Vapor Detectors and Sensors | 1168 Wireless Smoke/CO/Low Temp Detector1184 Wireless Carbon Monoxide Detector | 240 |
Table 2: Wireless Transmitter Supervision Times
Note: The 1100R Wireless Repeater and 1100T Wireless Translator follow the Receiver Supervision times for Listed Accessories.
FCC INFORMATION
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- this device must accept any interference received, including interference that may cause undesired operation.
The antenna used for this transmitter must be installed to provide a separation distance of at least 20 cm (7.874 in.) from all persons. It must not be located or operated in conjunction with any other antenna or transmitter.Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA INFORMATION
This device complies with Industry Canada Licence‑exempt RSS standards. Operation is subject to the following two conditions:
- This device may not cause interference, and
- this device must accept any interference, including interference that may cause undesired operation of the device.
This system has been evaluated for RF Exposure per RSS‑102 and is in compliance with the limits specified by Health Canada Safety Code 6. The system must be installed at a minimum separation distance from the antenna to a general bystander of 7.87 inches (20 cm) to maintain compliance with the General Population limits.1100D SERIES WIRELESS RECEIVERS
Specifications
Operating Voltage | 12 VDC Nominal |
Current Draw | 25 mA (average), 35 mA (peak) |
Frequency Range | 905‑924 MHz |
Housing Dimensions | 5.50” W x 3.75” L x 1.00” H |
Housing Color | White |
Housing Material | Flame Retardant ABS |
PatentsU. S. Patent No. 7,239,236
Ordering Information1100D‑W Standard Wireless Receiver1100DE‑W Encrypted Wireless Receiver
Certifications
California State Fire Marshal (CSFM)FCC Part 15 Registration ID: CCKPC0114R6Industry Canada: 5251A‑PC0114R6
Intertek (ETL) Listed
- ANSI/UL 365 Police Station Connected Burglar
- ANSI/UL 609 Local Burglar Alarm Units & Systems
- ANSI/UL 985 Household Fire Warning Systems
- ANSI/UL 1023 Household Burglar Alarm System Units
- ANSI/UL 1076 Proprietary Burglar Alarm Units
- ANSI/UL 1610 Central Station Burglar Alarm Units
Compatible With Devices Listed for:
- ANSI/UL 268 Smoke Detectors for Fire Alarm Signaling Systems
- ANSI/UL 634 Connections and Switches for use with Burglar Alarm Systems Accessory
- ANSI/UL 636 Safety Holdup Alarm Units and Systems
- ANSI/UL 639 Intrusion Detections Units Accessory
- ANSI/UL 2075 Gas and Vapor Detectors and Sensors
Designed, engineered, andmanufactured in Springfield, MOusing the U.S. and global components.LT-1820 1.04 21062© 2021INTRUSION • FIRE • ACCESS • NETWORKS2500 North Partnership BoulevardSpringfield, Missouri 65803‑8877800.641.4282DMP.com