DMP 1102 Series Wireless Universal Transmitter Installation Guide
Table of Contents
DMP 1102 Series Wireless Universal Transmitter
DESCRIPTION
The 1101 Series Wireless Universal Transmitters are two‑way supervisory wireless transmitters typically used for door and window applications. The 1101E features 128‑bit AES encryption.The transmitter provides a cover tamper, magnetic reed switch, and an onboard terminal block to allow for external contact wiring. Both sets of contacts, internal and external, can be programmed to operate at the same time. This allows two independent zones to operate from one 1101.The 1101 Series also features Disarm/Disable functionality. When this option is enabled, Zone Tripped messages are disabled when the system is disarmed.
Compatibility
All DMP XT Series and XR Series and all 1100 Series Wireless Receivers.To enable encryption on 1101E models, Version 183 is required for XT and XR Series panels. Version 300 is required for wireless receivers.
What is Included?
One 1101 Wireless Universal Transmitter
One Magnet with Standard and Commercial Housing
One 3.0 V lithium CR123A battery
Hardware pack
PROGRAM THE PANEL
Refer to the panel programming guide as needed. After completing each of the following steps, press CMD to advance to the next prompt.
At a keypad, enter 6653 (PROG) to access the Programmer Menu.
(1101E only) Go to SYSTEM OPTIONS. At 1100 ENCRYPTION, select ALL to only add encrypted wireless devices to the system. Select BOTH to allow both encrypted and non‑encrypted wireless devices to be programmed.
(1101E only) The default passphrase appears at the ENTER PASSPHRASE prompt. Press CMD to keep the default. Press any select key or area to change the passphrase and enter an 8‑character hexadecimal string (0‑9, A‑F).
At ZONE INFORMATION, enter the wireless zone number.
At *UNUSED*, enter the zone name.
At ZONE TYPE, press any select key or area and select the zone type.
At the NEXT ZN? prompt, select NO.
When WIRELESS? displays, select YES.
At SERIAL#, enter the eight‑digit device serial number.
At CONTACT, select either INTERNAL or EXTERNAL.Note: Use consecutive zone numbers if using both internal and external contacts.
At SUPRVSN TIME, enter a supervision time. Default is 240.
At DISARM DISABLE, select NO or YES.Note: Program the external contact first if using both internal and external contacts with Disarm/Disable functionality.
At the NEXT ZONE prompt, select YES if you are finished programming the zone. Select NO if you would like to access additional programming options.
To save panel programming, go to STOP and press CMD.
INSTALL THE BATTERY
Use a 3.0 V lithium battery, a DMP Model CR123A battery, or an equivalent model from Sony or Murata. For listed installations, use either an Energizer® 123 battery or a CR123A battery manufactured by Panasonic or Tekcell.
Push the button on the end of the 1101 and separate the two halves.
Observing polarity, place the battery in the holder and press it into place. Refer to Figure 2 during installation.
SELECT A LOCATION
The 1101 provides a Survey LED capability to allow one person to confirm communication with the wireless receiver or panel while the cover is removed.
With the cover removed, hold the transmitter in the desired location.
Press the tamper switch to send data to the panel and determine if communication is confirmed or faulty.
Confirmed: If communication is confirmed, for each press or release of the tamper switch, the LED blinks immediately on and immediately off. Repeat this test to confirm five separate consecutive LED blinks. Any indication otherwise means proper communication has not been established.Faulty: If communication is faulty, the LED remains on for about 8 seconds or flashes multiple times in quick succession. Relocate the transmitter or receiver until the LED confirms clear communication.
MOUNT THE TRANSMITTER
When mounting the transmitter, refer to Figure 2 for battery and mounting hole location.
Remove the battery.
Place the supplied #4 screw into the mounting hole and secure the transmitter housing to the surface.
Reinsert the battery.
Snap the transmitter cover back onto the base.
Mount the Magnet
For magnet placement options, refer to Figure 5.
Standard Installation
Push the supplied magnet into the magnet cover.
Hold the magnet base on the door closest to the magnetic reed switch, no more than 1/2” (1.3 cm) from the transmitter.
Use the provided #4 screws to mount the base. See Figure 3.
Snap the cover onto the base.
Commercial Installation
Push the supplied magnet into the magnet cover.
Place and hold the magnet cover directly on the door closest to the magnetic reed switch, no more than 1/2” (1.3 cm) apart from the transmitter.
Use the provided #4 screws to mount the cover. See Figure 4.
PLACEMENT OPTIONS
WIRE EXTERNAL CONTACTS (OPTIONAL)
Refer to Zone Information in the appropriate panel programming guide for more information. DMP recommends using 18 or 22 AWG unshielded wire for contact connections. Do not use twisted pair or shielded wire. Refer to Figure 6 when wiring external contacts.
Use a flathead screwdriver to loosen the two external contact terminal screws.
Insert external contact wiring into the 1101 terminal block and tighten the screws.
Connect the other ends of the wires to the external contact as either normally open (N/O) or normally closed (N/C) without an end‑of‑line resistor.
Snap the transmitter cover back onto the base.
EXTERNAL CONTACTS
TEST THE TRANSMITTER
After the transmitter has been installed, test to confirm that it is communicating reliably with the panel. Use the Tech APP™ to perform a Wireless Walk Test on the system or complete the following steps to perform a Walk Test from a keypad that is connected to the panel:At the keypad, enter 8144 (WALK) and select WLS. If the transmitter fails to check in at the keypad, ensure that it is wired properly and check for sources of interference such as metal objects and electronic equipment.
ADDITIONAL INFORMATION
Supervision TimeWhen a receiver is installed, powered up, or the panel is reset, the supervision time for transmitters is reset. If the receiver has been powered down for more than one hour, wireless transmitters may take up to an additional hour to send a supervision message unless tripped, tampered, or powered up. This operation extends battery life for transmitters. A missing message may display on the keypad until the transmitter sends a supervision message.
Replace the Battery
Push the button on the end of the transmitter and separate the two halves.
Remove the old battery, observe polarity, and place the new battery in the holder.
Snap the cover back on the transmitter.
Sensor Reset to Clear LOBATOnce the battery is replaced, a sensor reset is required at the keypad to clear the LOBAT message. On an LCD keypad, press and hold 2 for two seconds. On a graphic touchscreen keypad, press RESET. Enter your user code, if required. The keypad displays SENSORS OFF followed by SENSORS ON.
FCC INFORMATION
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference, and
this device must accept any interference received, including interference that may cause undesired operation.
The antenna used for this transmitter must be installed to provide a separation distance of at least 20 cm (7.874 in.) from all persons. It must not be located or operated in conjunction with any other antenna or transmitter.Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA INFORMATION
This device complies with Industry Canada Licence‑exempt RSS standards. Operation is subject to the following two conditions:
This device may not cause interference, and
this device must accept any interference, including interference that may cause undesired operation of the device.
This system has been evaluated for RF Exposure per RSS‑102 and is in compliance with the limits specified by Health Canada Safety Code 6. The system must be installed at a minimum separation distance from the antenna to a general bystander of 7.87 inches (20 cm) to maintain compliance with the General Population limits.
Specifications
Battery
Life Expectancy: 5 Years (normal operation)Type: 3.0 V lithium CR123A FrequencyRange: 905-924 MHz
Dimensions
Transmitter Case: 3.3” L x 1.6” W x 0.9” HTransmitter Base: 3.3” L x 1.6” W x 0.1” HMagnet Housing: 1.5” L x 0.5” W x 0.7” HMagnet Spacer: 1.5” L x 0.5” W x 0.1” HHousing Material: Flame-retardant ABS
Designed, engineered, and manufactured in Springfield, MO using U.S. and global components.LT-0694 1.04 201642500 North Partnership BoulevardSpringfield, Missouri 65803-8877800.641.4282 | DMP.com