EMERSON CC200 Controller Hardware and Wiring User Guide

EMERSON CC200 Controller Hardware and Wiring

Functions of the CC200

  • Low, medium, and dual temperature case types supported.
  • Stepper Valve Driver Onboard.
  • EEPR control based on pressure or temperature.
    • New patent pending floating evaporator SST setpoint management automatically adjusts evaporator SST to the optimum setpoint for discharge air.
  • Case Display with touchscreen.
  • Form C relays allow direct control of case loads and simplified wiring.
  • Simplified wiring and connections reduce labor and setup time.
  • Bluetooth® connectivity for easy controller status and service.
CC200 Main Controller Specifications
Name Description
Power Requirement 24VDC 71(Earth) – 72(+) – 73(-)
Mounting DIN Rail
Dimensions 7 3/16″x 4 5/16″x 3″ (W x H x D)
 

 

 

Serial Port

Master/slave, 1/8 load, up to 115.2K Baud, isolated; generic 150-ohm termination with switch. 3-Terminal connector with onboard 100-ohm between RS485 “C” Terminal and RS485 isolated ground to allow direct earth ground connection. The RS485 Port B Gnd is isolated from RS485 Port A Gnd and all other circuit and earth grounds.
ETH1 ETH2 BACnet TCP/IP repeater (Ethernet 10/100) BACnet TCP/IP repeater (Ethernet 10/100)
Operating Temperature 14°F to 122°F (-10°C to 50°C)
Relative Humidity 20-85% RH; non-condensing
Power Supply Wiring and Specifications
Power Supply Specifications
Primary Power 120VAC
Secondary Power 24VDC
CC200 Power Requirement 24VDC 60W
Required Power Supply CC200 Power Supply

24VDC 60W Emerson P/N 810-3182

Power Supply Terminals 2 (-V) & 3 (+V)
CC200 Power Terminals 72(+) –73(-) — 71(Earth)
Wire Spec 16AWG
24VDC Max Wire Length 20”
Mounting DIN Rail Mounted
Power Supply Dimensions 2.06” x 3.54” x 2.14” (W x H x D)

Step 1: Mount Power Supply and CC200 Main Controller to DIN Rail.Step 2: Wire Secondary power from Power Supply to CC200 Main Controller.a. Reference specification and drawing for Terminals.b. This is Polarity Sensitive.Step 3: Wire Primary power to Power Supply.a. Reference the specification and drawing for Terminals.

CC200 Main Controller Output Wiring

Note: Fan motors over 5 amps must use the alternate wiring method with a pilot device between CC200 and the motor

Step 1: Verify power is OFF on the CC200 Main Controller.Step 2: Refer to the specification drawing below for the correct termination terminals and how to wire:

For Fan Motors Over 5A

CC200 Main Controller Output Specifications

Relay Specifications
 

CC200 Label

 

AMP/VAC

LOADS CONTROLLED  

TERMINALS

 

 

 

 

Fan/CT

Form C Relay with built in CT:

NO: Resistive 5A, 240Vac or less;

5FLA, 30LRA, 240Vac

or less;

Pilot Duty B300 NC: Resistive 5A, 240Vac or less;

5FLA, 30LRA, 240Vac

or less;

Pilot Duty C300

 

 

 

 

Evap Fans

 

 

 

 

4(C) – 5(NO) – 6 (NC)

Defrost Form C Relay

NO: Resistive 12A, 240Vac or less;

10FLA, 60LRA, 240Vac

or less;

Pilot Duty B300 NC: Resistive 12A, 240Vac or less;

5FLA, 30LRA, 240Vac

or less;

Pilot Duty C300

Defrost Heaters 7(C) – 8(NO) – 9(NC)
Light Case Lights 10(C) – 11(NO) – 12(NC)
Refrig LLSV 13(C) – 14(NO) – 15(NC)
 

 

AUX Relay

Alarm Out, Door Alarm, Satellite for E2E control, backup for other RO  

 

16(C) – 17(NO) – 18(NC)

 

 

AO1 (AO)

 

 

4-20mA or 0-10VDC

Satellite for E2E control, future Light Dimming, future Antisweat  

 

39(+) – 40(-)

AO2 (AO) 4-20mA or 0-10VDC Future Light Dimming 41(+) – 42(-)

CC200 Main Controller Input Specifications

Input Specifications
CC200 Label Description TERMINALS & COLOR
DAT Discharge Air 46 – 47 Green
TERM Defrost Termination 48 – 49 Orange
RAT Return Air 50 – 51 Purple
COIL OUT Coil Out 52 – 53
 

PRESSURE

100lb Pressure Transducer

Polarity sensitive

43(0v) – 44(Sig) –

45(+5V)

Black – White – Red

Def CT Amps Defrost Amps (electric defrost only) 54(+) – 55(-)
Aux Inputs AI & DI
AI1 AI2 Configurable functions: External fan CT, Coil Inlet Temp, Product Temp, Circuit Suction Temp 56(+) – 57(-)

58(+) – 59(-)

DI1 DI2 DI3 DI4 Door switch, service switch, dual temp switch, defrost term switch, leak shutdown, satellite 1 for E2E, satellite 2 for E2E 31(DI1) – 32(C)

33(DI2) – 34(C)

35(DI3) – 36(C)

37(DI4) – 38(C)

Wire Specifications for extending Input and Valves
 

Analog Temp Sensors or Digital Inputs

General Cable 92454A #22/2 Shielded

Emerson P/N 1350600

If manufacturer harness must be extended, join wires with heat shrink and solder.

 

Pressure Transducer

Belden 28326AS #18/4 Shielded

Emerson P/N 1352832

If manufacturer harness must be extended, join wires with heat shrink and solder.

CC200 Input Wiring

Step 1: Make sure the power is OFF to the CC200 Main Controller.Step 2: Determine what sensors will be needed and wire per the specification above.

a. If sensor need to be extended Emerson only supports heat shrink and solder.

Step 3: Determine how many coils are on the cases.a. For multi-coil cases the CC200 supports one sensor per coil for discharge air, return air, defrost termination and coil outlet. Pressure transducers for multi-coil cases may be installed one per coil or one for the entire case (parameter selectable).b. For multi-coil cases the sensors on coil #1 will terminate on the CC200 Main Controller. Second and third sensor coils will require an Expansion Module per coil and each coil’s sensor will terminate on the each of the Expansion Modules.

CC200 Stepper Valve Wiring and Specifications

Stepper Valve (Sporlan CDS Only)
 

 

Stepper Valve

 

 

Bipolar

W2
76(White) – 77(Black)
W1
78(Red) – 79(Green)
 

 

Stepper Valve – Expansion Module

 

 

Bipolar

W2
33 (White) – 34 (Black)
W1
35 (Red) – 36 (Green)

Step 1: Make sure the power is OFF to the CC200 Main Controller.Step 2: The CC200 Case control system (Main Controller + Expansion Modules) supports Electronic Expansion Valve (EEV) control using either Pulse Width Modulation (PWM) valves OR Stepper valves but NOT both.The first case in a CC200 lineup (“a” Case) has support for control of Electronic Evaporator Pressure Regulation (EEPR) stepper valve.

  • PWM EEV 1 or Stepper EEV 1 is always located on CC200 Main Controller
  • PWM EEV 2 or Stepper EEV 2 is always located on Expansion Module 1
  • PWM EEV 3 or Stepper EEV 3 is always located on Expansion Module 2EEPR Location
  • When PWM EEV is used, EEPR is always located on CC200 MainController Stepper terminals
  • When Stepper EEV is used, EEPR is located on the last Expansion

Module Stepper terminals

a. The wiring specification above is only for the Sporlan CDS and SER valves.b. If other manufacturer valves are used, refer to the manufacturer’s specification and contact Emerson for instructions on how to terminate.

Step 3: Refer to the drawing and specification for termination of the valve:

CC200 Expansion Module Wiring and Specifications

CC200Label Description TERMINALS & COLOR
DAT Discharge Air 16 – 17 Green
TERM Defrost Termination 18 – 19 Orange
RAT Return Air 20 – 21 Purple
COIL OUT Coil Out 22 –23
 

PRESSURE

100lb Pressure Transducer Polarity sensitive 12(0v) – 13(Sig) – 14(+5V)

Black – White – Red

Wire Specs for Extending Inputs and Valves
Analog Temp Sensors or Digital Inputs Heat Shrink and Solder

General Cable 92454A #22/2 Shielded.

Emerson P/N 1350600

 

Pressure Transducer

Heat Shrink and Solder Belden 28326AS #18/4 Shielded.

Emerson P/N 1352832

 

 

Stepper Valve

Heat Shrink and Solder

Use the manufacturer harness with a max length not to exceed 30ft (9 meters).

Belden 28326AS #18/4

Emerson P/N 1352832

Step 1: Determine if you need an Expansion Module.a. You will add an Expansion for a second or third coil. Each coil will have temp sensors and a transducer and will be wired to the respective Expansion Module.Step 2: Addressing the Expansion Modulea. Set the address of each Expansion Module using the ON/OFF dip switch bank on the top left corner of the hardware (refer to figure below).b. Expansion Module one must be set to address 1, Expansion Module two to address 2, Expansion Module three to address 3.Step 3: Install the Expansion Module.a. Make sure power is OFF to the CC200 Main Controller. Power will be restored in a later step.b. Install Expansion Module 1 on the DIN rail adjacent to the CC200’s right side. The CC200 Expansion port terminal V+ should be aligned with Expansion Module 1 Expansion port terminal V+. Slide the Expansion Module into the CC200Expansion port so both device’s Expansion port connectors fasten together.c. If Expansion Modules 2 and 3 are present, connect to Expansion Module 1’s Expansion port using in the same manner described in the above step. No wiring is needed between the CC200 Main Controller and CC200 ExpansionModule. Power and communication are sourced from the CC200 Expansion port and passed through each Expansion Module Expansion port.Step 4: Terminate sensors on the Expansion Module and refer to the drawing and specifications above for terminal numbers and how to terminate. Once all sensor terminations are complete and the Expansion Module Expansion port is securely plugged into the CC200 Expansion port, restore the 24VDC supply power to the CC200 Main Controller. Once connected, the Expansion Module PWR ON LED will illuminate green indicating supply power is present.

CC200 Case Display

CC200 Display Specifications
Power Requirement Powered from the CC200 Case Controller
Required Wire Belden #8771 3C22AWG or Belden #8772 3C22AWG
Mounting Use the white sliding clips that are provided with the CC200 Display
Operating Temp UL: 32°F to 131°F / UL: 0°C to 55°C
Relative Humidity 20 to 85 RH% (non-condensing humidity)
Protection Body: IP20; Front: IP66
Points CC200 Terminals to CC200 Display Terminals
27(-) to 5(-)
+ 28(+) to 4(+)
VNR 29(VNR) to 3(VNR)

Step 1: Make sure power to the CC200 Main Controller is turned OFF.Step 2: Make termination from the CC200 Main Controller to the CC200 Display.a. It is critical that these terminations are made correctly as this can result in damage to both devices if not terminated correctly.b. Clip and insulate shield at both ends of the Belden connection cable. Keep cable length at less than 50 ft (15 meters).Step 3: Power ON the CC200 Main Controller.

Part Numbers for Ordering

*Emerson Part Number Description
810-3180 CC200 Main Controller
810-3181 CC200 Expansion Module
810-3182 CC200 Power Supply 24VDC 60W

Emerson P/N 8103182

810-3183 CC200 Case Display
501-1122 Discharge Air Temperature Sensor
501-1127 Defrost Termination Temperature Sensor
501-1128 Return Air Temperature Sensor
501-1125 (blue)

501-1126 (red)

Coil Out Temperature Sensor
800-2100 100lb Pressure Transducer

*For optimal performance of the CC200, Emerson parts are required.

Cold Chain Connect is the CC200 mobile application for setting parameters, graphing inputs and outputs, setting service overrides, and viewing alarms. Cold Chain Connect provides a window into CC200 operation and diagnostics directly at the location of the refrigerated fixture or walk-in box. Download Cold Chain Connect from the App Store at Apple: https://www.apple.com/ios/app-store

report this ad

This document may be photocopied for personal use. Visit our website at http://www.climate.emerson.com for the latest technical documentation and updates.Join Emerson Technical Support on Facebook http://on.fb.me/WUQRntFor Technical Support call 479-845-3430 or email ColdChain.[email protected]The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenanceof any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. Emerson is a trademark of Emerson Electric Co. ©2020 Emerson Retail Solutions, Inc. All rights reserved.

References

[xyz-ips snippet=”download-snippet”]


Posted

in

by