EMERSON Pressure Controls Series PS4 Instruction Manual
General information:
For application in refrigeration systems and heat pumps according to EN 378. A professional and appropriate storage and allocation of the devices is mandatory.
Safety instructions:
- Read operating instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.
- According to EN 13313 this product is intended for use by personnel having the appropriate knowledge and skill.
- Ensure that the system is correctly labeled with applied refrigerant type and a warning for explosion risk, when used with flammable refrigerants.
- Before opening any system make sure pressure in system is brought to and remains at atmospheric pressure.
- Do not release any refrigerant into the atmosphere!
- Do not exceed the specified maximum ratings for pressure, temperature, voltage and current.
- Before installation or service disconnect all voltages from system and device.
- Observe and avoid mechanical damage of housing in order to maintain protection class.
- Do not use any other fluid without prior approval of EMERSON. Use of fluids not listed could result in: Change of hazard category of product and consequently change of conformity assessment requirement for product in accordance with European pressure equipment directive 2014/68/EU.
- Ensure that design, installation and operation are according to European and national standards/regulations.
Setting:
PS4 Pressure switches are factory preset to a specific value (see label).Function / Type of switch : (Fig. 1,2)Fig.1: Pressostat automatic reset (NC/NO):
Installation:
PS4 Pressure switches should not be exposed to pulsations. Use a pulsation damper or a capillary tube connection (min.1m) when pulsations can be expected.
Mounting location: anyPressure connection:
Threaded connection:
- Use pulsation damper and high temperature diaphragm for direct compressor mounted high pressure applications.
- Do not apply torsional force to switch housing assembly during assembly.
(1) = Copper gasket
Brazing:
- Perform the brazing as per EN 14324.
- Before and after brazing clean tubing and brazing joints.
- Do not exceed the max. body temperature of 70°C!
Pressure Test:After completion of installation, a pressure test must be carried out as follows:– according to EN 378 for systems which must comply with European pressure equipment directive 2014/68/EU.– to maximum working pressure of system for other applications.
- Failure to do so could result in loss of refrigerant and personal injury.
- The pressure test must be conducted by skilled personnel with due respect regarding the danger related to pressure.
Tightness Test:Conduct a tightness test according to EN 378-2 with appropriate equipment and method to identify leakages of external joints. The allowable leakage rate must be according system manufacturer’s specification.
Electrical connection:
- Comply with local electrical regulations when wiring PS4. To maintain protection class, proper installation is mandatory.
- Ensure that the cables are mounted without tension; always leave the cable a bit loose.
- Ensure that cables are not mounted near sharp edges.
Operation:
- Perform a functional test of electrical circuit before charging the system with refrigerant.
Service / Maintenance:
- Disconnect electrical power before service.
- Defective PS4-… must be replaced; they cannot be repaired.
- In case of repair work or replacing the control always use new gasket Fig 3 (1).
Technical Data:
Type code: PS4 – e.g. PS4 A 1
(1) Function
- A Pressure controls, automatic, high pressure or low pressure
- W Pressure limiters, automatic, type approval acc. EN 12263, (Definition term by EN12263 & EN378: PSL/PSH)
- R Pressure controls, external manual reset (by hand)
- B Pressure limiters, external manual reset (by hand); type approval, acc. EN 12263, (Definition term by EN12263 & EN378: PZH)
(2) Electrical connection
- Normally closed silver contact with molded cable
- Normally open silver contact with molded cable
- Normally closed silver contact with quick connector; QC (for push-on spades)
- Normally open silver contact with quick connector, QC (for push-on spades)
- Normally closed gold-plated contact with molded cableL Normally closed silver contact with molded cable suitable for manual rest
Emerson Climate Technologies GmbH Am Borsigturm 31 I 13507 Berlin I Germany
Date: 18.05.2021
PS4_OI_EN_DE_FR_ES_IT_RU_0521_R05_865025.docx