Honeywell Home HZ432 True Zone Panel Installation Guide

Honeywell Home HZ432 True Zone Panel Installation Guide

SPECIFICATIONS

  • Input Ratings:Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more.
  • Current Draw:ZonePanel: 8.5 VA max.THM4000WirelessAdapter: 2 VA max.AllVA specifications at 24 VAC.
  • Wiring:18- or 20-gauge solid (not stranded) wire.
  • Humidity Ratings:5% to 90% RH non-condensing.
  • Temperature Ratings:Shipping: -20° to 150°F (-29° to 66°C)Operating: -40° to 165°F (-40° to 74°C)
  • Dimensions:See Fig. 1.
  • Emissions:Complies with FCC Class B, part 15 requirements.

Fig. 1. HZ432 TrueZONE panel dimensions in in. (mm).

Need Help?For assistance with this product please visit customer.resideo.com or call Zoning Hotline toll-free at 1-800-828-8367

Read and save these instructions.

APPLICATION

The HZ432 TrueZONE® panel controls:

  • Single-stage, multi-stage, conventional, or heat pump heat/cool HVAC equipment up to 3 stages of heat and 2 stages of cool;
  • Dual-fuel systems with up to 2 heat pump stages and 2 fossil fuel stages;
  • 2, 3, or 4 zones and is expandable to 32 zones using wired thermostats with the TotalZone® Add-A-Zone™ panel;
  • 2, 3, or 4 zones with wireless thermostats when used with the wireless adaptor.

Please refer to TrueZONE Panel Frequently Asked Questions form 50-9694 for operating details, or see customer.resideo.com

ACCESSORIES

Table 1. Recommended Thermostats.

System Thermostat
Single stage TH1110D2009 (non-programmable) TH4110U2005 (Programmable)
Multistage conventional TH6220U2000 (Programmable) TH6220WF2006 (Programmable, Wi-Fi)
Heat pump TH4210U2002 (2H/1C, Programmable) TH6210U2001 (2H/1C, Programmable) TH6220U2000 (2H/1C, Programmable) TH6220WF2006 (2H/1C, Programmable, Wi-Fi) TH6320WF2003 (3H/2C, Programmable, Wi-Fi)
All the above TH6320WF2003 (Programmable, Wi-Fi) TH8321WF1001 (Programmable, Wi-Fi) THX321WFS2001W (Programmable, Wi-Fi)
Wireless * TH5320R1002 TH6320R1004 TH8320R1003
  • For RedLINK™ wireless devices, a THM4000 is required. For more than 4 zones, see page 11.

Table 2. Recommended Dampers

Type Actuation Round Rectangular

Residential

Zone Spring-open/ power-closed ARD (6 VA) ZD (6 VA)
Zone Power-open/ power-closed RRD (2 VA)
Bypass Barometric Constant pressure regulating damper (CPRD)

Commercial

Zone Power-open/ power-closed Modulating Automatic Round Damper (MARD) (2 VA)
Bypass Power-open/ power-closed ModulatingAutomatic Round Damper (MARD) (2 VA) with SPC
  • Or equivalent damper and actuator.

Table 3. Maximum Dampers.*

Ambient Temp. Maximum Damper VA per Zone
100°F (38°C) 28.8
160°F (71°C) 16.8
  • Use an SDCR (Slave Damper Control Relay) for additional dampers tosurpass  the maximum damper VA per zone.Maximum dampers per panel is limited by transformer size.Ensure transformer is large enough to power the panel, thermostats, wireless adapter module, and dampers.

Table 4. Accessories.

Accessory Description
40 VA transformer* AT140A1042
75 VA transformer AT175A1008
Discharge Air Temperature Sensor (DATS)* C7735A1000
TAZ-4 TotalZone® Add-A-ZoneTM  Control Panel
SDCR** Slave Damper Control Relay
Portable Comfort Control*** REM5000R1001
Wireless Adapter*** THM4000R1000
Wired Outdoor Air Temperature Sensor C7089U1006 (hard wired)
Wireless Outdoor Air Temperature Sensor*** C7089R1013 (wireless)
RedLINK Internet Gateway*** THM6000R7001**
  • Included in HZ432K kit.
  • Use an SDCR (Slave Damper Control Relay) to add additional dampers to a zone to surpass the maximum Damper VA rating per Zone.
  • For RedLINK™ wireless devices, a THM4000 is required. ‡ A wired or wireless outdoor sensor is required for Dual Fuel applications.

MOUNTING

  1. Mount the HZ432 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or coldair return.NOTE: The HZ432 TrueZONE panel can be mounted in any orientation; level it for appearance only.
  2. Separate the zone panel cover from the base, and use the base as a template to drill mounting holes. Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).

WIRING

CAUTION: Voltage Hazard.Can cause electrical shock or equipment damage. Disconnect power before beginning installation.Wire entire panel before applying transformer power.

Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional systems, see page 5. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9.

Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring diagrams to wire the zone panel to the thermostats and dampers.

  1. Install thermostats using instructions provided with thermostats.If using wired thermostats, connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To release wire, press the button on top of the terminal.
  2. Install dampers using instructions provided with dampers.Connect dampers to zone panel.NOTE: Multiple dampers can be wired in parallel.
  3. Connect DATS as shown. See high and low limit settings in Table 5 “Advanced Configuration”
  4. Connect outdoor air temperature sensor as shown.Required for dual fuel systems; optional for other multistage systems. If using the C7089R1013 wireless outdoor sensor and THM4000R wireless adapter on 2- to 4-zone systems,
  5. Connect equipment as shown here.
  6. When a wireless thermostat, Portable Comfort Control, wireless outdoor air temperature sensor, or other RedLINK™ wireless device is used on systems up to four zones, wire the THM4000 Wireless Adapter Module to the ABCD terminals on the zone panel.For systems with more than 4 zones,CAUTION: Do not wire the A-B-C-D terminals of the THM5320R or THM5421R Wireless Equipment Interface Module to the A-B-C-D terminals on the HZ432 zone control panel. Doing so will damage the components
  7. Connect a dedicated transformer as shown

CONVENTIONAL

The following diagram is an overall view of wiring for a conventional system as depicted in steps 3–9.

Fig. 12. Zone panel wiring—conventional.

FOR OIL HEAT WITH A SEPARATE TRANSFORMER FOR COOLING, REMOVE JUMPER.

ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R OR THM5421R WIRELESS EIM TO THESE TERMINALS.

HEAT PUMP

Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat.

NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by heat pump thermostats or by pressing the Emergency Heat button on the zone panel. The diagram below shows a heat pump thermostat used with a heat pump system.

Fig. 13. Zone panel wiring—heat pump, 2-heat/1-cool with electric auxiliary heat.

JUMP W1/E TO W2 AT THE THERMOSTAT CONNECTIONS ON ALL ZONES OF THE ZONE PANEL.

FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR COOL CHANGEOVER VALVES OR ATTACH B FOR HEAT CHANGEOVER VALVES.

IF EQUIPMENT DOES NOT HAVE SEPARATE E AND AUXILIARY TERMINALS, JUMPER E TO W2 ON PANEL AND WIRE TO E.

ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R WIRELESS EIM TO THESE TERMINALS

Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat.

Fig. 14. Zone panel wiring—heat pump, 3-heat/2-cool with electric stage 3 heat.

UMP W1/E TO W3 AT THE THERMOSTAT CONNECTIONS ON ALL ZONES OF THE ZONE PANEL.

FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR COOL CHANGEOVER VALVES OR ATTACH B FOR HEAT CHANGEOVER VALVES.

IF EQUIPMENT DOES NOT HAVE SEPARATE E AND AUXILIARY TERMINALS, JUMPER E TO W3 ON PANEL AND WIRE TO E.

ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R WIRELESS EIM TO THESE TERMINALS.

DUAL FUEL

Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump.

Fig. 15. Zone panel wiring—dual fuel: single-stage furnace and single-stage heat pump.

FOR OIL HEAT WITH A SEPARATE TRANSFORMER FOR COOLING, REMOVE JUMPER.

vABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R OR THM5421R WIRELESS EIM TO THESE TERMINALS.

Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump.

Fig. 16. Zone panel wiring—dual fuel: two-stage furnace and two-stage heat pump.

ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R WIRELESS EIM TO THESE TERMINALS

CONFIGURATION

To enter Configuration:

  1. Press the Mode button (the Config LED will light up)
  2. Use the Back and Next buttons to navigate through the configuration settings. Scroll through the selection choices by using the “Adjust Setting” Left and Right arrow buttons. Pressing Next enters the selected option for that  menu item and advances to the next menu.
  3. The flow chart below illustrates basic zone panel configuration. For additional configuration, see Advanced Configuration. The label on the inside cover of the HZ432 Zone Panel also contains configuration information.

C7089U1006 WIRED OUTDOOR SENSOR, OR C7089R1013 WIRELESS OUTDOOR SENSOR AND THM4000R1000 WIRELESS ADAPTOR REQUIRED IF DUAL FUEL OPERATION IS SET TO YES.

SET TO “YES” IF WIRELESS (RADIO FREQUENCY) THERMOSTATS AND THM4000R ADAPTOR ARE USED. SET TO “NO” IF THE THM5320R IS USED AS DESCRIBED.

CANNOT USE TAZ-4 ADD-A-ZONE WITH THE HZ432 IF RF ENABLED IS SET TO “YES”. SYSTEM IS LIMITED TO 4 ZONES WHEN THM4000WIRELESS ADAPTER IS USED.

vSHOWN IF COMPRESSR STAGES, HEAT STAGES, OR DFUEL HT STAGES IS SET TO 2, OR AUX HT ENABLED IS SET TO “YES”

SHOWN ON NON DUAL FUEL HEAT-PUMPS IF COMPRESSR STAGES IS SET TO 2 AND AUX HT ENABLED IS SET TO “YES”, OR ON CONVENTIONAL APPLICATIONS IF HEAT STAGES IS SET TO 3.

CONNECT WIRELESS DEVICES

If connecting wireless devices, press the Mode button until the Wireless LED lights up. The TrueZONE must be configured for wireless devices to select Wireless mode.

  • Press Next to add devices.
  • While the display alternates the Press Connect and
  • Exit screens, push the Connect button(s) on the wireless device(s).
  • -ORFollow the instructions that came with the wireless device(s).
  • Press Next to exit.

If using more than 4 zones, use the TAZ-4 Add-A-ZoneTM Control Panel. Follow instructions with the TAZ-4 for installation (form 69-1366).If using a THM4000R wireless adaptor, a maximum of 4 zones may be used. For applications using wireless thermostats and requiring more than 4 zones, do not use a THM4000R. Instead, wire a separate EIM (EquipmentInterface Module) to the thermostat terminals of each zone on the zone panel. Then link each wireless thermostat to the corresponding EIM. Configure the HZ432 for RF Enabled = NO. The EIM used with RedLINK VisionPRO and Prestige models is THM5421R1021. The EIM used with RedLINK FocusPRO models is THM5320R1000.

CAUTION

  • Do not wire the A-B-C-D terminals of the THM5320R to the A-B-C-D terminals of the HZ432 zone control panel.
  • Doing so will damage the components.

ADVANCED CONFIGURATION

Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 10 for instructions on using these buttons. Options/information displayed will vary by system type, control type, number of zones, and other settings.

Table 5. Advanced Configuration

Menu Name Menu Title (LCD top line) Menu Options (LCD bottom line; defaults in bold) Menu option description Notes:
Heat Fan HEAT FAN CONTROL [HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or turned

on by panel in call for heat.

HVAC [PANEL] Fan control by Panel
Stage 2 Timer STAGE 2 TIMER [5 MIN] > – <  [60 MIN] [5 MIN] > 5 minutes–60 minutes Number of minutes to delay before engaging second stage.
Stage 3 Timer STAGE 3 TIMER [5 MIN] > – <  [60 MIN] [5 MIN] > 5 minutes–60 minutes Number of minutes to delay before engaging third stage.
Purge Timer PURGE TIME [2] 3.5 5 MIN 2.0 minutes Number of minutes panel will purge following call for heat or cool.
2 [3.5] 5 MIN 3.5 minutes
2 3.5 [5] MIN 5.0 minutes
Purge Fan FAN IN PURGE [HVAC] PANEL Fan control by HVAC Fan controlled by HVAC or panel during purge.
HVAC [PANEL] Fan control by Panel
Purge Dampers PURGE DAMPERS [UNCHANGD] OPEN Dampers Unchanged Damper position unchanged or all dampers open during purge.
UNCHANGD [OPEN] Dampers All Open
Auto Changeover Delay CHANGEOVER DELAY [15] 20 30 MIN 15 minutes auto changeover timer Number of minutes to delay auto changeover when one zone is calling for heat and another is calling for cooling.
15 [20] 30 MIN 20 minutes auto changeover timer
15 20 [30] MIN 30 minutes auto changeover timer
DATS Enabled DISCHARGE SENSOR [NO] YES Disabled Enables or disables DATS. If Disabled, the Multistage DATS Inhibit setting is Disabled.
NO [YES] Enabled
DATS High Limit DAT HIGH LIMIT [110 F]   > – <  [180 F] <  [160 F]  > 110 deg F–180 deg F For furnace systems, high limit should be set approximately 15 degrees below the furnace high limit setting.
DATS Low Limit DAT LOW LIMIT [30 F]   > – <   [60 F] <  [40 F]   > 30 deg F–60 deg F Low temperature limit.
Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES] Enabled Allow panel to downstage multistage equip- ment when near DATS high or low limit.
[NO] YES Disabled
Dual Fuel Changeover DUALFUEL CHGOVR [OT] MULTISTG Dual Fuel Changeover by OT Temp Allow panel to changeover from heat pump to fossil fuel based on outdoor temperature, or allow second stage call to changeover panel to fossil fuel for a minimum of one hour when

outdoor temperature is above OT balance tem- perature setting. Multistage changeover is only available on dual fuel applications configured for 2 heat pump stages.

OT [MULTISTG] Dual Fuel Changeover by OT Temp + multistage call
Dual Fuel Mstage Changeover Time CHANGEOVER DELAY [15 MIN]  > <  [180 MIN]

[30 MIN] >

Sets fossil fuel changeover delay time. Sets number of minutes to delay fossil fuel when calling for second stage heat.
OT Temp Enabled OT SENSOR [NO] YES Disabled Enables or disables outdoor temperature sensor. If Disabled, the Multistage OT Temp Lockout setting is Disabled.
NO [YES] Enabled
Multistage OT Temp Lockout MSTG OT LOCKOUT [NO] YES Disabled When outdoor temperature is above OT Lockout temperature, locks out second and third stage (only for conventional and heat pump configu- rations), not dual fuel configurations.
NO [YES] Enabled
OT Balance Temperature (Dual Fuel) OT BALANCE TEMP [0 F]   > – <   [50 F] <  [30 F]   > 0 deg F–50 deg F Selects the temperature at which a dual fuel configuration will change from heat pump to fossil fuel.
OT Trip point for multi- stage lockout OT LOCKOUT TEMP [0 F]   > – <   [50 F] <  [50 F]   > 0 deg F–50 deg F The temp that locks out second or third stage (only for conventional and heat pump configu- rations, not dual fuel systems).
LCD Contrast Adjust LCD CONTRAST [1]   > – <   [10] < [5]    > Contrast value 1–10 Sets LCD display contrast for ease of viewing. Lowest contrast is 1, highest contrast is 10.
Save Changes SAVE CHANGES? [NO] YES Disabled Saves or rejects the configuration settings.
NO [YES] Enabled

OPERATION

Much of this information, as well as configuration information, is listed on the label on the inside of the HZ432 cover. For users who prefer French or Spanish labels, they are provided in form 69-2198FS. Cut them out and attach them to the inside of the HZ432 cover.

Table 6. LED Operation.

LED Description
HEAT 1 Solid when in heat stage 1. Blinking when DATS high limit mode has been reached.
HEAT 2, 3 Solid when in heat stage 2, 3. Blinking when stage 2, 3 locked out due to DATS or OT.
COOL 1 Solid when in cool stage 1. Blinking when DATS low limit mode has been reached.
COOL 2 Solid when in cool stage 2. Blinking when stage 2 locked out due to DATS.
PURGE Solid when in purge (at power-up and after a call for heat or cool). Blinking when the DATS sen- sor has failed, or the wires are shorted or open. Will blink for 3 minutes at power-up if DATS is not present.
FAN Solid with a call for fan.
EM HEAT Solid when in emergency heat mode. This light does not indicate a call for heat. Emergency heat will only run when both HEAT and EM HEAT are lit.
ZONE 1, 2, 3, 4 Solid green when open or opening. Solid red when closed or closing. Blinking amber when the VA draw of the dampers exceeds the specified VA, or if there is a short circuit on the damper or thermostat wiring, causing that zone’s breaker to trip.

CHECKOUT

To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on page 10 for instructions on using these buttons.

Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation of the equipment and dampers. These steps energize the equipment and damper terminals.Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or cool and viewing the active wires as displayed on the LCD screen. This is a useful way to troubleshoot which thermostat terminals are actually energized on each zone.

Table 7. Checkout.

Checkout Step Line 1 display Line 2 Display Notes:
1. Display shows OT OT SENSOR VAL current OT temp (dynamic) All zone dampers open, all other relays OFF.
2. Display shows DATS DAT SENSOR VAL current DATS (dynamic)  
3. Heat stages test TEST HEAT [OFF] 1 2 3 Heat turns on (fan also turns on if configured for fan on in heat).
4. EM Heat stages test TEST EMERG HEAT [OFF] 1 2 Emergency heat turns on (fan also turns on).
5. Cool stages test TEST COOL [OFF] 1 2 Cooling turns on (fan also turns on).
6. Fan Test TEST FAN [OFF] ON Fan cycles on and off.
7. Damper 1 test TEST Z1 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
8. Damper 2 test TEST Z2 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
9. Damper 3 test TEST Z3 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
10. Damper 4 test TEST Z4 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
11. View Tstat1 inputs ZONE1 STAT INPTS Displays active Tstat1 terminals or displays wireless thermostat operation Tests thermostat connection with HVAC off.
12. View Tstat2 inputs ZONE2 STAT INPTS Displays active Tstat2 terminals or displays wireless thermostat operation Tests thermostat connection with HVAC off.
13. View Tstat3 inputs ZONE3 STAT INPTS Displays active Tstat3 terminals or displays wireless thermostat operation Tests thermostat connection with HVAC off.
14. View Tstat4 inputs ZONE4 STAT INPTS Displays active Tstat4 terminals or displays wireless thermostat operation Tests thermostat connection with HVAC off.
15. Exit checkout mode? EXIT CHECKOUT? (NEXT = EXIT)  

WARRANTY

Resideo warrants this product, excluding battery, to be free from defects in workmanship or materials, under normal use and service, for a period of five (5) years from the date of first purchase by the original purchaser. If at any time during the warranty period the product is determined to be defective due to workmanship or materials, Resideo shall repair or replace it (at Resideo’s option).

If the product is defective,

  1. return it, with a bill of sale or other dated proof of purchase, to the place from which you purchased it; or
  2. call Resideo Customer Care at 1-800-828-8367. Customer Care will make the determination whether the product should be returned to the following address:Resideo Return Goods, 1985 Douglas Dr. N., Golden Valley, MN 55422, or whether a replacement product can be sent to you.

This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Resideo that the defect was caused by damage which occurred while the product was in the possession of a consumer.

Resideo’s sole responsibility shall be to repair or replace the product within the terms stated above. RESIDEO SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY,EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT.

Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.

THIS WARRANTY IS THE ONLY EXPRESS WARRANTY RESIDEO MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE FIVE YEAR DURATION OF THIS WARRANTY. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

This warranty gives you specific legal rights, and you may have other rights which vary from state to state. If you have any questions concerning this warranty, please write Resideo Customer Care, 1985 Douglas Dr, Golden Valley, MN 55422 or call 1-800-828-8367.

Resideo Technologies, Inc.1985 Douglas Drive North, Golden Valley, MN 554221-800-633-399169-2198—09 M.S. Rev. 03-20 | Printed in United States

report this ad

http://www.resideo.com/

 

 

[xyz-ips snippet=”download-snippet”]


Posted

in

by