Honeywell Home V2605 Radiator Valves and Thermostats Mira-3 Installation Guide

Table of Contents

Radiator Valves and ThermostatsV2605Mira-3Presettable manual radiator valve

APPLICATIONMira-3 presettable manual valves are installed on the supply of radiators and heat exchangers in warm water heating systems. Control of the room temperature is done by manually opening or closing the valve.

FEATURES

  • Convertible to thermostatic control, also when installed and in operation
  • Presettable by stroke limitation
  • Robust, noise, and flow optimized valve housing
  • Maintenance-free spindle sealing
  • Valve housing with dimensions according to EN215, Appendix A, Series D
  •  Non-rising handwheel
  • Connection to all types of pipe DN10 – DN20

SPECIFICATIONS

Medium: Heating water, water quality to VDI2035
pH-value: 8 – 9.5
Max. operating temperature: 130°C (266°F)
Operating pressure: PN10
Max. differential pressure: 1 bar (14.5 psi)
kvs (cvs)-value: Angle DN10 Angle DN15 Angle DN20 Straight DNIO Straight DN15 Straight DN20 ‘ 1.50 (1.76) 1.95(2.28) 2.45 (2.87) 1.30 (1.52) 1.70 (1.99) 2.20 (2.57)
!Thermostat connection: M30 x 1.5

FUNCTIONThe orifice between the valve seat and valve cartridge increases when the valve is opened by turning the handwheel anticlockwise. More heating water can flow into the radiator or heat exchanger and the room temperature rises.The orifice between the valve seat and the valve cartridge decreases when the valve is closed by turning the handwheel clockwise and the supply of heating water into the radiator or heat exchanger is throttled. At the right limit stop, the valve is closed except for a possible leakage rate.

DESIGNThe manual radiator valve consists of:

  • Valve housing PN10, DN10, 15, or 20 with– internal thread connection to DIN2999 (ISO7) for threaded, copper or precision steel pipe on the inlet (compression ring fittings see ‘Accessories’)– external thread connection to DIN/ISO228 with union-nut and radiator tailpiece on the outlet– dimensions to EN215, Appendix A,, Series D
  • Presettable valve insert
  •  Handwheel

MATERIALS

  • Valve housing made of nickel-plated hot-forged brass
  • Valve insert made of brass with EPDM O-rings
  •  Handwheel made of white plastic
  • Threaded tailpiece and connection nut made of nickel-plated brass

PLEASE NOTE:

  • To avoid stone deposit and corrosion the composition of the medium should conform with VDI-Guideline 2035
  • Additives have to be suitable for EPDM sealings
  •  The system has to be flushed thoroughly before initial operation with all valves fully open
  • Any complaints or costs resulting from non-compliance with the above rules will not be accepted by Honeywell Home
  • Please contact us if you should have any special requirements or needs

DIMENSIONS AND ORDERING INFORMATION

Note:All dimensions in mm unless stated otherwise.

Tab. 1 Dimensions and OS-Nos (OS=Ordering System)

Body type DN Pipeconnection Cvs(Cvs)-value II. 12 131 14 OS-No.
Angle (Fig. 1) 15 Rp 3/8* 1.50 (1.76) 52 26 52 22 V2605E0010
20 Rp1/2″ 1.95 (2.28) 58 29 52 26 V2605E0015
25 Rp /4′ 2.45 (2.87) 66 34 52 29 V2605E0020
Straight (Fig. 2) 15 Rp 3/8; 1.30C1.52) 85 59 57 V2605D0010
20 Pp 1/2° 1.70 (1.99) 95 66 57 V2605D0015
25 Rp 3/4′ 2.20 (2.57) 106 74 57 V2605D0020

ACCESSORIES

Description Dimension Part No.
FIG3/8CS Compression fitting for COPPER and STEEL pipeConsisting of a compression nut and compression ring. For valves with internal thread.Note:Support inserts have to be used for copper or soft steel pipe with 1.0 mm wall thickness.Max. operating temperature 120 °C, max. operating pressure 10 bar.
3/8″, DN10 10 mm FIG3/8CS10
3 /8″, DN10 12 mm FIG3/8CS12
1 /2″, DN15 10 mm FIG1/2CS10
1 /2″, DN15 12 mm FIG1/2CS12
1 /2″, DN15 14 mm FIG1/2CS14
1 /2″, DN15 15 mm FIG1/2CS15
1 /2″, DN15 15 mm FIG1/2CS15-10
1 /2″, DN15 16 mm FIG1/2CS16
3 /4″, DN18 18 mm FIG3/4CS18
3 /4″, DN22 22 mm FIG3/4CS22
FIG3/8CSS Compression fitting for COPPER and STEEL pipe Consisting of compression nut and compression ring and support insert.For valves with internal thread.Note: Support inserts have to be used for copper or soft steel pipe with 1.0 mm wall thickness.Max. operating temperature 120 °C, max. operating pressure 10 bar.
3 /8″, DN10 12 mm FIG3/8CSS12
1 /2″, DN15 12 mm FIG1/2CSS12
1 /2″, DN15 14 mm FIG1/2CSS14
1 /2″, DN15 15 mm FIG1/2CSS15
1/2″, DN15 16 mm FIG1/2CSS16
1/2″, DN15 18 mm FIG1/2CSS18
3/4″, DN20 18 mm FIG3/4CSS18
FIG1/2M Compression fitting for MULTILAYER pipe. Consisting of a compression nut, compression ring, and support insert. For valves with internal thread.Note:Max. operating temperature 90°C, max. operating pressure 10 bar
1/2″, DN15 16 mm FIG1/2M16X2
VA6290 Reduction
1″ pipe >1/2″ valve VA6290A260
11/4″ pipe >1/2″ valve VA6290A280
1″ pipe >3/4″ valve VA6290A285
11/4″ pipe >3/4″ valve VA6290A305
VA5201Axxx Radiator tailpiece with thread up to collar
for valves DN10 (3/”) VA5201A010
for valves DN15 (1/2″) VA5201A015
for valves DN20 (/4″) VA5201A020
VA5204Bxxx Extended radiator tailpiece, nickel-plated, to be shortened as required
3/8″ x 70 mm (for DN10)thread approx. 50 mm VA5204B010
1/2″ x 76 mm  for DN15) thread approx. 65 mm VA5204B015
3/4″ x 70 mm (for DN20)thread approx. 60 mm VA5204B020
VA2202Axxx Pressure cap – for shutting off valves on radiator outlet
for valves DN10 (3/8″) VA5090A010
for valves DN15 (1/2″) VA5090A015
for valves DN20 (3/4″) VA5090A020
VA5090 Sealing ring for pressure cap
for valves DN10 (3 /8″) VA5090A010
for valves DN15 (1 /2″) VA5090A015
for valves DN20 (3/4″) VA5090A020
VA8200A Service tool to replace valve insert
for all sizes VA8200A001
VA8201M Presetting tool
or all Mira-3 VA8201M301

SERVICE PARTS

VS1200M Valve insert
for all Mira-3 VS1200M301
VS4200 Handwheel
for all Mira-3 VS4200MI03

FLOW DIAGRAM

PRESETTING VALUES

Presetting 1 2 3 4 5 6 7
kvs(cv)-values 0.034 (0.04) 0.085 (0.10) 0.17 (0.19) 0.32 (0.37) 0.49 (0.57) 0.70 (0.82) 0.86 (1.01)
Tolerance ± % 35 30 25 21 17 14 12
Approx. turns of handwheel 8-Mar 8-May 8-Jul 1 1/8 1 3/8 1 5/8 1 7/8

KVS (CV)-VALUES

Type Angle Straight
DN 10 15 20 10 15 20
kvs (cvs)-value 1.50 (1.76) 1.95 (2.28) 2.45 (2.87) 1.30 (1.52) 1.70 (1.99) 2.20 (2.57)

For more informationhomecomfort.resideo.com/europe

Ademco 1 GmbHHardhofweg 4074821 MOSBACHGERMANYPhone: +49 6261 810Fax: +49 6261 81309

Manufactured for and on behalf of thePittway Sàrl, La Pièce 4, 1180 Rolle, Switzerland by its Authorised Representative Ademco 1 GmbHEN0H-2118GE25 R0520Subject to change© 2020 Pittway Sàrl. All rights reserved.This document contains proprietary information ofPittway Sàrl and its affiliated companies and are protected by copyright and other international laws.Reproduction or improper use without the specific written authorization of Pittway Sàrl is strictly forbidden. The Honeywell Home trademark is used under license from Honeywell International Inc.

report this ad

Product Specification Sheet • EN0H-2118GE23 R0520 • Subject to change

References

[xyz-ips snippet=”download-snippet”]