Honeywell IO Remote Modules WEB-8000 Specifications
PRODUCT DEFINITION
IO Remote module is part of Honeywell’s portfolio of hardware, software and tools designed for remote monitoring and control applications that enables end-to-end automation and device-to-enterprise integration. IO R allows the WEB-8000 to interface directly with simple non-intelligent inputs and outputs remotely located up to 4,000 feet from the controller. The connection is established via an industry-standard RS 485 multi-drop communications bus. Multiple IO R devices can be utilized on a single controller, providing 250+ IO points on a single controller.
SPECIFICATIONS
WEBs-N4: Requires WEBs-N4.3 or laterWEBs-AX: Requires WEBs-AX 3.8u3 or later
IO-R-16
8 Universal inputs: Type 3 (10k) thermistors,0-100K ohm, 0-10VDC,0-20 mA with external resistor4 Relay outputs(Form A contacts, 24VAC @ .5 amp rated)4 Analog outputs (0-10VDC)Powered from IO-R-34Connected to WEB-8000 remotely over a shielded RS485 bus
IO-R-34
16 Universal inputs: Type 3 (10k) thermistors,0-100K ohm, 0-10VDC,0-20 mA with external resistor10 Relay outputs(Form A contacts, 24VAC @ .5 amp rated)8 Analog outputs (0-10VDC)Powered from a 24VAC/DC sourceCan power up to 4 IO-R-16 modulesConnected to WEB-8000 remotely over a shielded RS485 bus
EXPANDABILITY
MAXIMUM EXPANSION(8) IO-R-34s or (16) IO-R-16s
POWEROne IO-R-34 can power four IO-R-16 modules
COMMON CONFIGURATIONS
AGENCY CERTIFICATIONS
- UL 916
- C-UL
- CE EN 61326-1:2013
- RCM
- FCC part 15, class b
- RoHS2
- REACH
- WEEE
- China ROHS
- Open Energy Management Class 2
ENVIRONMENTAL SPECIFICATIONS
Operating temperature: -20 to 60 °CStorage temperature: -40 to 85 °CHumidity: 5–95% — Non condensingShipping & vibration: ASTM D4169, Assurance Level IIMTTF: 10 years+
MOUNTING & DIMENSIONS
The WEB-8000 IO modules support mounting on EN50022 standard 7.5mm x 35mm DIN rail or panel mounting.IO-R-1682.5mm (w) x 116mm (h) x 61mm (d) (3.25 in x 4.5 in x 2.4 in)
IO-R-34162mm (w) x 116mm (h) x 61mm (d) (6.8 in x 4.5 in x 2.4 in)
ORDERING INFORMATION
Part number | Description |
IO-R-16 | 16 Point IO Module. Powered by IO-R-34. Connected to WEB-8000 remotely over RS485. |
IO-R-34 | 34 Point IO Module. Powered by 24VAC. Capable of powering 4 IO-R-16 modules. Connected to WEB-8000 remotely over RS485. |
NIAGARA FOR REMOTE MONITORING APPLICATIONS
Home and Building TechnologiesIn the U.S.:Honeywell715 Peachtree Street NEAtlanta, GA 30308customer.honeywell.com
[xyz-ips snippet=”download-snippet”]