Honeywell TF243 Series Digital Thermostat User Manual

Home

User ManualTF243 Series Digital Thermostat

Thermostat Appearance

Operating Your Thermostat

Power On/Off Time-off

  • Press to switch on/off thermostat. When in off mode, the OFF icon and indoor temperature will display.
  • Press could set the automatic turn-off time when the thermostat is working.
  • Press and hold for more than 3s. After the timer icon flashes, press or to set turn off time, then press the button to exit.

Operating Mode

Temperature Setting

In or  mode, press or set the target room temperature.LCD Display

Trouble Shooting Tips

If…

Then…

Doesn’t work Set the mode to (heating mode) by pressMake sure the temperature is set above the room temperatureWait 5 minutes for the system to respond
Doesn’t work Set the mode to (cooling mode) by pressMake sure the temperature is set below the room temperatureWait 5 minutes for the system to respond
 Doesn’t work Make sure the keypad is unlocked Check that the thermostat is on
Doesn’t work Make sure the keypad is unlockedMake sure the system isn’t in  modeCheck that the thermostat is on
The system turns off automatically Make sure the memorized time off value isn’t set to “0”
Time-off doesn’t work Make sure the button is unlocked Make sure the turn off time is not 0 Make sure the thermostat is not in ISU Make sure the thermostat is not off

Installation Guide

Must be installed by a trained and experienced installer

  • Read instructions carefully. Failure to follow instructions will damage the product or cause a hazardous condition.
  • Check the ratings in this booklet to verify that this product is suitable for your application.
  • Always test for proper operation after installation.

Caution: ELECTRICAL HAZARD can cause electrical shock or equipment damage.Disconnect power before installation, reparation, and detachment.The manual interpretation is owned by Resideo Technologies, Inc. and its affiliates, we retain the rights that improve the products described in this manual without prior notice.

Installation Tips

TF243 Series is designed for standard 75x75x50mm wall mounting box installation.Install the thermostat about 5 feet (1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install in locations where the thermostat can be affected by:

  • Dead spots behind doors and in corners
  • Hot or cold air from ducts
  • Sunlight or radiant heat from appliances
  • Concealed pipes or chimneys
  • The temperature of the mounting box and wall should be in the operating temperature range.

Wiring and Installation

The screw must be locked tightly to avoid wire break off from the terminal. The wire should not be tangled and stacked between the front case assembly and the back case.

Terminal Designations

Terminal

Description

R 24VAC operating voltage
C Common 24vac / Common for control output
RS Remote temperature sensor/ Hotel card
vO 0-10V Modulating signal output for valve
F3 High-speed fan output
F2 Medium speed fan output
F1 Low-speed fan output
L Live wire

* Input rating: 24VAC(+10% , -10%) 50/60Hz  220/230VAC(+10% , -10%) 50/60Hz* The vO terminal RL>600 ohms

Two pipe application

Wiring Diagram

Valve type: Honeywell / Resideo VC7931 Serials

Warning* The 24VAC power supply should meet Class2 SELV and less than 100VA* A FUSE or BREAKER is necessary before L terminal.

WEEE Directive 2012/19/EU Waste of Electrical and Electronic Equipment Directive Disposal Information Do not dispose this device and contained batteries with the general household waste. For proper treatment, recovery, and recycling, please take the device and contained batteries to designated collection points.  Disposing of this device and of contained batteries correctly will help save valuable resources and prevent any potential negative effects on human health and  the environment, which could otherwise arise from inappropriate waste handling.

Installation Setup

Enter or Exit Installation Setup Mode

ISU Code

Description

Possible Options

1 System Type 0 Heat only
1 Cool only
2 Two pipes heating/cooling (Default)
2 Remote Sensor 0 Temperature Sensor – Onboard Sensor (Default)RSB – Button (Default)
1 Temperature Sensor – Remote Sensor (RSB is set to Button as default)
2 RSB – Hotel Card NO (Temperature Sensor is set to Onboard Sensor as default)
3 RSB – Hotel Card NC (Temperature Sensor is set to Onboard Sensor as default)
3 Temperature Scale 0 ºF
1 ºC (Default)
4 Fan Control Type 0 Auto only Auto has fan ramping algorithm
1 Manual only (3 speed: Low->Med->High-> Low)
2 User can choose Auto or Manual (Default) (Low->Med->High->Auto-> Low)
ISU Code Description Possible Options
8 Display Temperature Adjustment -2 ºC- 2 ºC, step 0.5 ºC, Default 0 ºC

(-4 ºF- 4 ºF, step 1 ºF, Default 0 ºF )

9 Temperature Display Mode 0 Display room temperature (Default)
1 Display setpoint
10 Heating Range Stops 10-32 ºC Default 32 ºC

(50-90ºF Default 90 ºF)

11 Cooling Range Stops 10-32ºC Default 10 ºC

(50-90ºF Default 50 ºF)

12 Keypad Lockout 0 All keys are available (Default)
1 System button locked out
2 Fan and System buttons locked out
3 All buttons locked out except power button
4 All buttons are locked
14 Remote Setback Heating Setpoint Range 10-21ºC Default : 18 ºC(Range 50-70ºF Default : 64 ºF)
15 Remote Setback Cooling Setpoint Range 22-32ºC Default : 26 ºC

(Range 72-90 ºF Default : 79 ºF)

16 Freeze Protection 0 Disabled
1 Enabled (Default)
17 Power Recovery Status 0 OFF
1 Previous status (Default)
19 Fan Mode In ES Mode 0 Run as Auto fan speed when ISU_4=2 (Default)
1 Run as Low fan speed when ISU_4=2