Intesis Interface integration Haier air conditioners User Manual

Intesis Interface integration Haier air conditioners User ManualKNX TP1 (EIB)

ORDER CODE

LEGACY ORDER CODE

INKNXHAI008C000

HA-AC-KNX-8

INKNXHAI016C000

HA-AC-KNX-16
INKNXHAI064C000

HA-AC-KNX-64

Important User Information

Disclaimer

The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.

HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.

The data, examples and illustrations found in this document are included for illustrative purposes and are onlyintended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

1 Presentation

INKNXHAI0–C000allows a complete and natural integration of Haier air conditioners with KNX control systems.Compatible with all models of VRF line of Haier air conditioners.

Main features: 

  • Reduced dimensions. Installation even inside the A.C. indoor unit.
  • Quick and non-visible installation.
  • External power not required.
  • Direct connection to the KNX EIB bus.
  • Direct connection to the AC indoor unit.
  • Fully KNX interoperable, configuration from ETS.
  • Multiple objects for control (of different types: bit, byte, characters…).
  • Control of the AC unit based in the ambient temperature read by the own AC unit, or in the ambient temperature read by any KNX thermostat.
  • Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit’s state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
  • AC unit can be controlled simultaneously by the IR remote control of the AC unit and by KNX.

2 Connection

Connection of the interface to the AC indoor unit: 

Disconnect mains power from the AC unit. Open the front cover of the indoor unit in order to have access to the internal control board. In the control board locate the socket connector marked as ABG1.

Using a 3-wire cable, connect the ABG1 connector from the INKNXHAI0- C000to the A B G1 connector of the AC unit’s control board.

Fix the INKNXHAI0–C000inside or outside the AC indoor unit depending on your needs – remember that INKNXHAI0–C000must be also connected to the KNX bus. Close the AC indoor unit’s front cover again.

Connection of the interface to the KNX bus:

Disconnect power of the KNX bus. Connect the interface to the KNX TP-1 (EIB) bus using the KNX standard connector (red/grey) of the interface, respect polarity. Reconnect power of the KNX bus.

Connections diagram:

                               Figure 2.1 Default parameter configuration

Each Haier Communication Adaptor connects to a single Outdoor Unit.

The INKNXHAI008C000-16-64 can be connected to more than one Haier Communication Adaptor simultaneously.

NOTE: More than one Haier Communication Adaptor can be present in the installation.Please make sure that the address of the Haier Communication Adaptor is correctly set in the ETS. Check section 4.6 for more information.

3 Configuration and setup

This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.

ETS project for this device can be downloaded from: https://www.intesis.com/products/ac-interfaces/haier-gateways/haier-knx-vrf-ha-ac-knx

Please consult the README.txt file, located inside the downloaded zip file, to find instructions on how to install the database.

4 ETS Parameters

When imported to the ETS software for the first time, the gateway shows the following default parameter configuration:Figure 4.1 Default parameter configuration

With this configuration it’s possible to send On/Off (Control_ On/Off), change the AC Mode (Control_ Mode), the Fan Speed (Control_ Fan Speed) and also the Setpoint Temperature (Control_ Setpoint Temperature). The Status_ objects, for the mentioned Control_ objects, are also available to use if needed. Objects Status_ AC Ambient Reference Temperature and Status_ Error/Alarm are shown too.

                           Figure 4.2 Default communication objects

4.1 General configuration

Inside this parameter’s dialog it is possible to activate or change the parameters shown in the Figure 4.1.

4.1.1 Download latest database entry for this product and its User Manual from:The first field shows the URL where to download the database and the user manual for the product.                              Figure 4.3 Parameter detail

4.1.2 Intesis ProductThis parameter is used to check, before sending the programing, the maximum number of AC units your device supports.                              Figure 4.4 Parameter detail

Select the version of the gateway that you have:

  • INKNXHAI008C000, if you only want to control up to 8 AC unit.
  • INKNXHAI016C000, if you only want to control up to 16 AC units.
  • INKNXHAI064C000, if you only want to control up to 64 AC units.

4.1.3 Number of Indoor Units in ETSThis parameter is used to hide/show communication object according to the number of AC units you need to configure. Value ranges go from 1 to 64.                                   Figure 4.5 Parameter detail

In case you introduce a number higher than the maximum number of units allowed by your license, you will get a warning message. This is just for information and will not block the configuration process. Configurations with more indoor units configured than the ones allowed by the license will not be downloaded correctly.Figure 4.6 Parameter detail

4.1.4 First Status Updated to KNXThis parameter defines how fast the status is updated to KNX. Depending on the value selected, more or less priority will be assigned to this action. As there are so many parameters available, it is important to consider carefully how to set this parameter.

  • If set to “ASAP”, all status communication objects will send its value (if needed).
  • If set to “Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (ASAP).
  • If set to “Super Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (Slow).Figure 4.7 Parameter detail

4.1.5 Enable object “Error Code [2byte]”This parameter shows/hides the Status_ Error Code communication object which shows the indoor unit errors, if occurred, in numeric format.

Figure 4.8 Communication object and parameter detail

  • If set to “Disabled” the object will not be shown.
  • If set to “Enabled” the Status_ Error Code [2byte signed value] object will appear.
    • This object can be read and also sends the indoor unit error, if occurred, in numeric format. If a “0” value is shown that means no error.

4.1.6 Enable object “Error Text Code [14byte]”This parameter shows/hides the Status_ Error Text Code communication object which shows the indoor unit errors, if occurred, in text format.

Figure 4.9 Communication object and parameter detail

  • If set to “Disabled” the object will not be shown.
  • If set to “Enabled” the Status_ Error Text Code object will appear.
    • This object can be read and also sends the indoor unit error, if occurred, in text format. The errors shown have the same format as in the remote controller and in the error list from the indoor unit manufacturer. If the object’s value is empty, that means there is no error.

4.2 Global mode configuration 

Figure 4.10 Default Mode Configuration dialog

All the parameters in this section are related with the different mode properties and communication objects.

The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be enabled with a “0” value, Heat mode with a “1” value, Cool mode with a “3” value, Fan mode with a “9” value and Dry mode with a “14” value.

4.2.1 Enable use of “Operating Mode” objectsThis parameter shows/hides the Control_ and Status_ Mode Operating Mode communication objects.

4.2.2 Enable use of Mode Heat/Cool objects

This parameter shows/hides the Control_ and Status_ Mode Cool/Heat communication objects.

  • If set to “Disabled” the objects will not be shown.
  • If set to “Enabled” the Control_ and Status_ Mode Cool/Heat objects will appear.
    • When a “1” value is sent to the Control_ communication object, Heat mode will be enabled in the indoor unit, and the Status_ object will return this value.
    • When a “0” value is sent to the Control_ communication object, Cool mode will be enabled in the indoor unit, and the Status_ object will return this value.

4.2.3 Enable use of + / – object for Mode

This parameter shows/hides the Control_ Mode +/- communication object which let’s you change the indoor unit mode by using two different datapoint types.

  • If set to “Disabled” the object will not be shown.
  • If set to “Enabled” the Control_ Mode +/- object and a new parameter will appear.                                 Figure 4.11 Parameter detail 

➢ DPT type for +/- Mode Object

This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Mode +/- object.

The sequence followed when using this object is shown below:

Keep in mind that depending on the indoor unit you have and the available features, Auto mode and Dry mode may not be present.

4.2.4 Enable use of bit-type Mode objects (for control)

This parameter shows/hides the bit-type Control_Mode objects.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Control_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear. To activate a mode by using these objects a “1” value has to be sent.

4.2.5 Enable use of bit-type Mode objects (for status)

This parameter shows/hides the bit-type Status_ Mode objects.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Status_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.When enabled, a mode will return a “1” through its bit-type object.

4.2.6 Enable use of Text object for Mode

This parameter shows/hides the Status_ Mode Text communication object.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Status_ Mode Text object will appear. Also, in the parameters, will be shown five text fields, one for each mode, that will let modify the text string displayed by the Status_ Mode Text when changing mode.

Figure 4.12 Parameter detail

4.3 Global Fan Speed Configuration dialog

Figure 4.13 Default Fan Speed Configuration dialog

All the parameters in this section are related with the Fan Speed properties and communication objects.

4.3.1 DPT object type for fan speed

With this parameter is possible to change de DPT for the Control_ Fan Speed and Status_ Fan Speed byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.

  • When “Enumerated [DPT 5.010]” is selected, Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will be different.The first fan speed will be selected if a “1” is sent to the Control_ object. The secondone will be selected sending a “2”, and the last one sending a “3”.The Status_ object will always return the value for the fan speed selected. Important: If a “0” value is sent to the Control_ object, the minimum fan speed will be selected. If a value bigger than “3” is sent to the Control_ object, then the maximum fan speed will be selected.
  • When “Scaling [DPT 5.001]” is selected, Control_ Fan Speed and Status_Fan Speed communication objects for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will be different.

When a value between 0% and 49% is sent to the Control_ object the first fan speed will be selected.When a value between 50% and 83% is sent to the Control_ object, the second speed will be selected.When a value between 84% and 100% is sent to the Control_ object, the third speed will be selected.The Status_ object will return a 33% when the first speed is selected, a 67% for the second one and a 100% for the third one.

4.3.2 Enable use of “Fan Speed Man/Auto” objects (for Control and Status)This parameter shows/hides the Control_ Fan Speed Man/Auto and Status_ Fan Speed Man/Auto communication object which lets you set the Fan Speed into Manual or Auto mode.

4.3.3 Enable use of +/- object for Fan Speed

This parameter shows/hides the Control_ Fan Speed +/- communication object which lets you increase/decrease the indoor unit fan speed by using two different datapoint types.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Control_ Fan Speed +/- object and a new parameter will appear.

➢ Fan speed +/- operationThis parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Fan Speed +/- object.

➢ Sequence for +/- objectThis parameter lets choose between the different modes available:

  • S1>S2>….>SNSelect this option if you don’t have Auto mode and you don’t want roll-over to be enabled.
  • S1>S2>….>SN>S1>…Select this option if you don’t have Auto mode and you want roll-over to be enabled.
  • Auto>S1>S2>….>SNSelect this option if you have Auto mode and you don’t want roll-over to be enabled.
  • Auto>S1>S2>….>SN>Auto>S1>…Select this option if you have Auto mode and you want roll-over to be enabled.

4.3.4 Enable use of bit-type Fan Speed objects (for Control)This parameter shows/hides the bit-type Control_ Fan Speed objects.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Control_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear. To activate a Fan Speed by using these objects a “1” value has to be sent.

4.3.5 Enable use of bit-type Fan Speed objects (for Status)

This parameter shows/hides the bit-type Status_ Fan Speed objects.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Status_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear. When a Fan Speed is enabled, a “1” value is returned through its bittype object.

4.3.6 Enable use of Text object for Fan Speed

This parameter shows/hides the Status_ Fan Speed Text communication object.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Status_ Fan Speed Text object will appear. Also, in the parameters, will be shown two (or three, depending on the number of fan speeds selected) text fields, one for each Fan Speed, that will let modify the text string displayed by the Status_Fan Speed Text when changing a fan speed.Figure 4.15 Parameter detail

4.4 Global temperature configuration

Figure 4.20 Default Temperature Configuration dialog

All the parameters in this section are related with the Temperature properties and communication objects.

4.4.1 Enable use of +/- obj for Setpoint

This parameter shows/hides the Control_ Setpoint Temp +/- communication object which lets you change the indoor unit setpoint temperature by using two different datapoint types.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Control_ Setpoint Temp +/- object and a new parameter will appear.

                                    Figure 4.23 Parameter detail

➢ DPT type for +/- Setp Temp objectThis parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Setpoint Temp +/- object.(Lower limit) 16ºC 17ºC 31ºC 32ºC (Upper limit) Up / Increase Down / Decrease

4.4.2 Ambient Ref. Temp. is provided from KNX

This parameter shows/hides the Control_ Ambient Temperature communication object which lets you use an ambient temperature reference provided by a KNX device.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Control_ Ambient Temperature object will appear. Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference ambient temperature for the air conditioner. Then, the following formula applies for the calculation of real Control_ Setpoint Temperature sent ot the AC unit:“AC Setp. Temp” = “Ambient ref. Temp” – (“KNX Amb. Temp.” – “KNX Setp Temp.”) Temp”)
    • AC Setp. Temp: AC indoor unit setpoint temperature
    • Ambient Ref. Temp: AC indoor unit return temperature
    • KNX Amb. Temp.: Ambient temperature provided from KNX
    • KNX Setp. Temp: Setpoint temperature provided from KNXAs an example, consider the following situation:User wants: 19ºC (“KNX Setp. Temp.”)User sensor (a KNX sensor) reads: 21ºC (“KNX Amb Temp.”)Ambient temp. read by Haier system is: 24ºC (“Ambient Ref. Temp”)In this example, the final setpoint temperature that INKNXHAI0–C000will send out to the indoor unit (shown in “Setp. Temp.”) will become 24ºC – (21ºC – 19ºC) = 22ºC. This is the setpoint that will actually be requested to Haier unit.This formula will be applied as soon as the Control_ Setpoint Temperature and Control_ Ambient Temperature objects are written at least once from the KNX installation. After that, they are kept always consistent.Note that this formula will always drive the AC indoor unit demand in the right direction, regardless of the operation mode (Heat, Cool or Auto).

4.5 Control Mode configuration

Figure 4.20 Control Mode Configuration dialog

All the parameters in this section are related with the Mode properties and communication objects.

4.5.1 Enable use of Control Mode objects (for Control and Status)

This parameter shows/hides the Control_ Control Mode and Status_ Control Mode communication objects which lets you change the indoor unit control: No Central, LIFO (Last Input First Output), Central Controller and Lock Central Controller.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Control_ and Status_ Control Mode objects for No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller will appear.

4.5.1 Initial state of Control Mode

This parameter sets the initial value for the Control Mode: No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller or Do not initialize.

Figure 4.24 Parameter detail

  • If set to “Apply same initial state to all Indoor Units”, the parameter option selected will apply to all indoor units.
  • If set to “Initial state for each Indoor Unit might differ”, you will be able to set this parameter for each Indoor Unit individually.

4.6 Addressing of Indoor Units

Figure 4.24 Parameter detail

In this section you will be able to set the AC addressing for each AC unit present in the installation.

  • Modbus GW address of ACxx refers to the addres of the Haier Communication Addapters.
  • IDU index (in Modbus GW) of ACxx refers to the AC system address of the Indoor Unit.

4.7 License

Figure 4.24 Parameter detail

Use this section to introduce the migration code in case you need to update your box from another version different from the factory default one.

5 Technical Specifications

Enclosure

ABS (UL 94 V-0) de 2,5 mm / 1” thick Net dimensions (dxwxh): 71 x 71 x 27 mm / 2.8” x 2.8” x 1.1” Color: White RAL 9010

Operation Temperature

0ºC to +60ºC

Weight

42 g.

Stock Temperature

-20ºC to +85ºC

Power supply

Power is supplied by: 1 x KNX bus (29V DC, 7mA)

Operational Humidity

<90% RH, non-condensing

Terminal Wiring (for low-voltage signals)

For terminal: solid wires or stranded wires (twisted or with ferrule) 1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.5mm2 3 cores: not permitted

Stock Humidity

<90% RH, non-condensing

KNX port

1 x KNX TP1 (EIB) port opto-isolated. Plug-in terminal block (2 poles). TNV-1

Isolation voltage

1500 VDC

AC unit port

1 x Specific connector Plug-in terminal block (3 poles)

Isolation resistance

1000 MΩ

Configuration

Configuration with ETS

Protection

IP20 (IEC60529)

LED indicators

1 x Onboard LED – Operational status

6 AC Unit Types compatibility.

A list of Haier indoor unit model references compatible with INKNXHAI0- C000and their available features can be found in: [PDF]

7 Error Codes

Error Code in

KNX Object

Error in Remote Controller

 

Category

 

Error Name

1

1

Indoor Unit

Indoor ambient temp.sensor TA (Tas) failure

2

2

Indoor gas pipe temp. sensor TC1 failure

3

3

Indoor liquid pipe temp. sensor TC2 failure

4

4

Dual heat source sensor TW failure

5

5

Indoor EEPROM failure

6

6

Communication between indoor and outdoor failure

7

7

Communication between indoor and wired controller failure

8

8

Indoor float switch failure

9

9

Indoor address repeated failure

10

10

Reserved

11

11

Reserved

12

12

No 50 Hz zero passage signal

13

13

Coil sensor TC3 failure

14

14

DC motor failure

15

15

Indoor ambient temp.sensor TA (Taf) failure

16

16

17

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

18

18

19

19

20

20

Defrosting temp. sensor Tdef1 failure Defrosting temp. sensor Tdef2 failure

21

21

Ambient temp. sensor Ta failure

 22

  22

Suction temp. sensor Ts1 failure Suction temp. sensor Ts2 failure Suction temp. sensor Tsacc failure Suction temp. sensor Tsuc failure
 

23

 

23

Discharging temp. sensor Tdi failure Discharging temp. sensor Td1 failure Discharging temp. sensor Td2 failure

24

24

Oil temp. sensor Toilp failure Oil temp. sensor Toil failure

25

25

Inlet temp. of heat exchanger Toci1 failure Inlet temp. of heat exchanger Toci2 failure

 26

 26

indoor communication failure

Reduce the number of indoor units failure Increase the number of indoor units failure

27

27

Oil temp. too high protection (Toil) Oil temp. too high protection (Toi2)

28

28

High pressure sensor Pd1 failure High pressure sensor Pd2 failure

29

29

Low pressure sensor Ps failure

 30

 30

High pressure switch HPSi failure High pressure switch HPS1 failure High pressure switch HPS2 failure

31

31

Liquid pipe pressure Pl failure

32

32

Outlet temp. of subcooler Tsco failure

Liquid pipe SC temp. of subcooler Tliqsc failure

33

33

EEPROM (AT24C04) failure
 

34

 

34

Discharging temp. too high protection (Tdi) Discharging temp. too high protection (Td1) Discharging temp. too high protection (Td2)

35

35

4-way valve reversing failure 4-way valve reversing failure

36

36

Oil temp. too low protection (Toil) Oil temp. too low protection (Toi2)

37

37

Lack of phase of 3N power supply or wrong phase sequence

38

38

High pressure sensor Pd too low protection

 39

 39

Low pressure sensor Ps too low protection Compression ratio too high protection

Compression 1 ratio too low protection Compression 2 ratio too low protection

40

40

High pressure sensor Pd1 too high protection High pressure sensor Pd2 too high protection

41

41 Water temp. Twi too low protection Water temp. Twi too high protection

 42

 42

Frost protection of water system

Water system out of water freeze protection Water flow of Water system is too small to protect

 43

 43

Discharging temp. sensor Tdi too low protection Discharging temp. sensor Td1 too low protection Discharging temp. sensor Td2 too low protection

44

44

Low pressure sensor PS too high protection

45

45

Communication among outdoors failure

46

46

Communication with inverter board 1 failure Communication with inverter board 2failure

47

47

48

48

Unloading valve SV1 failure

49

49

50

50

51

51

52

52

53

53

Current detector CT1 failure

54

54

Communication with Thermal storage module failure

55

55

Thermal storage module LEV failure

56

56

Thermal storage module too hot failure

57

57

Communication between Thermal storage module and host computer

58

58

Thermal storage module Tc1 temp. sensor failure

59

59

Thermal storage module Tc2 temp. sensor failure

60

60

Reserved

61

61

Reserved

62

62

Reserved

63

63

Thermal storage module DIP setting failure

64

64

CT1 over current CT2 over current

65

65

66

66

67

67

Communication with motor driving board failure

68

68

69

69

70

70

71

71

Left DC motor blocked Right DC motor blocked

72

72

Left DC motor reversed Right DC motor reversed

73

73

Left DC motor current too high Right DC motor current too high

74

74

75

75

No pressure drop between high pressure and low one Pressure too low between high pressure and low one

76

76

Incorrect outdoor address or capacity setting

77

77

Oil equalization protection among outdoors

78

78

Lack of refrigerant in cooling Lack of refrigerant in heating

79

79

Incorrect wiring

80

80

Indoor and outdoor do not match

81

81

Model temp. too high protection

82

82

Compressor current protection

83

83

Wrong model selection

84

84

85

85

86

86

87

87

88

88

89

89

90

90

91

91

92

92

93

93

94

94

95

95

96

96

97

97

98

98

99

99

Program self-test failure

100

100

DC motor driving board IPM alarm

101

101

DC motor driving board detecting out of control

102

102

DC motor driving board EEPROM faulty

103

103

DC motor driving board over current or current detector damaged

104

104

Voltage too low protection of DC motor driving board

105

105

Voltage too high protection of DC motor driving board

106

106

DC motor driving board blocked

107

107

Protection of motor rate over Limitation

108

108

109

109

110

110

model 1 Over current model 2 Over current

111

111

Compressor 1 out of control Compressor 2 out of control

112

112

Radiator of model 1 temp. too high Radiator of model 2 temp. too high

113

113

model 1 overload

model 2 overload

114

114

Voltage too low of model 1 Voltage too low of model 2

115

115

Voltage too high of model 1 Voltage too high of model 2

116

116

Communication abnormal with model 1 Communication abnormal with model 2

117

117

Model 1 Over current (software) Model 1 Over current (software)

118

118

Model 1 startup failure Model 2 startup failure

119

119

Current Detecting Circuit Abnormal of transducer 1 Current Detecting Circuit Abnormal of transducer 2

120

120

Power supply of transducer 1 abnormal Power supply of transducer 2 abnormal

121

121

Power supply of inverter board 1 is abnormal Power supply of inverter board 2 is abnormal

122

122

Radiator temp. sensor of transducer 1 abnormal Radiator temp. sensor of transducer 2 abnormal

123

123

124

124

125

125

Compressor 1 frequency not match Compressor 2 frequency not match

126

126

127

127

MCU reset abnormal

128

128

MCU Program needs to be upgraded

0

N/A

KNX interface No error

65535 (-1)

N/A

KNX interface Indoor Units not ready for communication

65436 (-100)

N/A

KNX interface License Error / indoor unit not supported by current license

65336 (-200)

N/A

KNX interface Overconsumption error in EXY bus

In case you detect an error code not listed, contact your nearest Haier technical support service for more information on the error meaning.

Appendix A – Communication Objects Table

 

SECTION

OBJECT NUMBER  

NAME

 

LENGTH

DATAPOINT TYPE FLAGS  

FUNCTION

DPT_NAME DPT_ID R W T U
On/Off 1 Control_ On/Off 1 bit DPT_Switch 1.001 W T 0 – Off; 1-On
 

 

 

 

 

 

 

 

Mode

2 Control_ Operating Mode 1 byte DPT_HVACMode 20.102 W T 0 – Auto; 1 – Com; 2 – Stan; 3 – Eco; 4 – Pro
3 Control_ Mode 1 byte DPT_HVACControl 20.105 W T 0 – Auto; 1 – Heat; 3 – Cool; 9 – Fan; 14 – Dry
4 Control_ Mode Cool/Heat 1 bit DPT_Cool/Heat 1.100 W T 0 – Cool; 1 – Heat
5 Control_ Mode Auto 1 byte DPT_Scaling 5.001 W T 1 – Auto
6 Control_ Mode Heat 1 byte DPT_Scaling 5.001 W T 1 – Heat
7 Control_ Mode Cool 1 bit DPT_Bool 1.002 W T 1 – Cool
8 Control_ Mode Fan 1 bit DPT_Bool 1.002 W T 1 – Dry
9 Control_ Mode Dry 1 bit DPT_Bool 1.002 W T 1 – Fan
 

10

Control_ Mode +/- 1 bit DPT_Step 1.007 W 0 – Decrease; 1 – Increase
Control_ Mode +/- 1 bit DPT_UpDown 1.008 W 0 – Up; 1 – Down
 

 

 

 

 

 

Fan Speed

 

11

 

Control_ Fan Speed / 3 Speeds

 

1 byte

 

DPT_Scaling

 

5.001

 

W

 

T

0%-49% – Speed 1; 50%-83% – Speed 2;

84%-100% Speed 3

Control_ Fan Speed / 3 Speeds 1 byte DPT_Enumerated 5.010 W T 1 – Speed 1; 2 – Speed 2; 3 Speed 3
12 Control_ Fan Speed Man/Auto 1 bit DPT_Bool 1.002 W T 0 – Manual; 1 – Auto
13 Control_ Fan Speed 1 1 bit DPT_Bool 1.002 W T 1 – Fan Speed 1
14 Control_ Fan Speed 2 1 bit DPT_Bool 1.002 W T 1 – Fan Speed 2
15 Control_ Fan Speed 3 1 bit DPT_Bool 1.002 W T 1 – Fan Speed 3
 

16

Control_ Fan Speed +/- 1 bit DPT_Step 1.007 W T 0 – Decrease; 1 – Increase
Control_ Fan Speed +/- 1 bit DPT_UpDown 1.008 W T 0 – Up; 1 – Down
 

 

 

Temperature

17 Control_ Setpoint Temperature 2 byte DPT_Value_Temp 9.001 W T 17ºC to 30ºC
 

18

Control_ Setpoint Temp +/- 1 bit DPT_Step 1.007 W 0 – Decrease; 1 – Increase
Control_ Setpoint Temp +/- 1 bit DPT_UpDown 1.008 W 0 – Up; 1 – Down
19 Control_ Ambient Temperature 2 byte DPT_Value_Temp 9.001 W T ºC value in EIS5 format
 

 

 

Control Mode

20 Control_ Control Mode No Central 1 bit DPT_Bool 1.002 W T 1 – No Central Controller
21 Control_ Control Mode LIFO 1 bit DPT_Bool 1.002 W T 1 – Last Input First Output (LIFO)
22 Control_ Control Mode Central 1 bit DPT_Bool 1.002 W T 1 – Central Controller
23 Control_ Control Mode Lock 1 bit DPT_Bool 1.002 W T 1 – Lock Central Controller
On/Off 24 Status_ On/Off 1 bit DPT_Switch 1.001 R T 0 – Off; 1-On
 

 

 

 

 

 

 

Mode

25 Status_ Operating Mode 1 byte DPT_HVACMode 20.102 R T 0 – Auto; 1 – Com; 2 – Stan; 3 – Eco; 4 – Pro
26 Status_ Mode 1 byte DPT_HVACContrMode 20.105 R T 0 – Auto; 1 – Heat; 3 – Cool; 9 – Fan; 14 – Dry
27 Status_ Mode Cool/Heat 1 bit DPT_Heat/Cool 1.100 R T 0 – Cool; 1 – Heat
28 Status_ Mode Auto 1 bit DPT_Bool 1.002 R T 1 – Auto
29 Status_ Mode Heat 1 bit DPT_Bool 1.002 R T 1 – Heat
30 Status_ Mode Cool 1 bit DPT_Bool 1.002 R T 1 – Cool
31 Status_ Mode Fan 1 bit DPT_Bool 1.002 R T 1 – Fan
32 Status_ Mode Dry 1 bit DPT_Bool 1.002 R T 1 – Dry
33 Status_ Mode Text 14 byte DPT_String_8859_1 16.001 R T ASCII String
 

 

Fan Speed

 

34

Status_ Fan Speed / 3 Speeds 1 byte DPT_Scaling 5.001 R T 33% – Speed 1; 67% – Speed 2; 100% – Speed 3
Status_ Fan Speed / 3 Speeds 1 byte DPT_Enumerated 5.010 R T 1 – Speed 1; 2 – Speed 2; 3 – Speed 3
35 Status_ Fan Speed Man/Auto 1 bit DPT_Bool 1.002 R T 0 – Manual; 1 – Auto
36 Status_ Fan Speed 1 1 bit DPT_Bool 1.002 R T 1 – Speed 1
37 Status_ Fan Speed 2 1 bit DPT_Bool 1.002 R T 1 – Speed 2
38 Status_ Fan Speed 3 1 bit DPT_Bool 1.002 R T 1 – Speed 3
39 Status_ Fan Speed Text 14 byte DPT_String_8859_1 16.001 R T ASCII String
 

Temperature

40 Status_ AC Setpoint Temp 2 byte DPT_Value_Temp 9.001 R T 16ºC to 32ºC
41 Status_ AC Ambient Ref Temp 2 byte DPT_Value_Temp 9.001 R T ºC value in EIS5 format
 

 

Error

42 Status_ Error/Alarm 1 bit DTP_Alarm 1.005 R T 0 – No Alarm; 1 – Alarm
43 Status_ Error Code 2 byte Enumerated R T 0 – No Error; Any other see user’s manual
44 Status_ Error Text code 14 byte DPT_String_8859_1 16.001 R T 2 char Haier Error; Empty – none
 

 

 

Control Mode

45 Control_ Control Mode No Central 1 bit DPT_Bool 1.002 W T 1 – No Central Controller
46 Control_ Control Mode LIFO 1 bit DPT_Bool 1.002 W T 1 – Last Input First Output (LIFO)
47 Control_ Control Mode Central 1 bit DPT_Bool 1.002 W T 1 – Central Controller
48 Control_ Control Mode Lock 1 bit DPT_Bool 1.002 W T 1 – Lock Central Controller

NOTE: This addressing corresponds to the first AC indoor unit of the configuration. Communication objects for the rest of AC units are consecutively listed.

 

 

 

[xyz-ips snippet=”download-snippet”]


Posted

in

by