Knightsbridge OP7N/OP9N IP66 13A 1 Gang DP Switched Socket with Neons User Manual

INSTALLATION & MAINTENANCE MANUALOP7N / OP9N

GENERAL INSTRUCTIONS

These instructions should be read carefully and retained after installation by the end-user for future reference and maintenance. These instructions should be used to aid the installation of the following products: OP7N / OP9N

SAFETY

  • This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
  • Please isolate mains prior to installation or maintenance
  • Check the total load on the circuit (including when this product is fitted) does not exceed the rating of the circuit cable, fuse, or circuit breaker
  • Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
  • Do not overload this accessory or subject it to conditions outside its rating
  • This product is Class I and must be earthed
  • This product is IP66 rated

INSTALLATION

Please note: the unit should be fixed to a rigid flat surface as unevenness could cause damage to the product or affect the operation

  • Provide power to the required point of installation (refer to BS7671 for correct cabling methods)
  • Remove the front assembly from the backbox and carefully lift off the gasket. Drill the required number of fixing holes in the backbox (see Fig. 1)
  • Using the backbox as a template, mark the location for, and drill the fixing holes ensuring not to infringe with any gas/water pipes or electrical cables. The backbox can be rotated through 180° if required, to position the two cable entries on the topThe backbox has drain hole drilling guides marked (see Fig. 2). Drilling a drain hole is advised if the unit is installed in a location subject to temperature fluctuations where a build-up of condensation may occur. It is not advised if the unit will be subject to spray or jets, as drilling a drain hole will reduce the IP rating. A 3-5mm hole can be drilled at the bottom back edge of the enclosure where marked. If the wiring in conduit to the bottom entry, then the drain hole should be drilled at the lowest point of the conduit run not in the backbox
  • Remove one or more of the pre-fitted blank plugs as required by pushing out from the inside and install a suitable IP rated gland or adaptor (not supplied). For rear entry, cut or drill a 20/25mm hole where marked and install a suitable IP-rated grommet (not supplied). Unused cable entries must have the blank plugs fitted
  • Feed the mains cable into the unit and secure the base plate to the surface. The fixing holes are slotted to allow some rotational adjustment
  • Replace the gasket onto the backbox, then wire, as shown in Fig. 3 ensuring the correct polarity, is observed: L – Live (brown), E – Earth (green/yellow), N – Neutral (blue)
  • An earth connection must be made to the earth terminal of the socket. Use green/yellow sleeving on earth conductors that are not insulated. The earth terminal in the backbox is provided for convenience and does not need to be connected
  • Check all electrical connections are secure with no loose strands of cable
  • Ensuring the gasket does not become damaged or pinched, fit the socket assembly onto the backbox, taking care not to compress, damage, or trap any cables, and secure with the screws provided – do not overtighten
  • Fit screw covers
  • Switch on and checks for correct operation For security, and to prevent unwanted tampering with the product, a lug feature with a 6mm hole is provided to accept a padlock or similar locking security device (see Fig. 4).

Note: The Power Indicator is lit when there is the power to the unit and the switch is on, irrespective of whether a load is plugged in or notWARNINGTo ensure continued safe and proper weatherproof operation, the unit must not be left with the cover raised open or the catch left unlocked. Irreparable damage will occur if this instruction is not followed.

GENERAL

This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for where facilities exist. To clean the external surfaces, securely close the cover and use a damp cloth with a mild solution of detergent and warm water only, do not use aggressive cleaning products or solvents that may damage the product. If it is necessary to clean inside the cover, use a soft dry cloth only. Do not use any source of high-pressure washers to maintain or clean this product.

WARRANTY

This product has a warranty of 1 year from the date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period it should be returned to the place of purchase for a free-of-charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specifications without prior notice.

ML Accessories Limited LU5 4LTwww.mlaccessories.co.ukDCMAY20_V2

References

[xyz-ips snippet=”download-snippet”]