2400W Power Supply with Single Output
2400W Power Supply with Single Output
RSP-2400 series
CNS14336-1
UL62368-1
Bauar t gepruft Sicherheitegelma ge od o s be wac gwww. tuv.com ID 2000000000EN62368-1
TPTC004
IEC62368-1
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
RSP-2400 series
SPECIFICATION
MODEL
RSP-2400-12
RSP-2400-24
RSP-2400-48
DC VOLTAGE RATED CURRENT CURRENT RANGE
12V 166.7A 0 ~ 166.7A
24V 100A 0 ~ 100A
48V 50A 0 ~ 50A
RATED POWER
2000.4W
2400W
2400W
RIPPLE & NOISE (max.) Note.2 150mVp-p
150mVp-p
200mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
10.8 ~ 13.2V
VOLTAGE TOLERANCE Note.3 ±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±0.5%
22 ~ 28V ±1.0% ±0.5% ±0.5%
43 ~ 56V ±1.0% ±0.5% ±0.5%
SETUP, RISE TIME
1000ms, 80ms at full load
HOLD UP TIME (Typ.)
12ms at full load
VOLTAGE RANGE
180 ~ 264VAC 254 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
INPUT
POWER FACTOR (Typ.) EFFICIENCY (Typ.)
0.95/230VAC at full load 88%
90.5%
91.5%
AC CURRENT (Typ.) INRUSH CURRENT (Typ.)
15.5A/180VAC 60A/230VAC
12A/230VAC
LEAKAGE CURRENT
<2.0mA / 240VAC
OVERLOAD (OLP)
100 ~ 112% rated output power User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
PROTECTION OVER VOLTAGEOVER TEMPERATURE OUTPUT VOLTAGE PROGRAMMABLE(PV)
13.8 ~ 16.8V
28.8 ~ 33.6V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
2.4 ~ 13.2V
4.8 ~ 28V
Please refer to the Function Manual.
57.6 ~ 67.2V 9.6 ~ 56V
CURRENT SHARING FUNCTION AUXILIARY POWERREMOTE ON-OFF CONTROL REMOTE SENSE ALARM SIGNAL OUTPUT WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATION RESISTANCE
Up to 7200W or (2+1) units. Please refer to the Function Manual.
(Only for Remote ON-OFF control)
Please refer to the Function Manual
Compensate voltage drop on the load wiring up to 0.25V. Please refer to the Function Manual.
Power OK signal. Please refer to the Function Manual
-20 ~ +70 (Refer to “Derating Curve”)
20 ~ 90% RH non-condensing
-40 ~ +85, 10 ~ 95% RH non-condensing
±0.05%/ (0 ~ 50)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL62368-1, CSA C22.2 No. 62368-1, TUV EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH
Parameter
Standard
Test Level / Note
Conducted
EN55032 (CISPR32)
Class B
EMC EMISSIONSAFETY & EMC (Note 4)
Radiated
EN55032 (CISPR32)
Harmonic Current
EN61000-3-2
Voltage Flicker
EN61000-3-3
EN55024 , EN61204-3, EN61000-6-2, BSMI CNS13438
Parameter
Standard
ESD
EN61000-4-2
Class A ———Test Level / Note Level 3, 8KV air ; Level 2, 4KV contact
EMC IMMUNITY
Radiated EFT / Burst Surge
EN61000-4-3 EN61000-4-4 EN61000-4-5
Level 3 Level 3 Level 3, 2KV/Line-Earth ; Level 2, 1KV/Line-Line
Conducted
EN61000-4-6
Level 3
Magnetic Field
EN61000-4-8
Level 4
Voltage Dips and Interruptions
EN61000-4-11
>95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods
OTHERS NOTE
MTBF
234.1K hrs min. Telcordia SR-332 (Bellcore) ; 83.9K hrs min. MIL-HDBK-217F (25)
DIMENSION
278*177.8*63.5mm (L*W*H)
PACKING
3.3Kg; 4pcs/14.2Kg/1.81CUFT
Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
RSP-2400 series
Block Diagram
I/P
EMI FILTER
ACTIVE INRUSH CURRENT LIMITING
RECTIFIERS & PFC
POWER SWITCHING
RECTIFIERS &FILTER
PFC CONTROLO.T.P.
O.L.P.PWM CONTROL
LOAD SHARING
AUX
FAN
POWER
O.V.P.DETECTION CIRCUIT REMOTE CONTROLRECTIFIERS &FILTER
PFC fosc : 88KHz PWM fosc : 100KHz+S +V -V -SPV P OK RC CSAUX POWER
Static Characteristics
100 90 80 70 60 50180 185 190 195 200 210 220 230 240 250 264INPUT VOLTAGE (V) 60Hz
MODEL INPUT
12V
180~264VAC
2000.4W 166.7A
24V2400W 100A
48V2400W 50A
Derating Curve
Efficiency vs Load (48V Model)
92
100
90
EFFICIENCY (%)
88
80
86
8460
50
82
40
80
782076
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
-20
0
10
20
30
40
50
60
70 (HORIZONTAL)
AMBIENT TEMPERATURE ()
LOAD
The curve above is measured at 230VAC.
LOAD (%)
LOAD (%)
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single OutputFunction Manual1. Remote Sense The Remote Sense compensates voltage drop on the load wiring up to 0.25V
RSP-2400 series
CN2
PIN7 -S +V
PIN8 +S
+V LOAD-V
-V
Sense lines should be twisted in pairs to minimize
noise pick-up.
Caution: The power supply, by factory default(also the assumption for other sections), is shipped with, -S & -V on CN2, as well as +S & +V, shorted by
connector. When activating the Remote Sense, the +S signal should be connected to the positive terminal of the load whereas -S signal to
the negative terminal.
2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim) In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 20~110%(Typ.) of the nominal voltage by applying
EXTERNAL VOLTAGE.
CN2
PIN7 -S +V
PIN8 +S
PIN3 PV
-V
EXTERNAL VOLTAGE (DC)
PIN5 -S
Connecting an external DC source between PV & -S on CN2, and +S & +V, -S & -V also need to be connected as exhibited above.
OUTPUT VOLTAGE (%) OUTPUT CURRENT (%)
Vout 120
OVP >120%
100
100
80
Non-Linear
60
40
80
MODEL
12V
24V
48V
60 PV Range 2.4 ~ 13.2V 4.8 ~ 28V 9.6 ~ 56V
40
20
20
V
1
2
3
4
56
EXTERNAL VOLTAGE (DC)
V 20 40 60 80 100 120OUTPUT VOLTAGE (%)
Please do not adopt PWM signal as the EXTERNAL VOLTAGE.
The rated current should change with the Output Voltage Programming accordingly.
Caution: (1)By factory default, the Output Voltage Programming is not activated, and PV(PIN3) and PS(PIN4) of CN2 are shorted by connector. Whenever this function is not needed to activate, as assumed in other sections’ diagrams, please keep PV(PIN3) and PS(PIN4) of CN2 shorted ; otherwise, the power supply will have no output.(2)PV(PIN3) and PS(PIN4) of CN1 or CN2 must be disconnected if “Output Voltage Programming” function is used; otherwise, the internal electrical components may be damaged, and the power supply unit may thus be out of order.
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
RSP-2400 series
3.Remote ON-OFF Remote ON-OFF is activated by the configuration with respect to CN1,CN2 and CN3 as shown in the following diagram.CN2
Example 3.2(A): Using external voltage sourceInternal 12V typ.
PIN1 RCG
PIN2 RC
CN3
PIN7 AUXG
PIN8 AUXBy factory default, PV(PIN3) and PS(PIN4) on CN2 are shorted by connector; likewise, OLP(PIN9) and OL-SD(PIN10) on CN3 are shorted when shipped.
1K
AUX12V RCSW RCG
AUXG
Example 3.2(B): Using internal 12V auxiliary output AUX
Internal 12V typ.
1K
RCRCG SWAUXG
Example 3.2(C): Using internal 12V auxiliary output
Internal 12V typ.
1K
AUX 1KRC SWRCG
Connection Method
AUXG
SW Logic
Power supply output ON Power supply output OFF
Example 3.2(A) SW Open SW Close
Example 3.2(B) SW Open SW Close
Example 3.2(C) SW Close SW Open
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
RSP-2400 series
4.Alarm Signal Output Alarm signal is sent out through “P OK” & “P OK GND” and P OK2 & P OK GND2 pins on CN3. Please acknowledge an external voltage source is required for this function.
CN3
PIN3 P OK GND2 PIN1 P OK GND
PIN4 P OK2 PIN2 P OK
By factory default, OLP(PIN9) and OL-SD(PIN10) on CN3 are shorted by connector when shipped.
Function P OK
DescriptionThe signal is “Low” when the power supply is above 80% of the rated output voltage, or, say, Power OKThe signal turns to be “High” when the power supply is under 80% of the rated output voltage, or, say, Power Fail
Output of alarm(P OK, Relay Contact) Low (0.5V max at 500mA)High or open (External applied voltage, 500mA max.)
Output of alarm(P OK2, TTL Signal) Low (0.5V max at 10mA)High or open (External applied voltage, 10mA max.)
Table 4.1 Explanation of alarm
P OK
P OK2
R V
0.1uF
R V
P OK GND
External voltage and R (The max. sink is 500mA and 20V)
Fig. 4.1 Internal circuit of P OK (Relay, total is 10W)
P OK GND2
External voltage and R (The max. sink is 10mA and 30V)
Fig. 4.2 Internal circuit of P OK2 (Open collector method)
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
RSP-2400 series
5.Select Overload Protection Type (1)Insert the shorting connector on CN3 that is shown in Fig 5.1, the Overload Protection Type will be “constant current limiting with delay shutdown after 5 seconds, re-power on to recover”. This is the factory default. (2)Remove the shorting connector on CN3 that is shown in Fig 5.2, the Overload Protection Type will be “continuous constant current limiting”.
OL-SD OLP
OL-SD OLP
Fig. 5.1 Insert the CN3 Overload Protection Type : constant current limiting with delay shutdown after 5 seconds
Fig. 5.2 Remove the CN3 Overload Protection Type : constant current limiting
6.Current Sharing with Remote SenseRSP-2400 has the built-in active current sharing function and can be connected in parallel, up to 3 units, to provide higher output power as exhibited below : The power supplies should be paralleled using short and large diameter wiring and then connected to the load. Difference of output voltages among parallel units should be less than 0.2V. The total output current must not exceed the value determined by the following equation:Maximum output current at parallel operation=(Rated current per unit)×(Number of unit)×0.9 When the total output current is less than 3% of the total rated current, or say (3% of Rated current per unit)×(Number of unit)the current shared among units may not be fully balanced.
No.1(Master)
AC/L AC/NNo.2(Slave)
+V -V
When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unitSense lines should be twisted in pairs to minimize noise pick-up.+S +V Load-V -S
AC/L AC/NNo.3(Slave)
+V -V
+V-V AC/L AC/N+S,-S and CS on CN1 or CN2are connected mutually in parallel. Under parallel operation, the “output voltage programming” function is not available.
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
RSP-2400 series
6.Three Phase Connect Users can exploit three units of RSP-2400(unit 1 ,unit 2,unit 3) to work with 3power system. Please refer to following diagrams for configuration.
FIG. A: 33 wire 220VAC SYSTEM
R
220V
unit 1 L1FG1 N1
unit 2 L2FG2 N2
unit 3
L3
S
FG3
N3
220V
T
FG
FIG. B: 34 wire 220/380VAC SYSTEMRN S T
380V
220V
unit 1 L1FG1 N1unit 2 L2FG2 N2unit 3 L3FG3 N3FG
FIG. C: 34 wire 190/110VAC SYSTEMRN (N.C.)S T
190V
110V
unit 1 L1FG1 N1unit 2 L2FG2 N2unit 3 L3FG3 N3FG
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single OutputMechanical Specification278 236.3
18-M4(Both Sides) L=5mm4-M4 L=5mm1
236.3
Air flow direction1
162
7.9
RSP-2400 series
271271
38 12.5 2063.5
Case No.982B Unit:mm
40
2-M4 8.5M3
CN1 CN2 CN38 6 4 2 8 6 4 2 10 8 6 4 2 7 531 7 5 31 9 75 31
OUTPUT +V-V
CN1 CN2 CN38 6 4 2 8 6 4 2 10 8 6 4 2 7 531 7 5 31 97 5 31
177.8 LED SVR +
13 10 4
INPUT116max.
TB1123
Mounting Instruction
Hole No. Recommended Screw Size
1
M4
MAX. Penetration Depth L 5mm
Recommended mounting torque 7~10Kgf-cm
Control Pin No. Assignment (CN1,CN2) : HRS DF11-8DP-2DS or equivalent
82
Mating Housing HRS DF11-8DS or equivalent
Terminal HRS DF11-**SC or equivalent
71
CN1 and CN2 are connected internally.
Pin No. 1 2 3 4 5,7 6 8
Function RCG RC PV PS -SCS(Current Share) +S
Description Remote ON-OFF Ground Remote ON-OFF Connection for output voltage programming Reference Voltage Terminal Negative sensing for remote sense Current Share Postive sensing for remote sense
Mounting Surface
Chassis of RSP-2400
Mounting Screw L
File Name:RSP-2400-SPEC 2020-09-29
2400W Power Supply with Single Output
Control Pin No. Assignment (CN3) : HRS DF11-10DP-2DS or equivalent
10 2 91
Mating Housing HRS DF11-10DS or equivalent Terminal HRS DF11-**SC or equivalent
Pin No. 1 2 3 4 5 6 7 8 9 10
Function P OK GNDP OK P OK GND2P OK2 RCG RC AUXG AUX OLP OL-SD
Description Power OK Ground Power OK Signal (Relay Contact) Power OK Ground Power OK Signal (TTL Signal) Remote ON-OFF Ground Remote ON-OFF Auxiliary Ground Auxiliary OutputOverload(OLP) type select
AC Input Terminal Pin No. Assignment
Pin No. Assignment
Diagram
1
AC/L
2
AC/N
3
FG
Maximum mounting torque 18Kgf-cm
Installation ManualPlease refer to : http://www.meanwell.com/manual.html
RSP-2400 series
File Name:RSP-2400-SPEC 2020-09-29
References