Munters ROTEM Platinum Pro Expansion Box Installation Guide

Munters ROTEM Platinum Pro Expansion Box Installation Guide

Platinum Pro Expansion

Rotem Expansion

 

Layout

Figure 1: Rotem Expansion

Figure 2: Platinum Pro Expansion

NOTE: The Rotem Expansion supports analog input, analog output, and digital input cards. Platinum Pro Expansion does not support these cards.

 

Wiring Diagrams

1. Wire the Platinum Pro PP-485ISO-485/PP232ISO-485 card to the Platinum Expansion RS-485 card.

Figure 3: Platinum Pro to Rotem Expansion Wiring

Figure 4: Platinum Pro to Platinum Expansion Wiring

2. To ensure proper termination, place a:

  • A terminator on the EXP jumpers on the Rotem One/Platinum Pro communication card (if the Platinum Pro is located at the end of a daisy chain)
  • A 120 ohm resistor on the Expansion communication card

3. The Controller and Expansion RS-485 cards each have dip switches that define the unit’s function and address.

  • Define the Controller’s RS-485 card dip switches as Main.
  • Define the Expansion units dip switches as required.

Table 1: Dip Switch Settings

Figure 5: Expansion Address Dip Switches

4. Connect the relays (and analog/digital devices if relevant) as required. Refer to the Platinum Pro/Rotem One Installation manual for details.5. Attach the power wiring to the Expansion as shown below.

Figure 6: Rotem Expansion Power Wiring

Figure 7: Platinum Expansion Power Wiring

  • Connect the power supply wires to the appropriate ports (1).
  • 230 VAC, 50/60 Hz; USA: L1, L2; ROW line, neutral (2)

 

© Munters AB, 2013 P/N: 116537Ag/MIS/IGB-2572-04/18 Rev. 1.1

 