MW 60W DIN R Ultra Slim Step Shape ail Owner’s Manual

60WUltra Slim Step Shape DIN-RailHDR-60 series

Features

  • Ultra slim design with 52.5mm(3SU) width
  • Universal input 85-264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections: Short circuit/Overload/Over voltage
  • Cooling by free air convection (working temperature: -30~+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • Overvoltage category III
  • LED indicator for power on
  • 3 years warranty

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

Description

HDR-60 is one economical ultra slim 60W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 52.5mm(3SU) in width, which allows space-saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC (277VAC operational) and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current.HDR-60 is designed with plastic housing that can effectively prevent a user from electric hazards. With a working efficiency of up to 91%, the entire series can operate at the ambient temperature between -30°C and air convection. The complete protection functions and relevant certificates for home automation and industrial 70°C under control apparatus (IEC60950-1, UL508, UL60950-1, EN61558-2-16) make HDR-60 a very competitive power supply solution for household and industrial applications.

Model Encoding

SPECIFICATION

MODEL HDR-60-5 HDR-60-12 HDR-60-15 HDR-60-24 HDR-60-48
 

 

 

 

 

 

 

OUTPUT

DC VOLTAGE 5V 12V 15V 24V 48V
RATED CURRENT 6.5A 4.5A 4A 2.5A 1.25A
CURRENT RANGE 0 ~ 6.5A 0 ~ 4.5A 0 ~ 4A 0 ~ 2.5A 0 ~ 1.25A
RATED POWER 32.5W 54W 60W 60W 60W
RIPPLE & NOISE (max.) Note.2 80mVp-p 120mVp-p 120mVp-p 150mVp-p 240mVp-p
VOLTAGE ADJ. RANGE 5.0 ~ 5.5V 10.8 ~ 13.8V 13.5 ~ 18V 21.6 ~ 29V 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 500ms, 50ms/230VAC   500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 30ms/230VAC    12ms/115VAC at full load
 

 

 

INPUT

VOLTAGE RANGE 85 ~ 264VAC (277VAC operational )      120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 85% 88% 89% 90% 91%
AC CURRENT (Typ.) 1.2A/115VAC     0.8A/230VAC
INRUSH  CURRENT (Typ.) COLD START 30A/115VAC       60A/230VAC
 

 

 

PROTECTION

 

OVERLOAD

105 ~ 160% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed

Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed

 

OVER VOLTAGE

5.75 ~ 6.75V 14.2 ~ 16.2V 18.8 ~ 22.5V 30 ~ 36V 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
 

 

 

ENVIRONMENT

WORKING TEMP. -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE 2000 meters
OVER VOLTAGE CATEGORY Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters
 

 

 

 

 

 

 

 

 

 

SAFETY & EMC

(Note 4)

SAFETY STANDARDS UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design refer to TUV EN60950-1
WITHSTAND VOLTAGE I/P-O/P:4KVAC
ISOLATION RESISTANCE I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
 

 

 

EMC EMISSION

Parameter Standard Test Level / Note
Conducted EN55032(CISPR32), CNS13438 Class B
Radiated EN55032(CISPR32), CNS13438 Class B
Harmonic Current EN61000-3-2 Class A
Voltage Flicker EN61000-3-3 ——-
 

 

 

 

 

 

EMC IMMUNITY

EN55024, EN55035, EN61000-6-2, EN61204-3
Parameter Standard Test Level /Note
ESD EN61000-4-2 Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility EN61000-4-3 Level 3, criteria A
EFT/Burest EN61000-4-4 Level 3, criteria A
Surge EN61000-4-5 Level 4,2KV/L-N, criteria A
Conducted EN61000-4-6 Level 3, criteria A
Magnetic Field EN61000-4-8 Level 4, criteria A
Voltage Dips and interruptions EN61000-4-11 >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods
 

OTHERS

MTBF 927.6K hrs min.     MIL-HDBK-217F (25℃)
DIMENSION 52.5*90*54.5mm (W*H*D)
PACKING 190g;60pcs/12.4Kg/0.97CUFT
 

 

 

 

 

NOTE

1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.3.  Tolerance: includes set up tolerance, line regulation and load regulation.4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMl testing of component power supplies.” (as available on http://www.meanwell.com}5.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}.

Block Diagram

Derating Curve

Output Derating VS Input Voltage

Mechanical Specification

( Unit: mm, tolerance ± 0.5mm)

 

Installation Manual

Please refer to: http://www.meanwell.com/manual.html