resideo Braukmann TM200 Thermostatic Mixing Valve Instruction Manual

BraukmannTM200Installation instructions

Thermostatic Mixing Valve

Safety Guidelines

  1. Follow the installation instructions.
  2. Use the appliance• according to its intended use• in good condition• with due regard to safety and risk of danger.
  3. Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical  Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.
  4. Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
  5. Immediately rectify any malfunctions which may influence safety.

Technical Data

Media
Medium: Drinking water
Connections/Sizes
Connection size: G3/4″ or Ø22
Pressure values
Max. operating pressure: max. 10 bar
Maximum pressure

difference between hot and cold inlet supplies:

2.5 bar
Operating temperatures
Max. hot water inlet temperature: 90 °C
Setting range: 30 – 60 °C
The preset temperature during manufacture: 40 °C
Control accuracy: <±4 K
Specifications
Flow rate at 1.0 bar pressure differential across valve: appr. 27 l/min
Installation position: Arbitrary

Options

For Options visit homecomfort.resideo.com/europe

Assembly

Installation Guidelines

  • Install without tension or bending stresses
  • Fit a return flow-retarder unit where the hot water supply system includes a circulation circuit
  • Observe the flow direction arrow when fitting a return flow-retarder unit
  • To prevent the growth of legionella, DVGW-W551 specifies that the water volume in the pipework between the mixer valve and the furthest take-off point should not exceed 3 liters. This corresponds to a maximum length of 10 meters for 3 /4″ (20  mm) pipework and 17 meters for 1 /2″ (15 mm)
  • Requires regular maintenance in accordance with EN 806-5

Assembly instructions

As a mixing valveThe flow direction arrows must be observed when connecting the hot and cold water inlets.As a diverter valve

CAUTION!For this application, flow is in the reverse direction and therefore is in the opposite direction to the arrows on the housing.

Changing the setting

The mixing valve can be set within the range 30 °C to 60 °C as follows:

  • Remove the protective cap.
  • Turn the adjuster knob until the required setting number aligns with the index mark 8 on the valve body.

Disposal

Observe the local requirements regarding correct waste recycling/disposal!

Spare Parts

For Spare Parts visit homecomfort.resideo.com/europe

Accessories

For Accessories visit homecomfort.resideo.com/europe