Bard 8403-062 Remote Indoor Air Temperature Sensor Instructions

Table of Contents

Bard 8403-062 Remote Indoor Air Temperature Sensor Instructions

Installation

Carefully read and follow entire instructions before starting the installation. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage the controller sensor.

The 8403-062 Remote Indoor Temperature Sensor is a 10k-ohm Type II thermistor, which can be used as an accessory for use with Bard 8403-060 controller system or the Bard CompleteStat controller series. The 8403-060 can be configured to control using the 8403-062 remote sensor as the only sensor, or to average the measured temperature at the remote sensor location with the temperature at the controller location.

  1. Shielded twisted pair, 22 AWG (or heavier) should be used to avoid possible interference from other electrical systems. The shield (drain) should be connected to 24V Common (C) on the controller end.
  2. The sensor comes with a cover and mounting base to mount and protect the remote indoor sensor.
  3. Select the exact mounting location and route a 2-conductor interconnecting wire between the remote indoor sensor and the 8403-060 controller location.
  4. Terminate the interconnection wiring at the two screw terminals on the remote indoor sensor. See Figure 1 for 8403-060 and CompleteStat connections.
  5. The termination point at the controller will be GND and ID terminals at the right side of the controller subbase. Sensor polarity is not important.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506www.bardhvac.com

Manual: 7960-554BSupersedes: 7960-554ADate: 10-2-2020

Testing Completed WiringWhen the 8403-062 sensor is properly connected, the 8403-060 controller will recognize the sensor connection and automatically place Remote Indoor Sensor selection options in the Installer menu. Access Installer menu and go to Remote Indoor Sensor option. Select either “Remote sensor only” or “Average with stat”.See Table 1 for Temperature/Ohm relationship of the sensor.

TABLE 1 Degrees F/Ω

Temp °F

Ω Temp °F Ω Temp °F Ω Temp °F Ω
0 85,378 33 31,738 66 13,138 99

5,961

1

82,710 34 30,855 67 12,811 100

5,827

2

80,135 35 30,000 68 12,493 101 5,697
3 77,649 36 29,171 69 12,184 102

5,570

4

75,249 37 28,367 70 11,883 103 5,446
5 72,931 38 27,589 71 11,591 104

5,326

6

70,693 39 26,834 72 11,307 105 5,208
7 68,531 40 26,103 73 11,031 106

5,094

8

66,442 41 25,394 74 10,762 107 4,982
9 64,475 42 24,706 75 10,501 108

4,873

10

62,475 43 24,039 76 10,247 109 4,767
11 60,592 44 23,393 77 10,000 110

4,663

12

58,771 45 22,766 78 9,760 111 4,562
13 57,012 46 22,158 79 9,526 112

4,464

14

55,311 47 21,568 80 9,298 113 4,368
15 53,667 48 20,996 81 9,077 114

4,274

16

52,077 49 20,441 82 8,862 115 4,183
17 50,540 50 19,902 83 8,651 116

4,094

18

49,054 51 19,379 84 8,448 117 4,007
19 47,616 52 18,872 85 8,250 118

3,922

20

46,225 53 18,379 86 8,056 119 3,839
21 44,880 54 17,902 87 7,868 120

3,758

22

43,578 55 17,438 88 7,685 121 3,679
23 42,318 56 16,987 89 7,507 122

3,602

24

41,099 57 16,550 90 7,333 123 3,527
25 39,920 58 16,125 91 7,164 124

3,453

26

38,778 59 15,713 92 7,000 125 3,382
27 37,672 60 15,312 93 6,839 126

3,312

28

36,602 61 14,923 94 6,683 127 3,243
29 35,566 62 14,545 95 6,531 128

3,177

30

34,563 63 14,178 96 6,383 129 3,112
31 33,591 64 13,822 97 6,238 130

3,048

32

32,650 65 13,475 98 6,098

 