Bard Dehumidification Refrigerant Reheat Circuit Installation Guide

Bard Dehumidification Refrigerant Reheat Circuit

This model provides a unique dehumidification circuit for periods of low outdoor ambient temperature and high indoor humidity conditions.Refer to Specification Sheet S3588 for the standard features of the base units and this manual for electrical data.

Dehumidification Circuit

The dehumidification refrigerant reheat circuit is controlled by a dehumidification valve directing the refrigerant gas to the normal condenser during periods when standard air conditioning is required. During periods of high indoor humidity, a humidistat senses the need for mechanical dehumidification. It then energizes both the compressor circuit and the dehumidification valve, thus directing the hot refrigerant discharge gas into a separate desuperheating condenser circuit, which reheats the conditioned air before it is delivered to the room. The refrigerant gas is then routed from the desuperheating condenser to the system condenser for further heat transfer. When the humidistat is satisfied, the system automatically switches back to normal A/C mode and either continues to operate or turns off based on the signal from the wall thermostat. The result is separate humidity control at minimum operating cost. See Figure 1 on page 2.

Dehumidification Sequence of Operation

Dehumidification is controlled through the thermostat (if capable) or through a separate humidistat. On a call for dehumidification mode of operation, the compressor and dehumidification valve of the unit are energized through circuit R – D to provide dehumidification. Dehumidification will continue until the humidistat is satisfied.

Any time there is a call for circuit R – Y1, the dehumidification mode will cancel and the system will return to cooling operation.

Balanced Climate™ Mode

It is recommended to enable Balanced Climate mode and utilize a 2-stage thermostat to enhance the dehumidification performance and comfort.

NOTE: To activate this mode, the jumper between Y1 and Y2 on the low voltage terminal strip needs to be removed.

In units with an economizer vent, balance climate mode should not be used. The Y1 and Y2 jumper must remain installed.

This mode will allow the indoor blower to run at a reduced airflow on the first stage of cooling. A 2-stage thermostat connected to Y2 will then allow the airflow to return to normal rated speed if the call for dehumidification or cooling is not satisfied within the allotted time frame specified by the thermostat. See latest revision of unit installation instructions 2100-721 for more information regarding the Balanced Climate operation.

Electronic Expansion Valve

Operation

This model employs an electronic expansion valve (EEV) which meters the refrigerant to the evaporator. The EEV is made of a stepper motor that is controlled with a step output from the controller. The valve is capable of 480 steps which drives a needle valve that in turn regulates the flow of refrigerant. The EEV allows for tighter control and better capacity management in varying operating conditions than a standard TXV. The EEV system consists of the electronic valve and stator, control board, relay, suction temperature sensor and suction pressure transducer. The pressure transducer and temperature sensor monitor the suction line to provide real time data to the control board so that a real time superheat can be calculated. This then determines the EEV position. The controller is sent to maintain around 13° superheat. The relay is used to activate the EEV system’s controller anytime that the compressor is energized.

WARNING/AVERTISSEMENT

– Exposure to high pressure refrigerant hazard.– This unit is equipped with an electronic expansion valve. In order to fully recover refrigerant or evacuate the system during repairs, be sure to use service tool 2151-021 to manually open the electronic expansion valve or be sure to recover and evacuate from all service ports; suction, liquid, and discharge. – Failure to do so could result in eye injuries and/or refrigerant burns.

EEV Instructions for Vacuuming, Reclaiming and Charging Unit

The electronic expansion valve moves to a closed position when there is no call to control. In order to pull a complete vacuum, fully reclaim the system or charge the unit, connections to both the suction and discharge service ports need to be utilized or the valve needs to be manually opened first. The valve can be opened manually using the magnetic EEV service tool (Bard Part # 2151-021) shown in Figure 2. To do this, remove the EEV stator coil (red color with retaining nut on top), slide the magnetic tool over the shaft where the stator was removed and turn in a clockwise direction to open the valve to the full open position (directional arrows are provided on the tool).Reapply the EEV stator coil and retaining nut once complete. Upon powering the unit back up, the control board will automatically drive the EEV back to the fully shut position. Once the compressor starts, the control board will again modulate the EEV position to control the system superheat.

Troubleshooting the Electronic Expansion Valve

The control board has two status LEDs.

  • The green LED should be lit anytime that the board has power and the control is functioning.
  • The red LED is to show that an alarm is present.

See Table 1 on page 4 for a guide to know where to start troubleshooting the EEV. Refer to the appropriate unit replacement parts manual for any parts that are needed.

Control Board

Check that the controller is getting 24VAC signal (GO 24VAC Hot and G 24VAC common). Reference unit wiring diagram for proper connections. If 24V is present but the green LED is not lit, replace the controller. If the green LED is now lit but the superheat is still not being maintained, troubleshoot the relay to check that the DI is connected to G; refer to Relay in EEV Control Box below.

Electronic Expansion Valve

Check to see if valve can be moved by manually moving the stepper motor using the EEV service tool shown in Figure 1 (Bard Part # 2151-021). If valve still does not control, check the transducer and thermistor sensors as described on page 5. If sensors are good, replace the valve.

Relay in EEV Control Box

Contacts NO to DI and COM to G must be closed for EEV control to start controlling superheat. Check that the relay is getting 24VAC. Reference unit wiring diagram for proper connections. If 24V is present, measure the resistance between COM and NO; it should be 0 ohms when the relay is getting 24V. If the resistance is out of range, replace the relay.

TABLE 1Electronic Expansion Valve Troubleshooting

Problem Probable Cause Troubleshoot
The green LED is not lit. Controller not receiving 24VAC signal. Control Board
The green LED is lit, but superheat is not being maintained. The relay is not closing the controller’s DI connection to ground. Relay
The red LED is flashing and EEV is not controlling superheat properly (13º superheat). One of the following is likely the fault:
1. Low superheat is detected and the controller is taking steps to protect the system by closing the valve. Stator is broken or connected incorrectly. Stator
Valve is stuck open. EEV Valve
2. Suction temperature sensor error. Poor connection of sensor or faulty sensor. Thermistor
3. Suction pressure transducer error. Pressure transducer wiring incorrect or faulty transducer. Transducer
The red LED is on steady. The operating parameters have been damaged. Replace Control Board
Stator Coil

Disconnect the stator from the valve and the control and measure the resistance of the windings using an electrical tester. The resistance of both windings should be around 40 ohms +/­ 10%. The four wire sets that will have resistance between them are: White and red, green and red, yellow and purple, blue and purple. If the resistance falls outside these values, replace the stator.

Transducer Sensor
  1. Check continuity of all three wires from transducer plug to controller plug. Replace wires if poor connection in any wire.
  2. Check to ensure wires are correctly connected as follows:Blue wire = pin 1 of controller plug to pin C on transducer plugRed wire = pin 2 of controller plug to pin B on transducer plugBlack wire = pin 3 of controller plug to pin A on transducer plug
  3. Check that there is 5VDC Nominal between the red and black wires going to the transducer.
  4. Check the signal voltage between the blue and black wires (0.5-4.5VDC Actual). The following formula and Figure 3 can be used to determine if the transducer’s voltage to pressure ratio is within range. Replace transducer if out of range.

Formula for Tech:(Measured Pressure x .016) + .5 =Expected Transducer Signal Voltage (see Figure 3)

Thermistor Sensor
  1. Make a visual check for broken wire insulation, broken wires or cracked epoxy material.
  2. Disconnect 10k ohm NTC thermistor from the EEV control box.
  3. Use an ohmmeter to measure the resistance between the two connectors. Also use ohmmeter to check for short or open.
  4. Compare the resistance reading to Table 2. Use sensor ambient temperature. (Tolerance of part is ±10 %.)
  5. If sensor is out of tolerance, shorted, open or reads very low ohms, it should be replaced.

TABLE 210K Ohm NTC Sensor: Temperature/Resistance

Temperature Resistance
F C Ω
-40 -40 188,500
-38.2 -39 178,500
-36.4 -38 169,000
-34.6 -37 160,200
-32.8 -36 151,900
-31 -35 144,100
-29.2 -34 136,700
-27.4 -33 129,800
-25.6 -32 123,300
-23.8 -31 117,100
-22 -30 111,300
-20.2 -29 105,700
-18.4 -28 100,500
-16.6 -27 95,520
-14.8 -26 90,840
-13 -25 86,430
-11.2 -24 82,260
-9.4 -23 78,330
-7.6 -22 74,610
-5.8 -21 71,100
-4 -20 67,770
-2.2 -19 64,570
-0.4 -18 61,540
1.4 -17 58,680
3.2 -16 55,970
5 -15 53,410
6.8 -14 50,980
8.6 -13 48,680
10.4 -12 46,500
12.2 -11 44,430
14 -10 42,470
15.8 -9 40,570
17.6 -8 38,770
19.4 -7 37,060
21.2 -6 35,440
23 -5 33,900
24.8 -4 32,440
26.6 -3 31,050
28.4 -2 29,730
30.2 -1 28,480
32 0 27,280
33.8 1 26,130
35.6 2 25,030
37.4 3 23,990
39.2 4 23,000
41 5 22,050
42.8 6 21,150
44.6 7 20,300
46.4 8 19,480
48.2 9 18,700
50 10 17,960
51.8 11 17,240
53.6 12 16,560
55.4 13 15,900
57.2 14 15,280
59 15 14,690
60.8 16 14,120
62.6 17 13,580
64.4 18 13,060
66.2 19 12,560
68 20 12,090
69.8 21 11,630
71.6 22 11,200
73.4 23 10,780
75.2 24 10,380
77 25 10,000
78.8 26 9,630
80.6 27 9,280
82.4 28 8,940
84.2 29 8,620
86 30 8,310
87.8 31 8,010
89.6 32 7,730
91.4 33 7,450
93.2 34 7,190
95 35 6,940
96.8 36 6,700
98.6 37 6,470
100.4 38 6,250
102.2 39 6,030
104 40 5,830
105.8 41 5,630
107.6 42 5,440
109.4 43 5,260
111.2 44 5,080
113 45 4,910
114.8 46 4,750
116.6 47 4,590
118.4 48 4,440
120.2 49 4,300
122 50 4,160
123.8 51 4,030
125.6 52 3,900
127.4 53 3,770
129.2 54 3,650
131 55 3,540
132.8 56 3,430
134.6 57 3,320
136.4 58 3,220
138.2 59 3,120
140 60 3,020
141.8 61 2,930
143.6 62 2,840
145.4 63 2,750
147.2 64 2,670
149 65 2,590
150.8 66 2,510
152.6 67 2,440
154.4 68 2,360
156.2 69 2,300
158 70 2,230
159.8 71 2,160
161.6 72 2,100
163.4 73 2,040
165.2 74 1,980
167 75 1,920
168.8 76 1,870
170.6 77 1,820
172.4 78 1,770
174.2 79 1,920
176 80 1,670
177.8 81 1,620
179.6 82 1,580
181.4 83 1,530
183.2 84 1,490
185 85 1,450
186.8 86 1,441
188.6 87 1,370
190.4 88 1,340
192.2 89 1,300
194 90 1,270
195.8 91 1,230
197.6 92 1,200
199.4 93 1,170
201.2 94 1,140
203 95 1,110
204.8 96 1,080
206.6 97 1,050
208.4 98 1,020
210.2 99 1,000
212 100 970

W24G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 26,700 13,300 26,100 11,500 25,500 10,300 24,700 7,900 23,900 6,000 23,100 4,000 22,200 2,000 21,200 20,100
Sensible Btuh 19,700 5,700 19,400 4,300 19,700 3,300 18,800 1,400 18,400 18,000 (1,500) 17,600 (3,000) 17,100 (4,400) 16,700 (6,000)
S/T 0.738 0.429 0.743 0.374 0.773 0.320 0.761 0.177 0.770 0.000 0.779 0 0.793 0 0.807 0 0.831 0
Latent Btuh 7,000 7,600 6,700 7,200 5,800 7,000 5,900 6,500 5,500 6,000 5,100 5,500 4,600 5,000 4,100 4,300 3,400 3,800
Lbs. H20/hr. 6.6 7.2 6.3 6.8 5.5 6.6 5.6 6.1 5.2 5.7 4.8 5.2 4.3 4.7 3.9 4.1 3.2 3.6
Supply Air DB 52.5 66.5 52.8 68.6 53.1 70.2 53.5 72.9 53.9 75.0 54.3 77.2 54.9 79.5 55.4 81.7 56.0 83.9
Supply Air WB 51.1 55.6 51.4 56.6 51.6 57.0 51.9 58.6 52.3 59.6 52.7 60.6 53.1 61.7 53.5 62.7 54.0 63.8
Suction PSIG4 123 116 124 118 124 119 126 121 127 123 128 125 130 127 131 128 133 130
Discharge PSIG4 273 240 292 253 308 263 333 282 356 298 379 314 404 331 430 348 457 367
75/64.1 (55% RH) Total Cooling Btuh 27,500 14,100 26,900 12,400 26,200 10,600 25,500 8,700 24,700 6,800 23,900 4,900 23,000 2,900 22,000 800 20,900
Sensible Btuh 18,700 5,100 18,400 3,700 18,100 2,300 17,800 800 17,400 (600) 17,000 (2,100) 16,600 (3,600) 16,100 (5,100) 15,700 (6,600)
S/T 0.680 0.36 0.684 0.30 0.691 0.22 0.698 0.09 0.704 0 0.711 0 0.722 0 0.732 0 0.751 0
Latent Btuh 8,800 9,000 8,500 8,700 8,100 8,300 7,700 7,900 7,300 7,400 6,900 7,000 6,400 6,500 5,900 5,900 5,200 5,300
Lbs. H20/hr. 8.3 8.5 8.0 8.2 7.6 7.8 7.3 7.5 6.9 7.0 6.5 6.6 6.0 6.1 5.6 5.6 4.9 5.0
Supply Air DB 53.6 67.3 53.9 69.5 54.3 71.6 54.6 73.8 55.0 75.9 55.5 78.1 56.0 80.4 56.6 82.6 57.2 84.8
Supply Air WB 52.5 56.7 52.8 57.7 53.0 58.7 53.3 59.7 53.7 60.7 54.1 61.8 54.5 62.8 55.0 63.8 55.5 64.9
Suction PSIG4 125 119 126 120 127 122 129 124 130 126 131 127 133 129 134 131 135 133
Discharge PSIG4 273 240 292 254 312 268 334 283 356 299 380 315 404 332 430 349 457 367
75/65.5 (60% RH) Total Cooling Btuh 28,300 15,000 27,700 13,200 27,100 12,000 26,300 9,600 25,500 7,700 24,700 5,700 23,800 3,700 22,800 1,600 21,700
Sensible Btuh 17,700 4,500 17,400 3,100 17,700 2,100 16,800 200 16,400 (1,200) 16,000 (2,700) 15,600 (4,200) 15,100 (5,700) 14,700 (7,200)
S/T 0.625 0.300 0.628 0.235 0.653 0.175 0.639 0.021 0.643 0 0.648 0 0.655 0 0.662 0 0.677 0
Latent Btuh 10,600 10,500 10,300 10,100 9,400 9,900 9,500 9,400 9,100 8,900 8,700 8,400 8,200 7,900 7,700 7,300 7,000 6,700
Lbs. H20/hr. 10.0 9.9 9.7 9.5 8.9 9.3 9.0 8.9 8.6 8.4 8.2 7.9 7.7 7.5 7.3 6.9 6.6 6.3
Supply Air DB 54.8 68.2 55.1 70.4 55.4 72.0 55.8 74.7 56.2 76.8 56.7 79.0 57.2 81.3 57.7 83.5 58.3 85.7
Supply Air WB 53.9 57.8 54.2 58.8 54.4 59.3 54.7 60.8 55.1 61.8 55.5 62.9 55.9 63.9 56.4 64.9 56.9 66.0
Suction PSIG4 128 121 129 123 129 124 131 126 133 128 134 130 135 132 137 134 138 135
Discharge PSIG4 274 241 293 255 309 265 334 284 356 299 380 316 405 332 431 350 458 368
75/66.7 (65% RH) Total Cooling Btuh 29,100 15,800 28,500 14,100 27,900 12,800 27,100 10,400 26,300 8,500 25,500 6,600 24,500 4,500 23,600 2,500 22,500 400
Sensible Btuh 16,700 3,900 16,400 2,500 16,700 1,500 15,800 (400) 15,400 (1,800) 15,000 (3,300) 14,600 (4,800) 14,100 (6,300) 13,700 (7,800)
S/T 0.574 0.25 0.575 0.18 0.599 0.12 0.583 0 0.586 0 0.588 0 0.596 0 0.597 0 0.609 0
Latent Btuh 12,400 11,900 12,100 11,600 11,200 11,300 11,300 10,800 10,900 10,300 10,500 9,900 9,900 9,300 9,500 8,800 8,800 8,200
Lbs. H20/hr. 11.7 11.2 11.4 10.9 10.6 10.7 10.7 10.2 10.3 9.7 9.9 9.3 9.3 8.8 9.0 8.3 8.3 7.7
Supply Air DB 56.0 69.1 56.3 71.3 56.6 72.8 57.0 75.6 57.4 77.7 57.8 79.9 58.3 82.1 58.9 84.4 59.5 86.6
Supply Air WB 55.3 58.9 55.6 59.9 55.8 60.4 56.1 61.9 56.5 63.0 56.9 64.0 57.3 65.0 57.8 66.1 58.3 67.1
Suction PSIG4 131 124 132 126 132 127 134 129 135 131 137 133 138 134 140 136 141 138
Discharge PSIG4 274 242 293 256 309 265 334 285 357 300 380 316 405 333 431 351 458 369
75/68 (70% RH) Total Cooling Btuh 29,800 16,700 29,300 14,900 28,700 13,700 27,900 11,300 27,100 9,400 26,200 7,400 25,300 5,400 24,300 3,300 23,300 1,200
Sensible Btuh 15,700 3,300 15,400 1,900 15,700 900 14,800 (1,000) 14,400 (2,400) 14,000 (3,900) 13,600 (5,400) 13,200 (6,900) 12,700 (8,400)
S/T 0.527 0.198 0.526 0.128 0.547 0.066 0.530 0 0.531 0 0.534 0 0.538 0 0.543 0 0.545 0
Latent Btuh 14,100 13,400 13,900 13,000 13,000 12,800 13,100 12,300 12,700 11,800 12,200 11,300 11,700 10,800 11,100 10,200 10,600 9,600
Lbs. H20/hr. 13.3 12.6 13.1 12.3 12.3 12.1 12.4 11.6 12.0 11.1 11.5 10.7 11.0 10.2 10.5 9.6 10.0 9.1
Supply Air DB 57.1 70.0 57.4 72.2 57.7 73.7 58.1 76.5 58.5 78.6 59.0 80.8 59.5 83.0 60.1 85.3 60.7 87.5
Supply Air WB 56.8 60.0 57.0 61.0 57.2 61.5 57.6 63.0 57.9 64.1 58.3 65.1 58.7 66.1 59.2 67.2 59.7 68.2
Suction PSIG4 134 126 135 128 135 130 137 132 138 133 140 135 141 137 142 139 144 141
Discharge PSIG4 274 243 293 256 309 266 334 285 357 301 380 317 405 334 431 352 458 370
80/68.3 (55% RH) Total Cooling Btuh 30,000 16,700 29,400 15,000 28,800 13,700 28,100 11,300 27,300 9,400 26,400 7,400 25,500 5,400 24,500 3,400 23,500 1,200
Sensible Btuh 19,000 5,900 18,700 4,500 18,900 3,500 18,000 1,600 17,600 200 17,200 (1,300) 16,800 (2,800) 16,400 (4,300) 15,900 (5,800)
S/T 0.633 0.35 0.636 0.30 0.656 0.26 0.641 0.14 0.645 0.02 0.652 0 0.659 0 0.669 0 0.677 0
Latent Btuh 11,000 10,800 10,700 10,500 9,900 10,200 10,100 9,700 9,700 9,200 9,200 8,700 8,700 8,200 8,100 7,700 7,600 7,000
Lbs. H20/hr. 10.4 10.2 10.1 9.9 9.3 9.6 9.5 9.2 9.2 8.7 8.7 8.2 8.2 7.7 7.6 7.3 7.2 6.6
Supply Air DB 58.0 71.0 58.2 73.2 58.6 74.7 58.9 77.5 59.4 79.6 59.8 81.8 60.3 84.0 60.9 86.3 61.5 88.5
Supply Air WB 56.8 60.2 57.0 61.2 57.2 61.7 57.6 63.3 57.9 64.3 58.3 65.3 58.7 66.4 59.2 67.4 59.7 68.5
Suction PSIG4 136 127 137 129 137 131 139 133 140 134 141 136 143 138 144 140 146 142
Discharge PSIG4 278 247 297 260 313 270 338 289 360 305 384 321 409 338 435 356 462 374
  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W30G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 31,800 15,400 30,800 13,400 29,900 10,900 29,000 9,200 28,100 7,100 27,100 4,900 26,200 2,600 25,200 300 24,200
Sensible Btuh 22,800 6,500 22,300 4,800 21,800 3,300 21,300 1,600 20,800 (100) 20,300 (1,700) 19,800 (3,300) 19,400 (4,900) 18,900 (6,500)
S/T 0.717 0.422 0.724 0.358 0.729 0.303 0.734 0.174 0.740 0 0.749 0 0.756 0 0.770 0 0.781 0
Latent Btuh 9,000 8,900 8,500 8,600 8,100 7,600 7,700 7,600 7,300 7,200 6,800 6,600 6,400 5,900 5,800 5,200 5,300 4,500
Lbs. H20/hr. 8.5 8.4 8.0 8.1 7.6 7.2 7.3 7.2 6.9 6.8 6.4 6.2 6.0 5.6 5.5 4.9 5.0 4.2
Supply Air DB 52.2 66.6 52.7 68.7 53.2 70.8 53.7 73.0 54.2 75.1 54.7 77.2 55.2 79.3 55.6 81.4 56.1 83.5
Supply Air WB 50.5 55.4 50.9 56.4 51.1 57.4 51.7 58.4 52.0 59.5 52.4 60.5 52.8 61.5 53.2 62.5 53.6 63.6
Suction PSIG4 123 115 124 116 124 118 125 119 127 121 128 123 129 125 130 127 132 130
Discharge PSIG4 264 238 283 251 307 265 324 280 346 296 370 312 394 329 420 347 447 366
75/64.1 (55% RH) Total Cooling Btuh 32,600 16,500 31,700 14,400 30,800 12,400 29,900 10,200 28,900 8,100 28,000 5,900 27,000 3,600 26,000 1,400 25,100
Sensible Btuh 21,700 5,800 21,200 4,100 20,700 2,500 20,200 900 19,700 (700) 19,200 (2,400) 18,700 (4,000) 18,200 (5,600) 17,800 (7,100)
S/T 0.666 0.35 0.669 0.28 0.672 0.20 0.676 0.09 0.682 0 0.686 0 0.693 0 0.700 0 0.709 0
Latent Btuh 10,900 10,700 10,500 10,300 10,100 9,900 9,700 9,300 9,200 8,800 8,800 8,300 8,300 7,600 7,800 7,000 7,300 6,100
Lbs. H20/hr. 10.3 10.1 9.9 9.7 9.5 9.3 9.2 8.8 8.7 8.3 8.3 7.8 7.8 7.2 7.4 6.6 6.9 5.8
Supply Air DB 53.2 67.4 53.8 69.6 54.3 71.7 54.8 73.9 55.3 76.0 55.8 78.1 56.2 80.2 56.7 82.3 57.1 84.3
Supply Air WB 51.9 56.4 52.2 57.5 52.6 58.5 53.0 59.5 53.4 60.5 53.8 61.5 54.1 62.6 54.5 63.6 54.9 64.6
Suction PSIG4 126 118 127 119 128 121 129 122 130 124 131 126 132 128 134 131 135 133
Discharge PSIG4 266 241 284 254 304 268 326 283 348 299 372 315 396 332 422 350 449 368
75/65.5 (60% RH) Total Cooling Btuh 33,500 17,500 32,600 15,500 31,600 13,000 30,700 11,300 29,800 9,100 28,800 6,900 27,900 4,700 26,900 2,400 25,900 100
Sensible Btuh 20,600 5,100 20,100 3,500 19,600 1,900 19,100 200 18,600 (1,400) 18,100 (3,000) 17,600 (4,600) 17,100 (6,200) 16,600 (7,800)
S/T 0.615 0.291 0.617 0.226 0.620 0.146 0.622 0.018 0.624 0 0.628 0 0.631 0 0.636 0 0.641 0
Latent Btuh 12,900 12,400 12,500 12,000 12,000 11,100 11,600 11,100 11,200 10,500 10,700 9,900 10,300 9,300 9,800 8,600 9,300 7,900
Lbs. H20/hr. 12.2 11.7 11.8 11.3 11.3 10.5 10.9 10.5 10.6 9.9 10.1 9.3 9.7 8.8 9.2 8.1 8.8 7.5
Supply Air DB 54.3 68.3 54.8 70.5 55.3 72.5 55.9 74.7 56.3 76.9 56.8 79.0 57.3 81.1 57.8 83.1 58.2 85.2
Supply Air WB 53.2 57.5 53.6 58.5 53.8 59.5 54.3 60.6 54.7 61.6 55.1 62.6 55.5 63.6 55.9 64.7 56.2 65.7
Suction PSIG4 129 122 130 123 131 124 132 126 133 128 134 130 136 132 137 134 138 136
Discharge PSIG4 267 244 286 257 310 271 327 286 350 301 373 318 398 335 424 353 451 371
75/66.7 (65% RH) Total Cooling Btuh 34,300 18,500 33,400 16,500 32,500 14,000 31,600 12,300 30,600 10,200 29,700 8,000 28,700 5,700 27,800 3,400 26,800 1,100
Sensible Btuh 19,400 4,400 19,000 2,800 18,500 1,200 18,000 (500) 17,500 (2,100) 17,000 (3,700) 16,500 (5,300) 16,000 (6,900) 15,500 (8,500)
S/T 0.566 0.24 0.569 0.17 0.569 0.09 0.570 0 0.572 0 0.572 0 0.575 0 0.576 0 0.578 0
Latent Btuh 14,900 14,100 14,400 13,700 14,000 12,800 13,600 12,800 13,100 12,300 12,700 11,700 12,200 11,000 11,800 10,300 11,300 9,600
Lbs. H20/hr. 14.1 13.3 13.6 12.9 13.2 12.1 12.8 12.1 12.4 11.6 12.0 11.0 11.5 10.4 11.1 9.7 10.7 9.1
Supply Air DB 55.4 69.2 55.9 71.3 56.4 73.4 56.9 75.6 57.4 77.7 57.9 79.8 58.4 81.9 58.8 84.0 59.3 86.1
Supply Air WB 54.5 58.6 54.9 59.6 55.1 60.6 55.7 61.6 56.1 62.6 56.4 63.7 56.8 64.7 57.2 65.7 57.6 66.7
Suction PSIG4 133 125 134 126 134 128 135 129 137 131 138 133 139 135 140 137 142 140
Discharge PSIG4 269 246 288 260 312 274 329 289 351 304 375 321 400 338 425 356 452 374
75/68 (70% RH) Total Cooling Btuh 35,200 19,600 34,300 17,500 33,300 15,100 32,400 13,300 31,500 11,200 30,500 9,000 29,600 6,700 28,600 4,500 27,600 2,100
Sensible Btuh 18,300 3,700 17,900 2,100 17,300 500 16,900 (1,200) 16,400 (2,800) 15,900 (4,400) 15,400 (6,000) 14,900 (7,600) 14,400 (9,200)
S/T 0.520 0.189 0.522 0.120 0.520 0.033 0.522 0 0.521 0 0.521 0 0.520 0 0.521 0 0.522 0
Latent Btuh 16,900 15,900 16,400 15,400 16,000 14,600 15,500 14,500 15,100 14,000 14,600 13,400 14,200 12,700 13,700 12,100 13,200 11,300
Lbs. H20/hr. 15.9 15.0 15.5 14.5 15.1 13.8 14.6 13.7 14.2 13.2 13.8 12.6 13.4 12.0 12.9 11.4 12.5 10.7
Supply Air DB 56.4 70.0 57.0 72.2 57.5 74.2 58.0 76.5 58.5 78.6 59.0 80.7 59.4 82.8 59.9 84.9 60.3 86.9
Supply Air WB 55.9 59.6 56.2 60.6 56.4 61.7 57.0 62.7 57.4 63.7 57.8 64.7 58.2 65.7 58.5 66.8 58.9 67.8
Suction PSIG4 136 129 137 130 138 131 139 133 140 134 141 136 142 139 144 141 145 143
Discharge PSIG4 271 249 289 263 313 276 331 292 353 307 377 323 401 341 427 358 454 377
80/68.3 (55% RH) Total Cooling Btuh 35,300 20,100 34,400 18,100 33,500 15,600 32,600 13,900 31,700 11,700 30,700 9,500 29,700 7,300 28,800 5,000 27,800 2,700
Sensible Btuh 22,500 7,100 22,000 5,400 21,500 3,900 21,100 2,100 20,600 500 20,100 (1,100) 19,600 (2,700) 19,100 (4,300) 18,600 (5,900)
S/T 0.637 0.35 0.640 0.30 0.642 0.25 0.647 0.15 0.650 0.04 0.655 0 0.660 0 0.663 0 0.669 0
Latent Btuh 12,800 13,000 12,400 12,700 12,000 11,700 11,500 11,800 11,100 11,200 10,600 10,600 10,100 10,000 9,700 9,300 9,200 8,600
Lbs. H20/hr. 12.1 12.3 11.7 12.0 11.3 11.0 10.8 11.1 10.5 10.6 10.0 10.0 9.5 9.4 9.2 8.8 8.7 8.1
Supply Air DB 57.3 70.6 57.8 72.8 58.3 74.8 58.8 77.1 59.3 79.2 59.8 81.3 60.2 83.4 60.7 85.5 61.2 87.5
Supply Air WB 56.3 59.7 56.6 60.7 56.8 61.7 57.4 62.7 57.8 63.7 58.2 64.8 58.6 65.8 58.9 66.8 59.3 67.8
Suction PSIG4 138 129 138 130 139 132 140 133 141 135 143 137 144 139 145 141 146 144
Discharge PSIG4 269 250 288 263 312 277 329 292 351 308 375 324 400 341 425 359 452 378
  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W36G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 38,500 18,300 37,400 16,100 36,400 13,700 35,200 11,400 34,000 9,000 32,900 6,600 31,800 4,100 30,600 1,600 29,500
Sensible Btuh 28,700 8,200 28,300 6,500 27,800 4,900 27,200 3,100 26,700 1,400 26,100 (400) 25,600 (2,100) 25,000 (3,900) 24,400 (5,700)
S/T 0.745 0.448 0.757 0.404 0.764 0.358 0.773 0.272 0.785 0.156 0.793 0 0.805 0 0.817 0 0.827 0
Latent Btuh 9,800 10,100 9,100 9,600 8,600 8,800 8,000 8,300 7,300 7,600 6,800 7,000 6,200 6,200 5,600 5,500 5,100 4,700
Lbs. H20/hr. 9.2 9.5 8.6 9.1 8.1 8.3 7.5 7.8 6.9 7.2 6.4 6.6 5.8 5.8 5.3 5.2 4.8 4.4
Supply Air DB 51.4 66.0 51.9 67.9 52.4 69.8 52.9 71.8 53.3 73.7 53.8 75.7 54.3 77.7 54.7 79.7 55.1 81.7
Supply Air WB 50.3 55.0 50.8 56.0 51.2 56.9 51.7 58.0 52.1 59.0 52.5 60.1 52.9 61.1 53.2 62.1 53.6 63.1
Suction PSIG4 123 114 124 115 124 116 126 117 127 118 128 120 129 121 130 123 132 125
Discharge PSIG4 287 251 307 265 328 279 350 294 373 310 396 326 421 342 447 359 474 377
75/64.1 (55% RH) Total Cooling Btuh 39,500 19,500 38,400 17,200 37,200 14,900 36,100 12,600 35,000 10,200 33,800 7,700 32,700 5,200 31,600 2,700 30,400 100
Sensible Btuh 27,300 7,300 26,800 5,600 26,300 3,900 25,700 2,200 25,200 500 24,600 (1,200) 24,100 (3,000) 23,500 (4,800) 22,900 (6,600)
S/T 0.691 0.37 0.698 0.33 0.707 0.26 0.712 0.17 0.720 0.05 0.728 0 0.737 0 0.744 0 0.753 0
Latent Btuh 12,200 12,200 11,600 11,600 10,900 11,000 10,400 10,400 9,800 9,700 9,200 8,900 8,600 8,200 8,100 7,500 7,500 6,700
Lbs. H20/hr. 11.5 11.5 10.9 10.9 10.3 10.4 9.8 9.8 9.2 9.2 8.7 8.4 8.1 7.7 7.6 7.1 7.1 6.3
Supply Air DB 52.6 67.1 53.1 69.0 53.6 70.9 54.1 72.9 54.5 74.8 55.0 76.8 55.5 78.8 55.9 80.8 56.4 82.7
Supply Air WB 51.7 56.1 52.2 57.1 52.6 58.1 53.0 59.1 53.4 60.1 53.8 61.1 54.2 62.1 54.6 63.1 54.9 64.1
Suction PSIG4 126 118 126 118 127 119 128 120 130 121 131 123 132 124 133 126 135 128
Discharge PSIG4 289 254 309 268 330 282 352 297 374 313 398 329 423 345 449 362 476 380
75/65.5 (60% RH) Total Cooling Btuh 40,400 20,700 39,300 18,400 38,300 16,000 37,100 13,700 35,900 11,300 34,800 8,900 33,700 6,400 32,500 3,900 31,400 1,300
Sensible Btuh 25,800 6,400 25,300 4,700 24,800 3,100 24,300 1,300 23,700 (400) 23,200 (2,100) 22,600 (3,900) 22,000 (5,700) 21,400 (7,400)
S/T 0.639 0.309 0.644 0.255 0.648 0.194 0.655 0.095 0.660 0 0.667 0 0.671 0 0.677 0 0.682 0
Latent Btuh 14,600 14,300 14,000 13,700 13,500 12,900 12,800 12,400 12,200 11,700 11,600 11,000 11,100 10,300 10,500 9,600 10,000 8,700
Lbs. H20/hr. 13.8 13.5 13.2 12.9 12.7 12.2 12.1 11.7 11.5 11.0 10.9 10.4 10.5 9.7 9.9 9.1 9.4 8.2
Supply Air DB 53.8 68.2 54.3 70.1 54.8 71.9 55.3 74.0 55.8 75.9 56.2 77.9 56.7 79.8 57.1 81.8 57.6 83.8
Supply Air WB 53.1 57.1 53.5 58.2 53.9 59.1 54.4 60.2 54.8 61.2 55.2 62.2 55.6 63.2 55.9 64.2 56.3 65.2
Suction PSIG4 128 121 129 121 130 122 131 123 132 125 134 126 135 128 136 129 137 131
Discharge PSIG4 291 257 311 271 331 285 353 300 376 316 400 332 425 348 451 365 478 383
75/66.7 (65% RH) Total Cooling Btuh 41,400 21,800 40,300 19,600 39,200 17,200 38,000 14,900 36,900 12,500 35,700 10,100 34,600 7,600 33,500 5,000 32,300 2,500
Sensible Btuh 24,300 5,500 23,800 3,900 23,400 2,200 22,800 500 22,200 (1,300) 21,700 (3,000) 21,100 (4,800) 20,500 (6,500) 19,900 (8,300)
S/T 0.587 0.25 0.591 0.20 0.597 0.13 0.600 0.03 0.602 0 0.608 0 0.610 0 0.612 0 0.616 0
Latent Btuh 17,100 16,300 16,500 15,700 15,800 15,000 15,200 14,400 14,700 13,800 14,000 13,100 13,500 12,400 13,000 11,500 12,400 10,800
Lbs. H20/hr. 16.1 15.4 15.6 14.8 14.9 14.2 14.3 13.6 13.9 13.0 13.2 12.4 12.7 11.7 12.3 10.8 11.7 10.2
Supply Air DB 55.0 69.2 55.5 71.2 56.0 73.0 56.5 75.0 57.0 77.0 57.4 78.9 57.9 80.9 58.4 82.9 58.8 84.9
Supply Air WB 54.4 58.2 54.9 59.2 55.3 60.1 55.7 61.3 56.1 62.3 56.5 63.3 56.9 64.3 57.3 65.3 57.6 66.3
Suction PSIG4 131 124 132 125 133 125 134 126 135 128 136 129 138 131 139 132 140 134
Discharge PSIG4 293 260 313 274 333 288 355 303 378 319 402 335 427 351 453 368 480 386
75/68 (70% RH) Total Cooling Btuh 42,300 23,000 41,200 20,700 40,200 18,300 39,000 16,100 37,800 13,700 36,700 11,200 35,600 8,700 34,400 6,200 33,300 3,600
Sensible Btuh 22,800 4,700 22,300 3,000 21,900 1,400 21,300 (400) 20,800 (2,100) 20,200 (3,900) 19,600 (5,600) 19,000 (7,400) 18,500 (9,200)
S/T 0.539 0.204 0.541 0.145 0.545 0.077 0.546 0 0.550 0 0.550 0 0.551 0 0.552 0 0.556 0
Latent Btuh 19,500 18,300 18,900 17,700 18,300 16,900 17,700 16,500 17,000 15,800 16,500 15,100 16,000 14,300 15,400 13,600 14,800 12,800
Lbs. H20/hr. 18.4 17.3 17.8 16.7 17.3 15.9 16.7 15.6 16.0 14.9 15.6 14.2 15.1 13.5 14.5 12.8 14.0 12.1
Supply Air DB 56.3 70.3 56.8 72.2 57.2 74.1 57.7 76.1 58.2 78.1 58.7 80.0 59.1 82.0 59.6 84.0 60.0 86.0
Supply Air WB 55.8 59.3 56.2 60.3 56.7 61.2 57.1 62.3 57.5 63.4 57.9 64.4 58.3 65.4 58.6 66.4 59.0 67.4
Suction PSIG4 134 127 135 128 136 128 137 130 138 131 139 132 141 134 142 136 143 138
Discharge PSIG4 295 263 314 277 335 291 357 306 380 322 404 338 429 354 455 371 482 389
80/68.3 (55% RH) Total Cooling Btuh 42,700 23,200 41,600 21,000 40,500 18,500 39,300 16,300 38,200 13,900 37,000 11,400 35,900 9,000 34,800 6,400 33,600 3,800
Sensible Btuh 28,100 8,600 27,600 6,900 27,200 5,300 26,600 3,500 26,100 1,800 25,500 24,900 (1,700) 24,400 (3,500) 23,800 (5,300)
S/T 0.658 0.37 0.663 0.33 0.672 0.29 0.677 0.21 0.683 0.13 0.689 0.00 0.694 0 0.701 0 0.708 0
Latent Btuh 14,600 14,600 14,000 14,100 13,300 13,200 12,700 12,800 12,100 12,100 11,500 11,400 11,000 10,700 10,400 9,900 9,800 9,100
Lbs. H20/hr. 13.8 13.8 13.2 13.3 12.5 12.5 12.0 12.1 11.4 11.4 10.8 10.8 10.4 10.1 9.8 9.3 9.2 8.6
Supply Air DB 56.6 70.7 57.1 72.6 57.6 74.4 58.1 76.5 58.5 78.4 59.0 80.4 59.5 82.3 59.9 84.3 60.4 86.3
Supply Air WB 55.7 59.4 56.2 60.4 56.6 61.3 57.0 62.4 57.5 63.4 57.9 64.4 58.2 65.4 58.6 66.4 59.0 67.4
Suction PSIG4 137 128 137 129 138 130 139 131 141 132 142 133 143 135 144 137 146 139
Discharge PSIG4 294 263 314 276 335 290 357 306 379 321 403 337 428 354 454 371 481 389
  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W42G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 43,800 21,200 43,400 18,300 42,800 15,400 41,900 12,400 40,800 9,500 39,600 6,600 38,100 3,700 36,400 800 34,500
Sensible Btuh 32,800 9,300 32,600 7,000 32,400 4,800 31,800 2,400 31,300 200 30,600 (1,900) 29,900 (3,900) 29,000 (5,900) 28,000 (7,700)
S/T 0.749 0.439 0.751 0.383 0.757 0.312 0.759 0.194 0.767 0.021 0.773 0 0.785 0 0.797 0 0.812 0
Latent Btuh 11,000 11,900 10,800 11,300 10,400 10,600 10,100 10,000 9,500 9,300 9,000 8,500 8,200 7,600 7,400 6,700 6,500 5,600
Lbs. H20/hr. 10.4 11.2 10.2 10.7 9.8 10.0 9.5 9.4 9.0 8.8 8.5 8.0 7.7 7.2 7.0 6.3 6.1 5.3
Supply Air DB 51.8 67.0 52.2 68.9 52.7 70.8 53.2 72.9 53.7 74.9 54.3 76.9 54.8 79.0 55.3 81.1 55.9 83.2
Supply Air WB 50.6 55.7 50.9 56.8 51.2 57.7 51.6 58.7 52.0 59.7 52.4 60.6 52.8 61.6 53.2 62.5 53.7 63.4
Suction PSIG4 124 116 126 118 126 119 128 121 129 122 130 122 131 123 131 123 132 123
Discharge PSIG4 282 249 300 263 319 277 340 291 363 307 387 323 413 339 441 356 471 374
75/64.1 (55% RH) Total Cooling Btuh 44,800 22,600 44,400 19,600 43,800 16,700 43,000 13,800 41,900 10,900 40,600 7,900 39,200 5,000 37,400 2,100 35,500
Sensible Btuh 31,200 8,400 31,000 6,000 30,600 3,700 30,200 1,400 29,600 (700) 29,000 (2,800) 28,200 (4,900) 27,300 (6,800) 26,400 (8,700)
S/T 0.696 0.37 0.698 0.31 0.699 0.22 0.702 0.10 0.706 0 0.714 0 0.719 0 0.730 0 0.744 0
Latent Btuh 13,600 14,200 13,400 13,600 13,200 13,000 12,800 12,400 12,300 11,600 11,600 10,700 11,000 9,900 10,100 8,900 9,100 7,900
Lbs. H20/hr. 12.8 13.4 12.6 12.8 12.5 12.3 12.1 11.7 11.6 10.9 10.9 10.1 10.4 9.3 9.5 8.4 8.6 7.5
Supply Air DB 52.9 68.0 53.4 69.9 53.9 71.8 54.4 73.8 54.9 75.8 55.4 77.8 56.0 79.9 56.5 82.0 57.0 84.1
Supply Air WB 52.0 56.8 52.3 57.8 52.7 58.8 53.0 59.8 53.4 60.8 53.8 61.7 54.2 62.7 54.6 63.6 55.1 64.5
Suction PSIG4 127 119 129 121 130 123 131 124 132 125 133 126 134 126 134 126 135 126
Discharge PSIG4 284 253 302 266 321 280 342 295 365 310 389 326 415 342 443 359 472 377
75/65.5 (60% RH) Total Cooling Btuh 45,900 23,900 45,500 21,000 44,900 18,100 44,000 15,100 43,000 12,200 41,700 9,300 40,200 6,400 38,500 3,500 36,600 600
Sensible Btuh 29,500 7,400 29,300 5,000 29,100 2,900 28,500 500 28,000 (1,700) 27,300 (3,800) 26,600 (5,800) 25,700 (7,800) 24,700 (9,700)
S/T 0.643 0.310 0.644 0.238 0.648 0.160 0.648 0.033 0.651 0 0.655 0 0.662 0 0.668 0 0.675 0
Latent Btuh 16,400 16,500 16,200 16,000 15,800 15,200 15,500 14,600 15,000 13,900 14,400 13,100 13,600 12,200 12,800 11,300 11,900 10,300
Lbs. H20/hr. 15.5 15.6 15.3 15.1 14.9 14.3 14.6 13.8 14.2 13.1 13.6 12.4 12.8 11.5 12.1 10.7 11.2 9.7
Supply Air DB 54.1 68.9 54.6 70.8 55.1 72.6 55.6 74.7 56.1 76.8 56.6 78.8 57.1 80.8 57.7 82.9 58.2 85.0
Supply Air WB 53.4 57.9 53.7 58.9 54.0 59.9 54.4 60.9 54.8 61.9 55.2 62.8 55.6 63.7 56.0 64.6 56.5 65.5
Suction PSIG4 130 123 132 124 132 125 134 127 135 128 136 129 137 129 137 129 138 129
Discharge PSIG4 286 256 303 269 322 283 344 298 366 313 391 329 417 345 444 362 474 380
75/66.7 (65% RH) Total Cooling Btuh 47,000 25,300 46,600 22,400 46,000 19,400 45,100 16,500 44,000 13,600 42,800 10,700 41,300 7,700 39,600 4,800 37,700 1,900
Sensible Btuh 27,800 6,400 27,600 4,100 27,400 1,900 26,800 (500) 26,300 (2,700) 25,600 (4,800) 24,900 (6,800) 24,000 (8,800) 23,000 (10,600)
S/T 0.591 0.25 0.592 0.18 0.596 0.10 0.594 0 0.598 0 0.598 0 0.603 0 0.606 0 0.610 0
Latent Btuh 19,200 18,900 19,000 18,300 18,600 17,500 18,300 17,000 17,700 16,300 17,200 15,500 16,400 14,500 15,600 13,600 14,700 12,500
Lbs. H20/hr. 18.1 17.8 17.9 17.3 17.5 16.5 17.3 16.0 16.7 15.4 16.2 14.6 15.5 13.7 14.7 12.8 13.9 11.8
Supply Air DB 55.3 69.8 55.8 71.7 56.3 73.6 56.8 75.7 57.3 77.7 57.8 79.7 58.3 81.8 58.8 83.9 59.4 86.0
Supply Air WB 54.8 59.0 55.1 60.0 55.4 61.0 55.8 62.0 56.2 62.9 56.6 63.9 57.0 64.8 57.4 65.7 57.9 66.6
Suction PSIG4 133 126 135 127 135 128 137 130 138 131 139 132 140 132 141 132 141 132
Discharge PSIG4 287 259 305 272 324 286 345 301 368 316 392 332 418 348 446 365 476 383
75/68 (70% RH) Total Cooling Btuh 48,000 26,600 47,600 23,700 47,000 20,800 46,200 17,900 45,100 14,900 43,800 12,000 42,400 9,100 40,600 6,200 38,700 3,300
Sensible Btuh 26,200 5,500 26,000 3,100 25,800 1,000 25,200 (1,500) 24,600 (3,600) 24,000 (5,700) 23,200 (7,800) 22,300 (9,700) 21,400 (11,600)
S/T 0.546 0.207 0.546 0.131 0.549 0.048 0.545 0 0.545 0 0.548 0 0.547 0 0.549 0 0.553 0
Latent Btuh 21,800 21,100 21,600 20,600 21,200 19,800 21,000 19,400 20,500 18,500 19,800 17,700 19,200 16,900 18,300 15,900 17,300 14,900
Lbs. H20/hr. 20.6 19.9 20.4 19.4 20.0 18.7 19.8 18.3 19.3 17.5 18.7 16.7 18.1 15.9 17.3 15.0 16.3 14.1
Supply Air DB 56.5 70.8 56.9 72.7 57.4 74.5 57.9 76.6 58.4 78.6 59.0 80.7 59.5 82.7 60.0 84.8 60.6 86.9
Supply Air WB 56.2 60.1 56.5 61.1 56.8 62.1 57.2 63.1 57.6 64.0 58.0 65.0 58.4 65.9 58.8 66.8 59.3 67.7
Suction PSIG4 136 129 138 131 138 131 140 133 141 134 142 135 143 135 144 136 144 136
Discharge PSIG4 289 262 306 275 325 289 347 304 369 319 394 335 420 351 448 368 477 386
80/68.3 (55% RH) Total Cooling Btuh 48,500 27,200 48,100 24,200 47,500 21,300 46,700 18,400 45,600 15,400 44,400 12,500 42,900 9,600 41,200 6,700 39,200 3,800
Sensible Btuh 32,300 10,200 32,100 7,900 31,900 5,700 31,300 3,300 30,800 1,100 30,100 (1,000) 29,300 (3,000) 28,500 (5,000) 27,500 (6,800)
S/T 0.666 0.38 0.667 0.33 0.672 0.27 0.670 0.18 0.675 0.07 0.678 0 0.683 0 0.692 0 0.702 0
Latent Btuh 16,200 17,000 16,000 16,300 15,600 15,600 15,400 15,100 14,800 14,300 14,300 13,500 13,600 12,600 12,700 11,700 11,700 10,600
Lbs. H20/hr. 15.3 16.0 15.1 15.4 14.7 14.7 14.5 14.2 14.0 13.5 13.5 12.7 12.8 11.9 12.0 11.0 11.0 10.0
Supply Air DB 57.2 71.6 57.6 73.5 58.1 75.3 58.6 77.4 59.1 79.4 59.7 81.4 60.2 83.5 60.7 85.6 61.2 87.7
Supply Air WB 56.2 60.0 56.5 61.0 56.8 62.0 57.2 63.0 57.6 64.0 58.0 64.9 58.4 65.9 58.8 66.8 59.3 67.7
Suction PSIG4 139 129 140 131 140 132 143 134 144 135 145 135 145 136 146 136 146 136
Discharge PSIG4 287 261 304 274 323 288 345 303 367 318 392 334 418 350 446 368 475 385
  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W48G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 51,700 24,800 50,300 21,800 48,900 18,700 47,500 15,500 46,000 12,200 44,600 8,900 43,100 5,400 41,600 1,900 40,200
Sensible Btuh 38,600 11,500 38,100 9,100 37,300 6,800 36,900 4,400 36,300 2,000 35,700 (400) 35,000 (2,800) 34,300 (5,200) 33,600 (7,700)
S/T 0.747 0.464 0.757 0.417 0.763 0.364 0.777 0.284 0.789 0.164 0.800 0 0.812 0 0.825 0 0.836 0
Latent Btuh 13,100 13,300 12,200 12,700 11,600 11,900 10,600 11,100 9,700 10,200 8,900 9,300 8,100 8,200 7,300 7,100 6,600 5,900
Lbs. H20/hr. 12.4 12.5 11.5 12.0 10.9 11.2 10.0 10.5 9.2 9.6 8.4 8.8 7.6 7.7 6.9 6.7 6.2 5.6
Supply Air DB 51.8 66.0 52.3 67.9 52.5 69.7 53.2 71.7 53.6 73.6 54.0 75.5 54.4 77.5 54.8 79.4 55.2 81.4
Supply Air WB 50.7 55.3 51.1 56.3 51.3 57.2 51.9 58.2 52.3 59.2 52.6 60.2 53.0 61.2 53.3 62.2 53.7 63.2
Suction PSIG4 119 109 120 110 120 112 121 113 122 115 123 116 124 118 126 119 127 121
Discharge PSIG4 282 252 301 265 325 279 343 294 366 309 390 324 415 340 442 357 470 375
75/64.1 (55% RH) Total Cooling Btuh 52,900 26,300 51,600 23,300 50,200 20,200 48,700 17,000 47,300 13,700 45,900 10,400 44,400 6,900 42,900 3,400 41,400
Sensible Btuh 36,600 10,300 36,000 8,000 35,500 5,600 34,900 3,300 34,200 900 33,600 (1,500) 32,900 (4,000) 32,200 (6,400) 31,500 (8,900)
S/T 0.692 0.39 0.698 0.34 0.707 0.28 0.717 0.19 0.723 0.07 0.732 0 0.741 0 0.751 0 0.761 0
Latent Btuh 16,300 16,000 15,600 15,300 14,700 14,600 13,800 13,700 13,100 12,800 12,300 11,900 11,500 10,900 10,700 9,800 9,900 8,600
Lbs. H20/hr. 15.4 15.1 14.7 14.4 13.9 13.8 13.0 12.9 12.4 12.1 11.6 11.2 10.8 10.3 10.1 9.2 9.3 8.1
Supply Air DB 53.1 67.0 53.5 68.9 54.0 70.8 54.4 72.7 54.8 74.6 55.2 76.6 55.6 78.5 56.0 80.5 56.4 82.4
Supply Air WB 52.1 56.4 52.5 57.4 52.9 58.3 53.3 59.3 53.6 60.3 54.0 61.3 54.4 62.3 54.7 63.3 55.1 64.3
Suction PSIG4 122 112 123 113 123 115 124 116 125 117 126 119 127 120 129 122 130 123
Discharge PSIG4 284 256 303 269 324 282 345 297 368 312 392 327 417 344 444 360 472 378
75/65.5 (60% RH) Total Cooling Btuh 54,200 27,900 52,800 24,800 51,400 21,700 50,000 18,500 48,600 15,300 47,200 11,900 45,700 8,400 44,200 4,900 42,700 1,300
Sensible Btuh 34,500 9,200 34,000 6,800 33,200 4,500 32,800 2,100 32,200 (300) 31,500 (2,700) 30,900 (5,100) 30,200 (7,600) 29,400 (10,000)
S/T 0.637 0.330 0.644 0.274 0.646 0.207 0.656 0.114 0.663 0 0.667 0 0.676 0 0.683 0 0.689 0
Latent Btuh 19,700 18,700 18,800 18,000 18,200 17,200 17,200 16,400 16,400 15,600 15,700 14,600 14,800 13,500 14,000 12,500 13,300 11,300
Lbs. H20/hr. 18.6 17.6 17.7 17.0 17.2 16.2 16.2 15.5 15.5 14.7 14.8 13.8 14.0 12.7 13.2 11.8 12.5 10.7
Supply Air DB 54.3 68.0 54.8 69.9 55.0 71.8 55.6 73.7 56.0 75.7 56.5 77.6 56.9 79.5 57.3 81.5 57.7 83.4
Supply Air WB 53.5 57.5 53.9 58.5 54.0 59.4 54.6 60.4 55.0 61.4 55.4 62.4 55.7 63.4 56.1 64.4 56.4 65.4
Suction PSIG4 125 115 126 116 126 118 127 119 128 120 129 122 130 123 132 125 133 126
Discharge PSIG4 287 259 305 272 329 285 347 300 370 315 394 330 419 347 446 364 474 381
75/66.7 (65% RH) Total Cooling Btuh 55,500 29,400 54,100 26,400 52,700 23,200 51,300 20,100 49,900 16,800 48,400 13,400 47,000 10,000 45,500 6,400 44,000 2,800
Sensible Btuh 32,500 8,000 31,900 5,700 31,100 3,400 30,700 1,000 30,100 (1,400) 29,500 (3,800) 28,800 (6,300) 28,100 (8,700) 27,400 (11,200)
S/T 0.586 0.27 0.590 0.22 0.590 0.15 0.598 0.05 0.603 0 0.610 0 0.613 0 0.618 0 0.623 0
Latent Btuh 23,000 21,400 22,200 20,700 21,600 19,800 20,600 19,100 19,800 18,200 18,900 17,200 18,200 16,300 17,400 15,100 16,600 14,000
Lbs. H20/hr. 21.7 20.2 20.9 19.5 20.4 18.7 19.4 18.0 18.7 17.2 17.8 16.2 17.2 15.4 16.4 14.2 15.7 13.2
Supply Air DB 55.6 69.1 56.0 70.9 56.3 72.8 56.9 74.8 57.3 76.7 57.7 78.6 58.1 80.5 58.5 82.5 58.9 84.5
Supply Air WB 54.9 58.6 55.3 59.6 55.4 60.5 56.0 61.5 56.4 62.5 56.8 63.5 57.1 64.5 57.5 65.5 57.8 66.5
Suction PSIG4 128 118 129 119 129 121 130 122 131 123 132 124 133 126 135 128 136 129
Discharge PSIG4 289 262 307 275 331 288 349 303 372 318 396 333 421 350 448 367 476 384
75/68 (70% RH) Total Cooling Btuh 56,800 30,900 55,400 27,900 54,000 24,800 52,600 21,600 51,200 18,300 49,700 14,900 48,300 11,500 46,800 7,900 45,300 4,300
Sensible Btuh 30,400 6,900 29,900 4,500 29,100 2,200 28,700 (200) 28,100 (2,600) 27,400 (5,000) 26,700 (7,400) 26,000 (9,900) 25,300 (12,300)
S/T 0.535 0.223 0.540 0.161 0.539 0.089 0.546 0 0.549 0 0.551 0 0.553 0 0.556 0 0.558 0
Latent Btuh 26,400 24,000 25,500 23,400 24,900 22,600 23,900 21,800 23,100 20,900 22,300 19,900 21,600 18,900 20,800 17,800 20,000 16,600
Lbs. H20/hr. 24.9 22.6 24.1 22.1 23.5 21.3 22.5 20.6 21.8 19.7 21.0 18.8 20.4 17.8 19.6 16.8 18.9 15.7
Supply Air DB 56.8 70.1 57.2 72.0 57.5 73.8 58.1 75.8 58.5 77.7 58.9 79.6 59.3 81.6 59.7 83.5 60.1 85.5
Supply Air WB 56.2 59.7 56.6 60.7 56.8 61.6 57.4 62.6 57.8 63.6 58.1 64.6 58.5 65.6 58.9 66.6 59.2 67.6
Suction PSIG4 131 120 132 122 132 123 133 124 134 126 135 127 136 129 138 130 139 132
Discharge PSIG4 291 265 309 278 333 291 351 306 374 321 398 337 423 353 450 370 478 387
80/68.3 (55% RH) Total Cooling Btuh 56,900 31,200 55,600 28,200 54,200 25,100 52,700 21,900 51,300 18,600 49,900 15,300 48,400 11,800 46,900 8,300 45,400 4,600
Sensible Btuh 37,700 12,000 37,100 9,700 36,300 7,400 35,900 5,000 35,300 2,600 34,700 200 34,000 (2,300) 33,300 (4,700) 32,600 (7,200)
S/T 0.663 0.38 0.667 0.34 0.670 0.29 0.681 0.23 0.688 0.14 0.695 0.01 0.702 0 0.710 0 0.718 0
Latent Btuh 19,200 19,200 18,500 18,500 17,900 17,700 16,800 16,900 16,000 16,000 15,200 15,100 14,400 14,100 13,600 13,000 12,800 11,800
Lbs. H20/hr. 18.1 18.1 17.5 17.5 16.9 16.7 15.8 15.9 15.1 15.1 14.3 14.2 13.6 13.3 12.8 12.3 12.1 11.1
Supply Air DB 57.4 70.7 57.9 72.6 58.1 74.4 58.7 76.4 59.2 78.3 59.6 80.2 60.0 82.2 60.4 84.1 60.8 86.1
Supply Air WB 56.5 59.7 56.9 60.7 57.0 61.6 57.6 62.6 58.0 63.6 58.4 64.6 58.7 65.6 59.1 66.6 59.4 67.6
Suction PSIG4 132 121 133 122 133 124 134 125 135 126 136 128 137 129 139 131 140 132
Discharge PSIG4 286 264 305 277 328 291 347 305 369 320 393 336 419 352 445 369 473 386
  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W60G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 61,600 31,700 59,800 28,400 58,000 25,000 56,200 21,600 54,400 18,200 52,600 14,600 50,900 11,000 49,100 7,300 47,400 3,600
Sensible Btuh 45,400 14,000 44,700 11,600 44,200 9,200 43,100 6,500 42,300 3,900 41,500 1,300 40,600 (1,300) 39,800 (4,100) 39,000 (6,800)
S/T 0.737 0.442 0.747 0.408 0.762 0.368 0.767 0.301 0.778 0.214 0.789 0.089 0.798 0 0.811 0 0.823 0
Latent Btuh 16,200 17,700 15,100 16,800 13,800 15,800 13,100 15,100 12,100 14,300 11,100 13,300 10,300 12,300 9,300 11,400 8,400 10,400
Lbs. H20/hr. 15.3 16.7 14.2 15.8 13.0 14.9 12.4 14.2 11.4 13.5 10.5 12.5 9.7 11.6 8.8 10.8 7.9 9.8
Supply Air DB 50.1 64.8 50.6 66.6 50.9 68.4 51.6 70.4 52.0 72.4 52.5 74.3 52.9 76.3 53.4 78.4 53.8 80.4
Supply Air WB 49.4 53.9 49.9 54.9 50.1 55.8 50.8 56.8 51.2 57.8 51.6 58.8 52.0 59.8 52.4 60.8 52.8 61.7
Suction PSIG4 122 114 123 115 124 116 125 118 126 120 127 121 128 122 130 124 131 125
Discharge PSIG4 284 267 304 280 325 293 347 308 370 323 394 339 419 355 445 372 473 390
75/64.1 (55% RH) Total Cooling Btuh 63,100 33,200 61,300 29,900 59,500 26,500 57,700 23,100 55,900 19,600 54,200 16,100 52,400 12,500 50,600 8,800 48,900 5,100
Sensible Btuh 43,100 12,600 42,400 10,200 41,600 7,700 40,800 5,100 40,000 2,600 39,200 (100) 38,300 (2,700) 37,500 (5,400) 36,700 (8,200)
S/T 0.683 0.38 0.692 0.34 0.699 0.29 0.707 0.22 0.716 0.13 0.723 0 0.731 0 0.741 0 0.751 0
Latent Btuh 20,000 20,600 18,900 19,700 17,900 18,800 16,900 18,000 15,900 17,000 15,000 16,200 14,100 15,200 13,100 14,200 12,200 13,300
Lbs. H20/hr. 18.9 19.4 17.8 18.6 16.9 17.7 15.9 17.0 15.0 16.0 14.2 15.3 13.3 14.3 12.4 13.4 11.5 12.5
Supply Air DB 51.5 65.9 51.9 67.8 52.4 69.6 52.9 71.5 53.3 73.5 53.8 75.5 54.2 77.5 54.7 79.5 55.1 81.6
Supply Air WB 50.8 55.0 51.3 56.0 51.7 57.0 52.2 58.0 52.6 59.0 53.0 60.0 53.4 61.0 53.8 61.9 54.2 62.9
Suction PSIG4 126 117 126 119 127 120 128 121 129 123 130 124 132 126 133 127 134 128
Discharge PSIG4 286 270 306 283 327 297 349 311 372 326 396 342 421 359 447 376 475 394
75/65.5 (60% RH) Total Cooling Btuh 64,600 34,600 62,800 31,400 61,000 28,000 59,200 24,600 57,500 21,100 55,700 17,600 53,900 14,000 52,200 10,300 50,400 6,600
Sensible Btuh 40,900 11,300 40,100 8,800 39,600 6,400 38,500 3,700 37,700 1,200 36,900 (1,500) 36,000 (4,100) 35,200 (6,800) 34,400 (9,600)
S/T 0.633 0.327 0.639 0.280 0.649 0.229 0.650 0.150 0.656 0.057 0.662 0 0.668 0 0.674 0 0.683 0
Latent Btuh 23,700 23,300 22,700 22,600 21,400 21,600 20,700 20,900 19,800 19,900 18,800 19,100 17,900 18,100 17,000 17,100 16,000 16,200
Lbs. H20/hr. 22.4 22.0 21.4 21.3 20.2 20.4 19.5 19.7 18.7 18.8 17.7 18.0 16.9 17.1 16.0 16.1 15.1 15.3
Supply Air DB 52.8 67.0 53.3 68.9 53.5 70.6 54.2 72.7 54.7 74.6 55.1 76.6 55.6 78.6 56.0 80.6 56.4 82.7
Supply Air WB 52.2 56.2 52.7 57.2 52.9 58.2 53.6 59.2 54.0 60.2 54.4 61.1 54.8 62.1 55.2 63.1 55.6 64.1
Suction PSIG4 129 120 130 122 130 123 131 124 132 126 134 127 135 129 136 130 137 131
Discharge PSIG4 287 274 308 287 329 300 351 315 374 330 398 346 423 362 449 379 476 397
75/66.7 (65% RH) Total Cooling Btuh 66,200 36,100 64,400 32,800 62,500 29,500 60,800 26,100 59,000 22,600 57,200 19,100 55,400 15,500 53,700 11,800 51,900 8,100
Sensible Btuh 38,600 9,900 37,800 7,400 37,300 5,100 36,200 2,400 35,400 (200) 34,600 (2,800) 33,700 (5,500) 32,900 (8,200) 32,100 (11,000)
S/T 0.583 0.27 0.587 0.23 0.597 0.17 0.595 0.09 0.600 0 0.605 0 0.608 0 0.613 0 0.618 0
Latent Btuh 27,600 26,200 26,600 25,400 25,200 24,400 24,600 23,700 23,600 22,800 22,600 21,900 21,700 21,000 20,800 20,000 19,800 19,100
Lbs. H20/hr. 26.0 24.7 25.1 24.0 23.8 23.0 23.2 22.4 22.3 21.5 21.3 20.7 20.5 19.8 19.6 18.9 18.7 18.0
Supply Air DB 54.1 68.1 54.6 70.0 54.8 71.8 55.5 73.8 56.0 75.7 56.4 77.7 56.9 79.7 57.3 81.7 57.7 83.8
Supply Air WB 53.6 57.4 54.1 58.4 54.3 59.3 55.0 60.4 55.4 61.3 55.8 62.3 56.2 63.3 56.6 64.3 57.0 65.3
Suction PSIG4 132 123 133 125 134 126 135 128 136 129 137 130 138 132 139 133 141 135
Discharge PSIG4 289 277 310 290 331 304 353 318 376 334 400 349 425 366 451 383 478 401
75/68 (70% RH) Total Cooling Btuh 67,700 37,600 65,900 34,300 64,100 30,900 62,300 27,600 60,500 24,100 58,700 20,500 57,000 16,900 55,200 13,300 53,500 9,500
Sensible Btuh 36,300 8,500 35,500 6,000 35,000 3,700 33,900 1,000 33,100 (1,600) 32,300 (4,200) 31,400 (6,900) 30,600 (9,600) 29,800 (12,400)
S/T 0.536 0.226 0.539 0.175 0.546 0.120 0.544 0.036 0.547 0 0.550 0 0.551 0 0.554 0 0.557 0
Latent Btuh 31,400 29,100 30,400 28,300 29,100 27,200 28,400 26,600 27,400 25,700 26,400 24,700 25,600 23,800 24,600 22,900 23,700 21,900
Lbs. H20/hr. 29.6 27.5 28.7 26.7 27.5 25.7 26.8 25.1 25.8 24.2 24.9 23.3 24.2 22.5 23.2 21.6 22.4 20.7
Supply Air DB 55.4 69.3 55.9 71.1 56.2 72.9 56.8 74.9 57.3 76.8 57.7 78.8 58.2 80.8 58.6 82.8 59.1 84.9
Supply Air WB 55.0 58.6 55.5 59.5 55.7 60.5 56.4 61.5 56.8 62.5 57.2 63.5 57.6 64.5 58.0 65.5 58.4 66.4
Suction PSIG4 135 126 136 128 137 129 138 131 139 132 140 134 141 135 142 136 144 138
Discharge PSIG4 291 281 311 294 332 307 355 322 378 337 402 353 427 369 453 386 480 404
80/68.3 (55% RH) Total Cooling Btuh 67,900 37,800 66,100 34,500 64,300 31,100 62,500 27,700 60,700 24,200 58,900 20,700 57,200 17,100 55,400 13,400 53,700 9,700
Sensible Btuh 43,900 14,400 43,100 11,900 42,700 9,600 41,500 6,900 40,700 4,300 39,900 1,700 39,100 (1,000) 38,300 (3,700) 37,400 (6,400)
S/T 0.647 0.38 0.652 0.34 0.664 0.31 0.664 0.25 0.671 0.18 0.677 0.08 0.684 0 0.691 0 0.696 0
Latent Btuh 24,000 23,400 23,000 22,600 21,600 21,500 21,000 20,800 20,000 19,900 19,000 19,000 18,100 18,100 17,100 17,100 16,300 16,100
Lbs. H20/hr. 22.6 22.1 21.7 21.3 20.4 20.3 19.8 19.6 18.9 18.8 17.9 17.9 17.1 17.1 16.1 16.1 15.4 15.2
Supply Air DB 55.9 69.6 56.4 71.5 56.6 73.3 57.3 75.3 57.8 77.2 58.2 79.2 58.7 81.2 59.1 83.2 59.5 85.3
Supply Air WB 55.3 58.6 55.7 59.6 55.9 60.6 56.6 61.6 57.0 62.6 57.4 63.6 57.9 64.6 58.3 65.5 58.6 66.5
Suction PSIG4 136 127 136 128 137 129 138 131 139 133 140 134 142 135 143 137 144 138
Discharge PSIG4 291 280 311 293 332 306 354 321 377 336 401 352 426 368 452 385 480 403
  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

Specifications

TABLE 3AW24G4D, W30G4D and W36G4D Model

Models W24G4DA W24G4DB W24G4DC W30G4DA W30G4DB W30G4DC W36G4DA W36G4DB W36G4DC
Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 187-253 414-506 197-253 187-253 414-506 197-253 187-253 414-506
Minimum Circuit Ampacity 20.8 12.8 7.8 22.5 16 7.8 26.4 18.7 10.6
* Field Wire Size 10 14 14 10 12 14 8 10 14
Ground Wire Size 10 14 14 10 12 14 10 10 14
** Delay Fuse or Circuit Breaker Max. 30 15 10 30 20 10 35 25 15
Compressor
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 7.9/9.2 4.8/5.6 2.6 9.3/10.6 6/6.8 3.2 12.6/14.3 8.2/9.3 5.1
Branch Circuit Selection Current 12.9 6.5 3.6 14.2 9 4.2 16.7 10.5 5.8
Lock Rotor Amps 58.3 55.4 28 73 58 28 79 73 38
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor and Condenser
Fan Motor – HP/RPM/SPD 1/5-1100-1 1/5-1100-1 1/5-1100-1 1/5-1100-1 1/5-1100-1 1/5-1100-1 1/5-1100-1 1/5-1100-1 1/5-1100-1
Fan Motor – Amps 1.4 1.4 0.8 1.4 1.4 0.8 1.4 1.4 0.8
Fan – DIA/CFM 20” – 2100 20” – 2100 20” – 2100 20” – 2100 20” – 2100 20” – 2100 20” – 2000 20” – 2000 20” – 2000
Blower Motor and Evaporator
Blower Motor – HP/RPM/SPD 1/2-670-5 1/2-670-5 1/2-670-5 1/2-750-5 1/2-750-5 1/2-750-5 1/2-870-5 1/2-870-5 1/2-870-5
Blower Motor – Amps 1 1 1.2 1.1 1.1 0.6 1.9 1.9 1.2
CFM Cooling and E.S.P. 800 – 0.15 800 – 0.15 800 – 0.15 900 – 0.15 900 – 0.15 900 – 0.15 1100 – 0.15 1100 – 0.15 1100 – 0.15
Filter Size 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2
Shipping Weight – LBS. 500 500 500 530 530 530 540 540 540
Unit Charge (R-410A lb.) 5.750 5.750 5.750 6.125 6.125 6.125 7.125 7.125 7.125

* 75° C Copper wire size** Maximum time delay fuse or circuit breaker

TABLE 3BW42G4D, W48G4D and W60G4D Models

Models W42G4DA W42G4DB W42G4DC W48G4DA W48G4DB W48G4DC W60G4DA W60G4DB W60G4DC
Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 187-253 414-506 197-253 187-253 414-506 197-253 187-253 414-506
Minimum Circuit Ampacity 31.3 23.4 11.6 34.8 25 12 40.6 30.1 15.2
* Field Wire Size 8 10 14 8 10 14 8 8 12
Ground Wire Size 10 10 14 10 10 14 10 10 12
** Delay Fuse or Circuit Breaker Max. 40 30 15 50 30 15 50 40 20
Compressor
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 14.3/16.2 9.8/11.1 5.9 16.2/18.6 10.2/11.8 6.2 20/22.6 13.2/14.9 7.2
Branch Circuit Selection Current 19.9 13.6 6.1 21.8 13.8 6.3 24.4 16 7.8
Lock Rotor Amps 112 88 44 117 83.1 41 144.2 110 52
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor and Condenser
Fan Motor – HP/RPM/SPD 1/3-850-1 1/3-850-1 1/3-850-1 1/3-830-1 1/3-830-1 1/3-830-1 1/2-1000-1 1/2-1000-1 1/2-1000-1
Fan Motor – Amps 1.9 1.9 1 1.9 1.9 1 3.8 3.8 2.5
Fan – DIA/CFM 24” – 2900 24” – 2900 24” – 2900 24” – 2700 24” – 2700 24” – 2700 24” – 3400 24” – 3400 24” – 3400
Blower Motor and Evaporator
Blower Motor – HP/RPM/SPD 3/4-850-5 3/4-850-5 3/4-850-5 3/4-940-5 3/4-940-5 3/4-940-5 3/4-1040-5 3/4-1040-5 3/4-1040-5
Blower Motor – Amps 2.3 2.3 1.7 3.4 3.4 1.7 4.1 4.1 1.7
CFM Cooling and E.S.P. 1300 – 0.15 1300 – 0.15 1300 – 0.15 1450 – 0.20 1450 – 0.20 1450 – 0.20 1650 – 0.20 1650 – 0.20 1650 – 0.20
Filter Size 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2
Shipping Weight – LBS. 500 500 500 530 530 530 550 550 550
Unit Charge (R-410A lb.) 6.375 6.375 6.375 7.500 7.500 7.500 10.250 10.250 10.250

* 75° C Copper wire size** Maximum time delay fuse or circuit breaker

TABLE 4Wiring Diagram Index

Unit Model No. Basic Wiring Diagram
W24G4DA 4085-173
W24G4DB 4085-273
W24G4DC 4085-396
W30G4DA 4085-173
W30G4DB 4085-273
W30G4DC 4085-396
W36G4DA 4085-173
W36G4DB 4085-273
W36G4DC 4085-396
W42G4DA 4085-173
W42G4DB 4085-273
W42G4DC 4085-396
W48G4DA 4085-173
W48G4DB 4085-273
W48G4DC 4085-396
W60G4DA 4085-171
W60G4DB 4085-271
W60G4DC 4085-394

TABLE 5Thermostat Wire Size

Transformer VA FLA Wire Gauge Maximum Distance in Feet
20 gauge 45
18 gauge 60
55 2.3 16 gauge 100
14 gauge 160
12 gauge 250

TABLE 6Wall Thermostat

Thermostat Predominant Features
8403-060* (1120-445) 3 Stage Cool; 3 Stage Heat Programmable/Non-Programmable Electronic HP or Conventional Auto or Manual changeover
8403-082 (VT8600U5500B) 2 stage Cool; 2 stage Heat Programmable/Non-Programmable Electronic HP or Conventional, Auto or Manual changeover with Occupancy Sensor, BACnet
8403-084 (VT8600U5000B) 2 stage Cool; 2 stage Heat Programmable/Non-Programmable Electronic HP or Conventional, Auto or Manual changeover with BACnet
8403-089 (T4 Pro) 1 stage Cool; 1 stage Heat – Heat Pump 1 stage Cool; 1 stage Heat – Conventional Programmable/Non-Programmable Electronic Auto or Manual changeover
8403-090 (T6 Pro) 2 stage Cool; 3 stage Heat – Heat Pump 2 stage Cool; 2 stage Heat – Conventional Programmable/Non-Programmable Electronic Auto or Manual changeover
8403-091 (T701-FEMA) 1 stage Cool, 1 stage Heat Non-Programmable FEMA use
8403-092 (T6 Pro Wi-Fi) 2 stage Cool, 3 stage Heat – Heat Pump 2 stage Cool, 2 stage Heat – Conventional Programmable/Non-Programmable Electronic Auto or Manual changeover Wi-Fi

* Integrated thermostat and humidistat in one

TABLE 7Humidistat

Thermostat Predominant Features
8403-060* (1120-445) Programmable Thermostat (above) with Integral Humidistat
8403-038 (H600A 1014) Humidistat SPDT
8403-047 (H200 10-21-10) Dehumidistat – Electronic (range 10% to 90% with adjustable stops, 3.6% differential)

* Integrated thermostat and humidistat in one

TABLE 8Dehumidification Relay Logic Board

24V Terminal Block Connections G Y 3 W1 Outputs from Board
Inputs to Board G Y D W2 G1 TWV YO
Cooling Mode Unoccupied X X X X
Cooling Mode Occupied X X X X
Cooling Mode j With Dehum X X X X X
1st Stage Heating Unoccupied X X
1st Stage Heating Occupied X X
1st Stage Heating With Dehum X X X
2nd Stage Heating Unoccupied X X
2nd Stage Heating Occupied X X
2nd Stage Heating k With Dehum X X X
Dehumidification Unoccupied X l l l
Dehumidification Occupied X X X X
  1. Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
  2. First stage heating cancels dehumidification.
  3. If jumper on RLB is set to “1-2 full-time dehumidification”, outputs will energize. This is the factory default setting. If jumper is set to “2-3 occupied dehumidification only”, outputs will be off.

Refrigerant Charge

The correct system R-410A charge is shown on the unit rating plate.Reference Table 9 to validate proper system operation (+2 psig suction, +5 psig discharge) in cooling mode, not dehumidifation mode. However, it is recommended that if incorrect charge is suspected, the system refrigerant be reclaimed, evacuated and charged to the nameplate charge quantity and type.

The nameplate charge quantity is optimized for thermal performance and efficiency of this self-contained package system.The system operating pressures in Table 9 are based upon rated airflow across the evaporator during cooling cycle.Total system charge for these models can be found in Tables 3A and 3B on pages 12 and 13.

TABLE 9Cooling Pressure Table

Model Return Air Temperature Pressure 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125°
W24G4D 75° DB

62° WB

Low Side

High Side

126.3

301.3

127.3

322.1

128.4

344.2

129.6

367.4

130.8

391.9

132.2

417.6

133.7

444.4

135.2

472.5

136.9

501.8

138.6

532.4

140.4

564.1

80° DB

67° WB

Low Side

High Side

135.1

309.0

136.2

330.4

137.3

353.0

138.6

376.8

139.9

401.9

141.4

428.3

143.0

455.8

144.6

484.6

146.4

514.7

148.2

546.0

150.2

578.6

85° DB

72° WB

Low Side

High Side

139.8

319.8

141.0

342.0

142.1

365.4

143.5

390.0

144.8

416.0

146.3

443.3

148.0

471.8

149.7

501.6

151.5

532.7

153.4

565.1

155.5

598.9

W30G4D 75° DB

62° WB

Low Side

High Side

127.0

304.5

127.9

325.5

128.8

347.5

130.0

370.6

131.1

394.8

132.4

419.9

133.8

446.3

135.3

473.7

136.9

502.0

138.7

531.6

140.4

562.1

80° DB

67° WB

Low Side

High Side

135.8

312.3

136.8

333.8

137.8

356.4

139.0

380.1

140.2

404.9

141.6

430.7

143.1

457.7

144.7

485.8

146.4

514.9

148.3

545.2

150.2

576.5

85° DB

72° WB

Low Side

High Side

140.6

323.2

141.6

345.5

142.6

368.9

143.9

393.4

145.1

419.1

146.6

445.8

148.1

473.7

149.8

502.8

151.5

532.9

153.5

564.3

155.5

596.7

W36G4D 75° DB

62° WB

Low Side

High Side

126.1

324.8

127.2

345.4

128.2

367.4

129.3

390.5

130.5

414.8

131.6

440.2

133.0

466.9

134.3

494.7

135.7

523.9

137.1

554.1

138.6

585.6

80° DB

67° WB

Low Side

High Side

134.9

333.1

136.0

354.3

137.1

376.8

138.3

400.5

139.6

425.4

140.8

451.5

142.2

478.9

143.6

507.4

145.1

537.3

146.6

568.3

148.2

600.6

85° DB

72° WB

Low Side

High Side

139.6

344.8

140.8

366.7

141.9

390.0

143.1

414.5

144.5

440.3

145.7

467.3

147.2

495.7

148.6

525.2

150.2

556.1

151.7

588.2

153.4

621.6

W42G4D 75° DB

62° WB

Low Side

High Side

126.8

318.2

127.8

338.8

128.8

360.9

129.9

384.5

130.9

409.7

132.0

436.3

133.1

464.5

134.2

494.1

135.3

525.3

136.4

558.0

137.5

592.2

80° DB

67° WB

Low Side

High Side

135.6

326.4

136.7

347.5

137.8

370.2

138.9

394.4

140.0

420.2

141.2

447.5

142.3

479.4

143.5

506.8

144.7

538.8

145.9

572.3

147.1

607.4

85° DB

72° WB

Low Side

High Side

140.3

337.8

141.5

359.7

142.6

383.2

143.8

408.2

144.9

434.9

146.1

463.2

147.3

493.1

148.5

524.5

149.8

557.7

151.0

592.3

W48G4D 75° DB

62° WB

Low Side

High Side

124.0

320.3

124.5

341.3

125.3

363.6

126.1

387.0

127.1

411.7

128.2

437.7

129.4

464.9

130.8

493.3

132.3

523.0

133.9

553.8

135.7

586.0

80° DB

67° WB

Low Side

High Side

132.6

328.5

133.2

350.1

134.0

372.9

134.9

396.9

135.9

422.3

137.1

448.9

138.4

476.8

139.9

505.9

141.5

536.4

143.2

568.0

145.1

601.0

85° DB

72° WB

Low Side

High Side

137.2

340.0

137.9

362.4

138.7

386.0

139.6

410.8

140.7

437.1

141.9

464.6

143.2

493.5

144.8

523.6

146.5

555.2

148.2

587.9

150.2

622.0

W60G4D 75° DB

62° WB

Low Side

High Side

124.8

326.7

125.9

347.6

127.0

369.9

128.1

393.7

129.2

419.0

130.3

445.6

131.5

473.8

132.7

503.3

133.9

534.3

135.1

566.8

136.3

600.6

80° DB

67° WB

Low Side

High Side

133.5

335.1

134.6

356.5

135.8

379.4

137.0

403.8

138.2

429.7

139.4

457.0

140.6

485.9

141.9

516.2

143.2

548.0

144.5

581.3

145.8

616.0

85° DB

72° WB

Low Side

High Side

138.2

346.8

139.3

369.0

140.6

392.7

141.8

417.9

143.0

444.7

144.3

473.0

145.5

502.9

146.9

534.3

148.2

567.2

149.6

601.6

Low side pressure ± 4 PSIG High side pressure ±10 PSIGTables based upon rated CFM (airflow) across the evaporator coil.If there is any doubt as to correct operating charge being in the system, the charge should be reclaimed, and the system evacuated and recharged to serial plate instruction.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506www.bardhvac.com