LUTRON Typical Wallbox Load Controls Instructions
WIRING LEGEND:
NPUT POWER (NORMAL-EMERGENCY) INPUT POWER (NORMAL) 2 #12AWG (4 mm2) 0-10V SIGNAL: 2 #18AWG (1.0 mm2) ECOSYSTEM BUS/LOOP: LUTRON CABLE C-CBL-216-GR-1 (2 #16 CONDUCTOR NON-PLENUM) OR C-PCBL-216-CL-1 (2 #16 CONDUCTOR PLENUM RATED). OTHERWISE USE 2 #16 AWG (1.5 mm2) BY OTHERS.
1-WAY RF COMMUNICATION2-WAY RF COMMUNICATION 2 #18AWG (1.0 mm2)E CAT5E OR BETTER CABLE FOR LUTRON NETWORK TERMINATED WITH RJ45 CONNECTORS (TO BE PROVIDED BY OTHERS). 328 ft (100 m) MAXIMUM RUN.
WIRING NOTES:
LUTRON LIGHTING MANAGEMENT NETWORKWHEN A LIGHTING MANAGEMENT NETWORK (LMN) IS REQUIRED TO ENABLE COMMUNICATIONS BETWEEN INDIVIDUAL LIGHT MANAGEMENT HUBS (LMH) AND BETWEEN LMH AND THE SYSTEM SERVER/DESKTOP/LAPTOP (Q-MANAGER). THE LMN REQUIRES A DEDICATED LAN OR VLAN. IT IS THE RESPONSIBILITY OF THE NETWORK PROVIDER TO ENSURE THE RELIABILITY AND SECURITY OF THE LMN. CAT5E OR BETTER ETHERNET CABLE TO BE RUN FOR DEDICATED LMN TERMINATED WITH RJ45 CONNECTORS (PROVIDED BY OTHERS). THE NUMBER OF ETHERNET HOPS/SEGMENTS BETWEEN THE SERVER/DESKTOP/LAPTOP (Q-MANAGER) AND ANY LMN NODE SHALL NOT EXCEED 6. TOTAL LENGTH OF ETHERNET CABLE SHALL NOT EXCEED 328 FT (100M) POINT-TO-POINT. IF LONGER RUNS ARE REQUIRED, MULTI-MODE FIBER OPTIC CABLE CAN BE USED INSTEAD WITH APPROPRIATE FIBER OPTIC CONNECTORS (PROVIDED BY OTHERS). CONSULT WITH NETWORK PROVIDER FOR STANDARD ETHERNET AND FIBER OPTIC WIRING RULES FOR DISTANCE AND SEPARATION AS WELL AS FOR PLACEMENT OF SWITCHES, ROUTERS, HUBS, ETC. FOR MORE INFORMATION REGARDING NETWORK EQUIPMENT REQUIREMENTS AND NETWORK CONFIGURATION, PLEASE REFER TO THE QUANTUM LIGHTING MANAGEMENT NETWORK SPECIFICATION SHEET OR CONTACT LUTRON. CONCEPT DRAWING NOTES: CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE VERIFIED IN ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW SCHEDULES/DETAILS. LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL. LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS COMBINATION. TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON’S PRODUCT COMPATIBILITY MATRIX ON-LINE AT WWW.LUTRON.COM/LED. TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME A-SERIES LED DRIVERS USED WITH APPROPRIATE LUTRON CONTROLS. THE HI-LUME A-SERIES LED DRIVER CAN BE USED ON PRODUCTS UNDER 40 WATTS WITH SUITABLE MOUNTING LOCATIONS. PLEASE REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMATION. IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION. IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. A-SERIES OR ELV PRODUCTS PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION. TYPICAL HUB FLUSH MOUNT AND SURFACE MOUNT OPTIONS AVAILABLEBACNET INTEGRATION AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON THE SAME FLOORTYPICAL HUB FLUSH MOUNT AND SURFACE MOUNT OPTIONS AVAILABLE BACNET INTEGRATION AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON THE SAME FLOORTYPICAL WALLBOX LOAD CONTROLS MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOORMRF2S-6ANS-WH MAESTRO WIRELESS 6A, 120V COMMERCIAL SWITCH (1 GANG US BACKBOX BY OTHERS)LOCATION TBDMRF2S-8ANS120-WH MAESTRO WIRELESS 8A, 120V~ COMMERCIAL SWITCH (1 GANG US BACKBOX BY OTHERS)LOCATION TBDMRF2S-8S-DV-WH MAESTRO WIRELESS 8A, 120/277V~ COMMERCIAL SWITCH (1 GANG US BACKBOX BY OTHERS)LOCATION TBD
MRF2S-6CL-WH MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLEL DIMMER, 120V~ 150 W DIMMABLE CFL/LED/ 600W INCANDESCENT/HALOGEN (1 GANG US BACKBOX BY OTHERS) LOCATION TBD
RMJS-8T-DV-B POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-8TN-DV-B POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-ECO32-SZ POWPAK SINGLE ZONE CONTROL MODULE W/ ECOSYSTEM 120-277V~, 50/60 Hz (1) PARTIAL BUS SUPPLY FOR UP TO 32 BALLASTS/INTERFACES DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D)(87mm X 72mm X 32mm)LOCATION TBD TYPICAL IN-WALL SENSOR DEVICES (VACANCY-ONLY MODELS ALSO AVAILABLE) MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR
MRF2S-8SD010-WH 120/277V~, 50/60 Hz MAESTRO SENSOR 0-10V DIMMER OCCUPANCY/VACANCY SENSOR SINGLE POLE/MULTI-LOCATION *NEUTRAL WIRE REQUIRED AUTO ON/AUTO OFF OR MANUAL ON/AUTO OFF (1 GANG US BACK BOX BY OTHERS) LOCATION TBD
MRF2S-8SS-WH 120/277V~, 50/60 Hz MAESTRO SENSOR SWITCH OCCUPANCY/VACANCY SENSOR SINGLE POLE/MULTI-LOCATION *NEUTRAL WIRE REQUIRED AUTO ON/AUTO OFF OR MANUAL ON/AUTO OFF (1 GANG US BACK BOX BY OTHERS) LOCATION TBD TYPICAL PER FIXTURE LOAD CONTROL MODULES & SENSORS MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR FCJS-010 TO WIRED SENSOR POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
FCJS-ECO TO WIRED SENSOR POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR ECOSYSTEM (1) PARTIAL BUS SUPPLY FOR UP TO 3 BALLASTS/INTERFACES DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD
TYPICAL CLEAR CONNECT WIRELESS FIXTURE CONTROLS (OEM SUPPLIED) MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR TYPICAL WIRELESS RECEPTACLES MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR CAR2S-20-DTR-WH 20A TAMPER RESISTANT, DUPLEX RECEPTACLE 120V~, 50/60 HzDUAL SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG US BACKBOX BY OTHERS) LOCATION TBD
TYPICAL WIRELESS RECEPTACLES
MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR
LUT-ALCR LVS CONTROLS SHUNT RELAY FOR USE WITH SWITCHING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
LUT-ATS-DLVS CONTROLS TRANSFER SWITCH FOR USE WITH LINE VOLTAGE DIMMING LOADSREFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS